PI150 series frequency inverter operation manual 1.Foreword Thank you for choosing Powtran PI150 series fundamental form frequency inverter. The diagrams of these operating instructions are used for convenience of explanation and may be slightly different from the product due to product upgrades. Please refer to the actual product.
Indicator light Name Running indicator light * ON: The inverter is working * OFF: The inverter stops Forward/reverse running light Status FWD/REV * ON: In forward status light * OFF: In reversal status Frequency indicator Current indicator 4.2 Operation panel button description Sign Name Function...
7. Parameter List In PI150 series frequency inverters ,some parameters are "manufacturer reserved", and their serial numbers are not listed in the function parameter table,which leads to the discontinuity of some parameter serial numbers in the table. For the parameters not introduced in the manual, please do not attempt to modify them to avoid causing errors.
Page 4
d0.05 Output power Calculated value for motor output power 0.1kW d0.06 Output torque Motor output torque percentage 0.1% d0.07 DI input status DI input status d0.08 DO output status DO output status d0.09 AI1 voltage AI1 input voltage value 0.01V d0.12 Count value Actual pulse count value in counting function...
Page 5
Depends on ☆ F0.18 Carrier Frequency 0.5kHz to 16.0kHz models Maximum output ★ F0.19 50.00Hz to 320.00Hz 50.00Hz frequency Upper limit frequency 0:F0.21setting; 1:Analog AI1 setting; ★ F0.20 source 5: Communications reference F0.23 (Lower limit frequency) to F0.19 (Maximum ☆ F0.21 Upper limit frequency 50.00Hz...
Page 6
vice versa. When the terminal is active, the PID integral adjustment function is PID integral pause paused, but the proportion and differential adjustments of PID are still valid. Switch between frequency source When the terminal is active, the frequency source A is replaced by the master setting and preset frequency (F0.01) preset frequency...
Page 7
When the count reaches the set value of E0.08, output ON signal. Setup counter arrive Specifies the count value reaches. Specifies the count When the count reaches the set value of E0.09, output ON signal. value reaches Counting Function Reference E0 group. When the actual length of the detection of more than E0.05 set length, Length arrival output ON signal.
Page 8
☆ F3.10 Braking current 0% to 100% ☆ F3.11 Braking time 0.0s to 100.0s 0.0s ☆ F3.12 Braking utilization rate 0% to 100% 100% 0:Linear acceleration and deceleration; ★ F3.13 Ac/deceleration mode 1:S curve acceleration and deceleration A 2:S curve acceleration and deceleration B ★...
Page 9
Single digit: CRC mistake selection: 0: Reply verification error; 1: No reply on verification error; Communication read and write ☆ F6.13 Ten digit: Broadcast message screening selection: 0-no data selection screening; 1-screening Hundred digit: Inverter fault information read selection: 0-read; 1-no read ☆...
Page 10
☆ F7.47 Awaken delay time 0.0s t0 6500.0s 0.0s 0.00Hz ☆ F7.48 Dormancy frequency 0.00Hz t0 awaken frequency (F7.46) ☆ F7.49 Dormancy delay time 0.0s t0 6500.0s 0.0s AI1 input voltage protection lower ☆ F7.50 0.00V t0 F7.51 3.1V limit AI1 input voltage protection upper ☆...
Hundreds digit:b group display selection(The same above) Thousands digit:y group display selection(The same above) Tens thousands digit:L group display selection(The same above) Units digit:Reserved Personality parameter Tens digit :User’s change parameter display selection ☆ y0.03 group display selection 0:Not display 1:Display Function code 0: Modifiable ☆...
Page 14
1.The acceleration time is too short 1.Increase acceleration time 2.Manual torque boost or V/F curve is 2.Adjust manual torque boost or not suitable V/F curve 3.The voltage is low 3.Set the voltage to the normal range 4.The short-circuit or earthing of 4.Eliminate peripheral faults inverter output happens Acceleration...
Page 15
running time initialization function parameters arrival fault Input custom fault 1 signal through the Err.27 Custom fault 1 Reset run multi-function terminal DI Input custom fault 2 signal through the Err.28 Custom fault 2 Reset run multi-function terminal DI Total power-on Total power-on time reaches the set Clear history information by using Err.29...