DKS 6500 Series Owner's Manual

DKS 6500 Series Owner's Manual

Vehicular swing gate operator
Hide thumbs Also See for 6500 Series:

Advertisement

Owner's Manual
Series 6500
Series 6500
Vehicular Swing Gate Operator
Copyright 2008 DoorKing, Inc. All rights reserved.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 6500 Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for DKS 6500 Series

  • Page 1 Owner’s Manual Series 6500 Series 6500 Vehicular Swing Gate Operator Copyright 2008 DoorKing, Inc. All rights reserved.
  • Page 3: Specifications

    July 12, 2008. 31” Use this manual with the following models only: 6500-080, 6500-081, 6500-082*, 6500-083*, 6500-084, 6500-085, 6500-086*, 6500-087*, 6500-088, 6500-089*, 6500-090, 6500-091*, 6500-092, 6500-093*, 6500-094, 6500-095*, 6500-096, 6500-097*, 6500-098, 6500-099*. *Optional Convenience Open System DoorKing, Inc. reserves the right to make changes in the products described in this manual without notice and without obligation of DoorKing, Inc. to notify any persons of any such revisions or changes.
  • Page 4: Table Of Contents

    1.7 Installation of Warning Signs SECTION 2 - WIRING 2.1 High Voltage Wire Runs 2.2 High Voltage Terminal Connections 2.3 Control Wiring 2.4 Loop Detector Wiring 2.5 Auxiliary Device Wiring 2.6 Primary / Secondary (Dual) Gate Connection 2.7 Main Terminal Description 11-12 6500-065-K-7-08...
  • Page 5 SECTION 5 - OPTIONAL CONVENIENCE OPEN ADJUSTMENTS 5.1 Operating Mode 5.2 DC System Description 5.3 DIP-Switch Settings SECTION 6 - MAINTENANCE AND TROUBLESHOOTING 6.1 Maintenance 6.2 Troubleshooting 6.3 Built-in Diagnostics 6.4 Accessory Items Model 6500’s Wiring Diagrams 6500-065-K-7-08 26-27 32-33 35-44...
  • Page 6: Instructions Regarding Intended Installation

    3. One or more non-contact sensors shall be located where the risk of entrapment or obstruction exist, such as the perimeter reachable by a moving gate or barrier. NO ONE SHOULD CROSS THE PATH OF THE MOVING GATE. 6500-065-K-7-08...
  • Page 7: Important Notices

    Do not allow children to play in the area of the operator or to play with any gate-operating device. • To remove the gate operator from service, operate the gate to the full open position and then shut off power to the operator at the service panel. 6500-065-K-7-08...
  • Page 8: Ul325 Entrapment Protection

    A, B1, B2, D or E A, B1, B2, C or D ST AT E PR IS ON Secondary Protection A, B1, B2, C or D A, B1, B2, C or D A, B1, B2, C, D or E 6500-065-K-7-08...
  • Page 9: Glossary

    ENTRAPMENT - The condition when an object is caught or held in a position that increases the risk of injury. 6500-065-K-7-08...
  • Page 10: Swing Gate Requirements

    Gates shall have smooth bottom edges, with vertical bottom edged protrusions not exceeding 0.50 inches. ASTM F2200 4.3 Pedestrians must be supplied with a separate With the hinge mounted on the corner of the pilaster, the entrapment area eliminated and protection is not required for this area. Closed Gate 6500-065-K-7-08...
  • Page 11: Swing Gate Protection

    Automatic Exit Loop (Optional) will provide an open command to the gate operator(s) when a vehicle is exiting the property. 6500-065-K-7-08 Non-contact Sensor Minimizes the potential of the gate closing on vehicular or other traffic that loops cannot sense.
  • Page 12: Underground Conduit Requirements

    Reinforced concrete recommended. Secondary Operator Position Concrete Pad CAUTION NEVER REMOVE HUB after manual release. Concrete pad MUST be level. Note: Bevel the edges of concrete pad to eliminate water puddling under the operator. 22” Approximate Conduit Position 6500-065-K-7-08...
  • Page 13: Type Of Installations

    Standard Compact Installation Recommended for gates up to 14 feet opening 90°. 90° 23” 2” 28” 22” Concrete Pad Concrete Pad Location 6500-065-K-7-08 46” 38.5” 29.5” Gate opens in approximately 15 seconds. 42” 32.5” 31.25” Gate opens in approximately 12 seconds.
  • Page 14 28” 22” 2” Concrete Pad is 2” away from open gate. Concrete Pad Location 34” 26.5” Gate opens in approximately ?? seconds. 42” Gate’s opening time will vary. 13” 29.5” 26.5” 23” Operator Installation 35” Operator Installation 6500-065-K-7-08...
  • Page 15: Securing Operator To Pad

    Slide control arm into elbow assembly. KEEP ARM ASSEMBLY LEVEL. Bolt gate bracket to gate. Arm assembly and gate bracket MUST be level for gate to function correctly. Gate Bracket 31” 6500-065-K-7-08 Sleeve Anchor (Not supplied) DO NOT REMOVE HUB! Control Arm Elbow...
  • Page 16: Installation Of Warning Signs

    Since building codes vary from city to city, we highly recommend that you check with your local building department prior to installing any permanent wiring to be sure that all wiring to the operator (both high and low voltage) complies with local code requirements. THIS GATE OPERATOR MUST BE PROPERLY GROUNDED!! excess excess SECTION 2 - WIRING 6500-065-K-7-08...
  • Page 17: High Voltage Terminal Connections

    This table illustrates the high voltage wire size and distance requirements. Model Voltage Type Required 6500 1/2 HP 6500 1/2 HP 6500 1/2 HP 6500 1 HP 6500 1 HP 6500 1 HP Reduce the wire distance in half for primary/secondary dual gate applications Never run high voltage and low voltage wires in the same conduit.
  • Page 18: Control Wiring

    Reverses gate during the closing cycle only. Holds gate in the full open position until obstruction is cleared. Note: SW 1, switch 3 must be ON. Fire Box Telephone Entry Key Switch Stand-Alone Keypad Stand-Alone Card Reader SW 1 6500-065-K-7-08...
  • Page 19: Loop Detector Wiring

    6 twists per foot. Reverse loop lead in wires are twisted approx. 6 twists per foot and are wired in series. 6500-065-K-7-08 9410 9409 Shadow Loop Output N.O. • If other detectors are used, use a separate power supply to power these detectors.
  • Page 20: Auxiliary Device Wiring

    1404-080) MUST be mounted in the line-of-sight of the gate operator. Using a 2351-010 Tracker Expansion Board, operator data can be sent to the access controller. Models 1833, 1835, 1837 or 1838 only. Refer to the manual 2351-065 for detailed information. 6500-065-K-7-08...
  • Page 21: Primary / Secondary (Dual) Gate Connection

    (Gray) COM 8 Primary Operator Second Terminal Operator Chassis Ground Conduit AC Power Conduit to Primary Operator Only. 6500-065-K-7-08 Secondary Operator Motor 1 (Red) Motor 2 (Blue) Neutral 3 (White) 24VAC 4 (Purple) Limit 5 (Yellow) Spare 6 (Brown) Limit 7 (Orange)
  • Page 22: Main Terminal Description

    When gate is closing, input will When gate is closing, input has no • 24-volt DC magnetic lock power is provided constantly except when the gate is opening or open. Contact 6500-065-K-7-08 SW 1 SW 1 SW 1 SW 1 SW 1...
  • Page 23: Auxiliary Terminal Description

    This terminal is used to connect the secondary operator in a dual gate application. Operator Chassis Ground 6500-065-K-7-08 1. OPEN DIRECTION NON-CONTACT SENSOR (Photocell) Stops gate movement in the open cycle. Gate resumes normal operation when the input (obstruction) is cleared.
  • Page 24: Circuit Board Adjustments

    Mode Dry Relay Contact • Dry relay contacts (terminals 10-11) can be set for Normally Open (NO) or Normally Closed (NC) operation by placing the relay shorting bar on the N.O. or N.C. pins respectively. 6500-065-K-7-08...
  • Page 25: Dip-Switch Settings

    Switch 3 Switch 4 Spare switch, not used. Leave in OFF position. 6500-065-K-7-08 SW 1 (Top 8 Switches) Direction-operator should cycle open upon initial power up and open command. Direction-operator should cycle open upon initial power up and open command.
  • Page 26: Secondary Entrapment Protection System Connection

    A secondary entrapment protection device must be installed with this operator. CAUTION DO NOT REMOVE HUB! Magnetic Sensor Activator Magnetic Close Limit Sensor Magnetic Open Limit Sensor Secondary Primary Min Max Min Max Safety Protection Photo Cells 6500-065-K-7-08...
  • Page 27: Section 4 - Operating Instructions

    POWER DC Power Switch - Turns the DC system power ON (toggle up) or OFF (toggle down). This switch is only installed on model 6500 operators with the DC convenience open system installed. GATE. Reset Switch - Used to turn off the...
  • Page 28: Shutdown Conditions

    The hard shutdown condition will remain in affect even if the audio alarm shuts off after five minutes. • After 5 minutes, the audio alarm will “chirp” every 5 seconds. This indicates that the operator is in a hard shutdown condition and the reset switch must be activated to reset the operator and silence the alarm. 6500-065-K-7-08...
  • Page 29: Hard Shutdown

    3. In the event of a primary (AC) power failure and a back-up system (DC) power failure (low charged or dead batteries for example), the system must have a release system to allow the gate to be manually operated. 6500-065-K-7-08...
  • Page 30: Manual Release

    Be sure that power is removed or shut-off prior to placing the gate operator in manual operation. CAUTION DO NOT REMOVE HUB! Unlock the cover and rotate sliding door. Release hub. Gate can now be manually operated. Remove release tool and place where shown. 6500-065-K-7-08...
  • Page 31: Section 5 - Optional Convenience Open Adjustments

    ONCE during adverse conditions. If continu- ous gate and access control system operation is required, refer to the DoorKing Model 2000 Inverter / Backup Power System. 6500-065-K-7-08 Automatic Open after loss of AC Power...
  • Page 32: Dc System Description

    AC power failure. DIP-Switch 3 setting will determine how operator will return to normal operation once AC power has been restored. To Secondary Operator Orange to Second Terminal #5 White to Second Terminal #7 Purple to Second Terminal #8 Green not used. Description 6500-065-K-7-08...
  • Page 33: Section 6 - Maintenance And Troubleshooting

    Loop(s) Release Secondary Reverse Device Complete System 6500-065-K-7-08 Maintenance Activate the primary (inherent) reverse system by blocking the gate with a solid object. When the gate reverses, block the gate in the opposite direction prior to the limit being reached. The entrapment alarm should activate.
  • Page 34: Troubleshooting

    If the secondary motor runs in both directions, replace the control board. If secondary motor does not run, or runs in only one direction, problem can be in the wiring from the primary to secondary operator, bad secondary motor or motor capacitor. Possible Solution(s) 6500-065-K-7-08...
  • Page 35 • Check that the DC system power switch is in the ON position. AC power outage. • Check the batteries for proper voltage. Replace if necessary. • Replace the DC system circuit board. 6500-065-K-7-08 Possible Solution(s)
  • Page 36: Built-In Diagnostics

    (1/2 HP motor - 2 loops, 1 HP motor - 1 loop). 6.4 Accessory Items The following accessory items are available for the model 6500 swing gate operator. Contact Sensors - For use as a secondary entrapment protection device. Miller Edge, Inc., MGO20, MGR20, MGS20 Photo Cell - Non-contact (photo-cells) sensors for use as a secondary entrapment protection device.
  • Page 37 Model 6500 1/2 HP 115 VAC Magnetic Magnetic Close Open Sensor Sensor Yellow Orange Orange Yellow EXIT LOOP TIME DELAY REV SENSE REV SENSE SECONDARY PRIMARY REVERSE LOOP Current Sensor 4405 Push to Operate Ground Neutral Power Yellow Alarm AC Power...
  • Page 38 Model 6500 1/2 HP 115 VAC / Convenience Open Magnetic Magnetic Close Open Sensor Sensor Yellow Orange Diode EXIT LOOP TIME DELAY REV SENSE REV SENSE SECONDARY PRIMARY REVERSE LOOP Current Sensor 4405 Push to Operate Ground Neutral Power Yellow...
  • Page 39 Model 6500 1/2 HP 230 / 460 VAC Magnetic Magnetic Close Open Sensor Sensor Yellow Orange Orange Yellow EXIT LOOP TIME DELAY REV SENSE REV SENSE SECONDARY PRIMARY REVERSE LOOP Current Sensor 4405 Push to Operate Ground Neutral Power Yellow...
  • Page 40 Model 6500 1/2 HP 230 / 460 VAC / Convenience Open Magnetic Magnetic Close Open Sensor Sensor Yellow Orange Diode EXIT LOOP TIME DELAY REV SENSE REV SENSE SECONDARY PRIMARY REVERSE LOOP Current Sensor 4405 Push to Operate Ground Blue...
  • Page 41 Model 6500 1 HP 115 VAC Magnetic Magnetic Close Open Sensor Sensor Yellow Orange Orange Yellow EXIT LOOP TIME DELAY REV SENSE REV SENSE SECONDARY PRIMARY REVERSE LOOP Current Sensor 4405 Push to Operate Ground Neutral Power Yellow Alarm AC Power...
  • Page 42 Model 6500 1 HP 115 VAC / Convenience Open Magnetic Magnetic Close Open Sensor Sensor Yellow Orange Diode EXIT LOOP TIME DELAY REV SENSE REV SENSE SECONDARY PRIMARY REVERSE LOOP Current Sensor 4405 Push to Operate Ground Neutral Power Yellow...
  • Page 43 Model 6500 1 HP 230 / 460 VAC Magnetic Magnetic Close Open Sensor Sensor Yellow Orange Orange Yellow EXIT LOOP TIME DELAY REV SENSE REV SENSE SECONDARY PRIMARY REVERSE LOOP Current Sensor 4405 Push to Operate Ground Neutral Power Yellow...
  • Page 44 Model 6500 1 HP 230 / 460 VAC / Convenience Open Magnetic Magnetic Close Open Sensor Sensor Yellow Orange Diode EXIT LOOP TIME DELAY REV SENSE REV SENSE SECONDARY PRIMARY REVERSE LOOP Current Sensor 4405 Push to Operate Ground Blue...
  • Page 45 Model 6500 1/2 HP Secondary Operator 1/2 HP Ground Model 6500 1/2 HP Secondary Operator/Convenience Open 1/2 HP 50uf Capacitor Blue Ground White 6500-065-K-7-08 Magnetic Close 50uf Capacitor Sensor Blue Blue White Magnetic Close Sensor Blue DC Power Magnetic Open...
  • Page 46 Model 6500 1 HP Secondary Operator 1 HP Ground Model 6500 1 HP Secondary Operator/Convenience Open 1 HP Blue White Ground Magnetic Close Sensor Blue White Magnetic Magnetic Close Open Sensor Sensor DC Power Magnetic Open Sensor Diode Orange Purple...
  • Page 48 Owner’s Manual Series 6500 Series 6500 Vehicular Swing Gate Operator DoorKing, Inc. 120 Glasgow Avenue Inglewood, California 90301 U.S.A. Phone: 310-645-0023 Fax: 310-641-1586 6500-065-K-7-08 www.doorking.com...