Returning Equipment - HP Integrity Superdome SX1000 User Manual

User guide, sixth edition - hp integrity superdome; hp9000 superdome
Hide thumbs Also See for Integrity Superdome SX1000:
Table of Contents

Advertisement

Table 2-1
Available Power Options
Source
Option
Type
6
3-phase
7
3-phase
a. A dedicated branch circuit is required for each PDCA installed.
Table 2-2
Option 6 and 7 Specifics
PDCA
Attached Power Cord
Part Number
A5201-69023
OLFLEX 190 (PN 600804) is a
(Option 6)
2.5 meter multi conductor,
600 volt, 90 degree C, UL and
CSA approved, oil resistant
flexible cable. (8 AWG 60 A
capacity)
A5201-69024
H07RN-F (OLFLEX PN
(Option 7)
1600130) is a 2.5 meter heavy
duty neoprene jacketed
harmonized European flexible
cable. (4 mm

Returning Equipment

If the equipment is found to be damaged, use the original packing material to repackage the cabinet for
shipment. If the packing material is not available, contact the local Hewlett-Packard Sales and Support Office
regarding shipment.
Before shipping, place a tag on the container (or equipment) to identify the owner and the service to be
performed. Include the equipment model number and the full serial number, if applicable. The model number
and the full serial number are printed on the System Information Labels located at the bottom front of the
cabinet.
WARNING
Do not attempt to push the loaded cabinet up the ramp onto the pallet. Three people
are required to push the cabinet up the ramp and position it on the pallet. Check the
condition of the loading/unloading ramp before use.
Chapter 2
Source Voltage
(nominal)
Required
Voltage range
four-wire
200-240 VAC,
phase-to-phase,
50/60 Hz
Voltage range
five-wire
200-240 VAC,
phase-to-neutral,
50/60 Hz
2
32A capacity)
Input Current
PDCA
Per Phase
200-240 VAC
44A Maximum
per phase
24A Maximum
per phase
Attached Plug
Mennekes
ME 460P9
(60 A capacity)
Mennekes
ME 532P6-14
(32A capacity)
Installing the System
Unpacking and Inspecting
Power Receptacle
Required
a
Connector and plug
provided with a 2.5-meter
power cable. Electrician
must hard-wire receptacle to
60A site power.b,d
Connector and plug
provided with a 2.5-meter
power cable. Electrician
must hard-wire receptacle to
32A site power.b,d
Receptacle
Required
Mennekes
ME 460R9
(60 A capacity)
Mennekes
ME 532R6-1500
(32 A capacity)
35

Advertisement

Table of Contents
loading

Table of Contents