Cisco Nexus 2248TP-E
Figure 1-6
1
1
Handle
2
FAIL (top) and OK (bottom) LEDs
3
Ejector latch
You can order the Cisco Nexus 2248TP-E FEX with AC power supplies that have front-to-back or
back-to-front airflow for cooling or DC power supplies that offer front-to-back airflow. The
back-to-front airflow components have a black stripe on their front surface for easy visual identification.
The front-to-back airflow components do not have a black stripe.
Caution
Be sure that all of the power supply and fan tray modules in the same chassis have the same airflow
direction and that the air intake for those modules is positioned on a cool aisle. If you install a module
that uses a different direction of airflow from the other modules in your system, you will see an error
message. If you position a chassis with its modules taking cooling air from a warm aisle, the switch can
reach an overtemperature state and shut down.
If one power supply is installed in the chassis, but the other power supply slot is empty, you should use
a blank filler panel (part number N2200-P-BLNK) to cover the empty slot.
power supply filler panel.
Cisco Nexus 2000 Series Hardware Installation Guide
1-6
DC Power Supply with Back-to-Front Airflow for the Cisco Nexus 2200 Platform
Chassis
A 2
2 0
P C
- 4 0
0
2
5
3
4
Chapter 1
Using a Fabric Extender with a Cisco Nexus 5000 Series Switch
4
Black stripe (back-to-front airflow)
5
AC power receptacle
Figure 1-7
shows a blank
OL-19013-05