Fan Trays; Power Supplies - Cisco SD2008T-NA Installation Manual

Hardware installation guide
Hide thumbs Also See for SD2008T-NA:
Table of Contents

Advertisement

Cisco Nexus 2232PP
Table 1-13
Power Supply
DC power supply with front-to-back airflow
DC power supply with back-to-front airflow
Figure 1-12 on page 1-12
page 1-13
power supply with front-to-back airflow.
You can order the Cisco Nexus 2232PP FEX with AC power supplies that have front-to-back or
back-to-front airflow for cooling or DC power supplies that have front-to-back airflow. The
back-to-front airflow components have a black stripe on their front surface for easy visual identification.
The front-to-back airflow components do not have a black stripe.
Table 1-5 on page 1-12
FEXs.
Caution
Be sure that all of the power supply and fan tray modules in the same chassis have the same airflow
direction and that the air intake for those modules is positioned on a cool aisle. If you install a module
that uses a different direction of airflow from the other modules in your system, you will see an error
message. If you position a chassis with its modules taking cooling air from a warm aisle, the switch can
reach an overtemperature state and shut down.
If one power supply is installed in the chassis, but the other power supply slot is empty, you should use
a blank filler panel (N2200-P-BLNK) to cover the empty slot.
power supply filler panel.
For power supply specifications, see
"Removing and Installing Power Supplies" section on page

Fan Trays

The Cisco Nexus 2232PP FEX has one fan tray that is hot swappable during operations. Depending on
whether there is a cold aisle in front of or in back of the chassis, you can order front-to-back airflow or
back-to-front airflow for the fan tray and the power supplies in the same chassis.
numbers for each of the fan trays that you can use with this chassis.
Table 1-14
Description
Front-to-back airflow
Back-to-front airflow
To see the components used when installing a fan tray, see
Figure 1-26
Cisco Nexus 2000 Series Hardware Installation Guide
1-26
Power Supplies for the Cisco Nexus 2200 Platform Chassis
shows an AC power supply with front-to-back airflow.
shows an AC power supply with back-to-front airflow.
lists the power supplies that you can order with the Cisco Nexus 2200 Platform
Fan Trays for the Cisco Nexus 2232PP FEX
(back-to-front airflow).
Chapter 1
Using a Fabric Extender with a Cisco Nexus 5000 Series Switch
Part Number
N2200-PDC-400W
N2200-PDC-350W-B
Figure 1-15 on page 1-14
Table B-1 on page
B-2. To replace a power supply, see the
3-17.
Part Number
N2K-C2232-FAN
N2K-C2232-FAN-B
Figure 1-25
Figure 1-13 on
Figure 1-14 on page 1-13
shows a DC
shows a blank
Table 1-14
lists the part
(front-to-back airflow) or
OL-19013-05

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

Sfe2000pSlm2024t-naSr2016t-naNexus 2000 series

Table of Contents