4.4.e Ground-Fault Protection
Local codes and regulations may require the use of a ground fault interruption device (GFI Circuit
Breaker). Nuisance tripping of these devices is common and not covered under the terms of the
Manufacturer's warranty.
4.4.f External Controls / Equipment
The Great Big Bopper allows external equipment to control the heat pumps "ON" / "OFF" functionality.
A direct connection for external controllers has been provided on the microprocessor board.
1) Connect the external controller to the terminal block of the microprocessor board using at
least 18-guage low voltage.
2) For a two-wire controller (which has a thermostat) – Connect to the "Y" and "Z" connections
of the block labeled "X-Y-Z". See Figure 16.
3) For a three-wire controller (which does not have a thermostat) – Connect to the block
labeled "FS-2".
4) Program the heat pump to accept an external controller's signal. See section entitled
"Configuring for External Controller" on page 25 for more information.
Data Plate Example
Figure 15