Programming - Aquacal Great Big Bopper Operation And Installation Manual

Hide thumbs Also See for Great Big Bopper:
Table of Contents

Advertisement

Page 24

4.5 Programming

CAUTION
- Failure to heed the following may result in equipment damage.
Service Level Programming must only be attempted by authorized service centers. If
adjustments are deemed necessary, contact installing dealer or AquaCal AutoPilot Customer
Support. Un-authorized adjustments in the Service Menu (beyond the "LOC" menu) will void
factory warranty.
The time delay should only be de-activated for diagnostic convenience, and must be re-activated
prior to placing heat pump back in service. Failure to reset time delay could result in permanent
damage to the heat pump compressor.
Using the back door entry will reset all settings to factory default; including any installer entered
configuration. See section entitled "Re-Setting Heat Pump ("Back Door" Entry)" on page 27 for
more information. Re-entry of all custom site condition settings will be required when using this
re-set.
The heat pump allows for two levels of programming; User-level and Service-level programming. This
section describes programming for site specific conditions in the Service-level programming.
The installer must insure the programming is compatible with any external controllers and confirm heat
pump starts and operates per manufacturer's specifications. Unless instructed by AquaCal AutoPilot
Technical Support Group, the installer should not adjust sensor calibration or dead-band values.
Figure 17

Advertisement

Table of Contents
loading

This manual is also suitable for:

Autopilot great big bopper

Table of Contents