INVT Goodrive880 Series Hardware Manual
INVT Goodrive880 Series Hardware Manual

INVT Goodrive880 Series Hardware Manual

Single-drive vfd
Hide thumbs Also See for Goodrive880 Series:
Table of Contents

Advertisement

Quick Links

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Goodrive880 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for INVT Goodrive880 Series

  • Page 2 Goodrive880 Series Single-Drive VFD Hardware Manual Change history Change description Version Release date First release. V1.0 March 2024...
  • Page 4: Preface

    Goodrive880-11 series is the single-drive unit of Goodrive880 Pro series. If not otherwise specified, the single-drive unit in this manual refers to the single-drive unit of Goodrive880 series, that is, Goodrive880-11 series product. The rated power of a single unit is 4 –710kW, and the max. parallel power can be 1300kW.
  • Page 5: Table Of Contents

    Goodrive880 Series Single-Drive VFD Hardware Manual Contents Contents Preface ................................. i Contents ..............................ii 1 Safety precautions .............................1 1.1 Safety declaration ..............................1 1.2 Safety definition ..............................1 1.3 Warning symbols ..............................1 1.4 Safety guidelines ..............................1 1.4.1 Delivery and installation ..........................2 1.4.2 Commissioning and running ........................
  • Page 6 Goodrive880 Series Single-Drive VFD Hardware Manual Contents 3.3.6 Fastening torque ............................29 3.3.7 Checklist ..............................29 4 Electrical installation ..........................31 4.1 Safety notes................................. 31 4.2 Insulation inspection ............................31 4.3 EMC regulations ..............................32 4.3.1 Power cable............................... 33 4.3.2 Control cable ............................. 33 4.3.3 Wiring suggestions ............................
  • Page 7: Contents

    Goodrive880 Series Single-Drive VFD Hardware Manual Contents 7.1 Periodical inspection ............................63 7.1.1 Overview ..............................63 7.1.2 Required tools ............................63 7.1.3 Maintenance cycle ............................ 63 7.2 Replacement of wearing parts ........................... 65 7.2.1 Capacitor ..............................65 7.2.2 Electrolytic capacitor replacement ......................66 7.2.3 Cooling fan ..............................
  • Page 8 Goodrive880 Series Single-Drive VFD Hardware Manual Contents 2.8 Structure diagram ............................... 12 2.8.1 Single-drive unit structure........................12 2.8.2 Single-drive cabinet structure ........................13 2.9 System configuration ............................17 2.9.1 Single-drive cabinet system ........................17 2.9.2 Cabinet configuration table ........................17 2.10 Electrical model selection ..........................
  • Page 9 Goodrive880 Series Single-Drive VFD Hardware Manual Contents 5.4.1 External standard interfaces ........................50 5.4.2 Detailed introduction to external interfaces ................... 50 5.5 Control unit function application ........................53 5.5.1 Function module ............................53 5.5.2 SLOT expansion application ........................54 6 Accessories .............................. 56 6.1 Function expansion module ..........................
  • Page 10: Safety Precautions

    Goodrive880 Series Single-Drive VFD Hardware Manual Safety precautions 1 Safety precautions 1.1 Safety declaration Read this manual carefully and follow all safety precautions before moving, installing, operating and servicing the product. Otherwise, equipment damage or physical injury or death may be caused.
  • Page 11: Delivery And Installation

    Goodrive880 Series Single-Drive VFD Hardware Manual Safety precautions Minimum waiting Drive unit model time 3.7–90kW 5 minutes 380V 110–200kW 15 minutes Higher than 355kW 25 minutes 55–315kW 15 minutes 690V Higher than 400kW 25 minutes Do not refit the drive unit unless authorized; otherwise fire, electric shock or other ...
  • Page 12: Maintenance And Component Replacement

    Goodrive880 Series Single-Drive VFD Hardware Manual Safety precautions supplies. High voltage presents inside the drive unit during running. Do not carry out any  operation on the drive unit during running except for keypad setup. The control terminals of the product form extra-low voltage (ELV) circuits. Therefore, you need to prevent the control terminals from connecting to accessible terminals of other devices.
  • Page 13: Product Overview

    Goodrive880 Series Single-Drive VFD Hardware Manual Product overview 2 Product overview For Goodrive880-11 series single-drive units, the rated power of a single unit is 5.5kW–710kW, while that of parallel units can be up to 1300kW. The single-drive unit products consists of rectifier, bus capacitor, IGBT, control unit, and some models carry built-in reactors.
  • Page 14: Product Nameplate And Model

    Goodrive880 Series Single-Drive VFD Hardware Manual Product overview 2.2 Product nameplate and model Figure 2-1 Product nameplate IP00 Model: GD880-11-0900-4 Power(Output): 500kW Input: AC 3PH 380V(-15%)-440V(+10%) 47Hz-63Hz Output: AC 3PH 0V-Uinput 900A S/N: Made in China Shenzhen INVT Electric Co.,Ltd Note: The preceding nameplate is a standard product nameplate example.
  • Page 15 Goodrive880 Series Single-Drive VFD Hardware Manual Product overview Light overload Heavy overload Rated value Heat application application dissipa- VFD model Input Output Output Output Output Output Output Frame volume tion current current power current power current power (kW) (kW) (kW)
  • Page 16 Goodrive880 Series Single-Drive VFD Hardware Manual Product overview Light overload Heavy overload Rated value Heat application application dissipa- VFD model Input Output Output Output Output Output Output Frame volume tion current current power current power current power (kW) (kW) (kW)
  • Page 17: Product Dimensions And Weight

    Goodrive880 Series Single-Drive VFD Hardware Manual Product overview Light overload Heavy overload Rated value Heat application application dissipa- VFD model Input Output Output Output Output Output Output Frame volume tion current current power current power current power (kW) (kW) (kW)
  • Page 18: Derating Due To Carrier Frequency

    Goodrive880 Series Single-Drive VFD Hardware Manual Product overview Figure 2-4 Derating due to altitude 1.00 0.70 0.60 1000m 4000m 2.5.3 Derating due to carrier frequency Rated power Carrier frequency (kHz) VFD model P (kW) GD880-11-0013-4-B 100% 100% 100% 100% 100%...
  • Page 19: Overload Capability

    Goodrive880 Series Single-Drive VFD Hardware Manual Product overview 2.6 Overload capability Based on the light overload continuous run current (I ), the single-drive unit can keep running for 60s at 110% of the rated current. See Figure 2-5. Figure 2-5 Light overload application...
  • Page 20 Goodrive880 Series Single-Drive VFD Hardware Manual Product overview Figure 2-8 Main circuit diagram of the E6 drive unit (+) (-) Figure 2-9 Main circuit diagram of the E7–E8 drive unit Optional (+) (-) Figure 2-10 Main circuit diagram of the E9–E12 drive unit (+)...
  • Page 21: Paralleling Principle Of 11A8

    Goodrive880 Series Single-Drive VFD Hardware Manual Product overview 2.7.2 Paralleling principle of 11A8 Figure 2-12 Main circuit diagram of the parallel 11A8 drive unit Note: In general, the paralleling is only applicable to the units corresponding to 11A8. 2.8 Structure diagram 2.8.1 Single-drive unit structure...
  • Page 22: Single-Drive Cabinet Structure

    Goodrive880 Series Single-Drive VFD Hardware Manual Product overview 2.8.2 Single-drive cabinet structure Figure 2-14 Layout of the 16S4 drive cabinet ① ② ③ ④ ⑤ ⑥ Description Remarks Air outlet hood AC breaker VFD unit GD880-11 Control unit GD880-ICU 3PH AC input...
  • Page 23 Goodrive880 Series Single-Drive VFD Hardware Manual Product overview Figure 2-15 Layout of the 16S5 drive cabinet ① ② ③ ④ ⑤ ⑥ ⑦ Description Remarks Air outlet hood DC fuse AC breaker VFD unit GD880-11 Control unit GD880-ICU 3PH AC input...
  • Page 24 Goodrive880 Series Single-Drive VFD Hardware Manual Product overview Figure 2-16 Layout of the 16S6–16S7 drive cabinet Description Remarks Air outlet hood AC breaker VFD unit GD880-11 Control unit GD880-ICU 3PH AC input R, S, T 3PH AC output U, V, W Output reactor 202403 (V1.0)
  • Page 25 Goodrive880 Series Single-Drive VFD Hardware Manual Product overview Figure 2-17 Layout of the 16S8–16S10 drive cabinet Description Remarks Air outlet hood AC breaker VFD unit GD880-11 Control unit GD880-ICU 3PH AC input R, S, T 3PH AC output U, V, W...
  • Page 26: System Configuration

    Goodrive880 Series Single-Drive VFD Hardware Manual Product overview 2.9 System configuration 2.9.1 Single-drive cabinet system Figure 2-18 Main circuit diagram of single-drive cabinet system ④ ⑥ ② ① ⑧ ⑨ ⑦ ⑤ ③ ⑩ The rectifier module converts AC voltage to DC voltage, and the DC voltage is distributed to inverter modules through the DC bus, then the inverter modules convert the DC voltage to AC voltage to drive the motor to rotate.
  • Page 27: Electrical Model Selection

    Goodrive880 Series Single-Drive VFD Hardware Manual Product overview Code Description 16S4 16S5 16S6 16S7 16S8 16S9 16S10 E150 Braking unit ① ② □ □ □ □ □ E203 Input reactor ● ● □ □ ● ● ● E204 DC reactor ●...
  • Page 28 Goodrive880 Series Single-Drive VFD Hardware Manual Product overview Table 2-7 Recommended breaker and contactor Breaker rated current High speed fuse rated Contactor rated VFD model current (A) current (A) GD880-11-0013-4-B GD880-11-0017-4-B GD880-11-0023-4-B GD880-11-0033-4-B GD880-11-0038-4-B GD880-11-0048-4-B GD880-11-0060-4-B GD880-11-0078-4-B GD880-11-0094-4-B GD880-11-0116-4 GD880-11-0149-4...
  • Page 29: Mechanical Installation

     applied. Ensure all the input power supplies have been disconnected before wiring or inspection, and wait for at least the time designated on the Goodrive880 series product or until the DC bus voltage is less than 36V. 3.2 Installation environment...
  • Page 30: Installation Procedure

    Goodrive880 Series Single-Drive VFD Hardware Manual Mechanical installation Environment Condition Install the drive unit in a place: Without electromagnetic radiation sources and direct sunlight. Note: The unit must be installed in a clean and well-ventilated environment based on the housing IP rating.
  • Page 31: Unpacking

    Goodrive880 Series Single-Drive VFD Hardware Manual Mechanical installation Figure 3-1 Transportation requirements When transported with a forklift, the single-drive unit must be fixed to the pallets and transported together, which means you are not allowed to remove the pallets to transport the single-drive unit. If the forklift's fork tines are too short, it may cause the unit/cabinet to tip over, resulting in serious injury, property damage or even death.
  • Page 32: Lifting

    Goodrive880 Series Single-Drive VFD Hardware Manual Mechanical installation Step 2 Use tools such as a pry bar or large one-piece screwdriver to remove the wooden box cover and the steel tongue nails of the surrounding boards. Step 3 Remove the surrounding boards and EPE filling materials from the wooden box.
  • Page 33 Goodrive880 Series Single-Drive VFD Hardware Manual Mechanical installation Figure 3-5 Unit top structure Never apply force Lifting ring The drive unit has a high center of gravity and must be placed on a flat and solid ground with sufficient support strength and a tilt angle of less than 5°. Failure to comply with this requirement will cause the drive unit to tip over or topple over, which may result in serious injury or property damage.
  • Page 34: Installation

    Goodrive880 Series Single-Drive VFD Hardware Manual Mechanical installation Figure 3-8 Unfolding the anti-tipping stand Figure 3-9 Folding the anti-tipping stand 3.3.4.2 Single-drive cabinet To lift the device with the steel lifting holes at the top corners, the lifting rope or slings must be installed into the hole of the lifting holes and fixed to ensure safety.
  • Page 35 Goodrive880 Series Single-Drive VFD Hardware Manual Mechanical installation A minimum ventilation clearance must be kept from the top and bottom of the drive unit to ensure good heat dissipation. See Figure 3-11. Both sides of the drive unit are designed with air baffle and sealing sponge for isolation to prevent the hot air at the drive unit top outlet from circulating inside the cabinet and ensure that the heat of the drive unit is discharged from the heat dissipation holes at the cabinet top outlet cover.
  • Page 36: Cabinet Requirements

    Goodrive880 Series Single-Drive VFD Hardware Manual Mechanical installation following: The drive unit must be installed and used in a cabinet. A minimum ventilation clearance must be kept from the top and bottom of the drive unit to ensure good heat dissipation. See Figure 3-13.
  • Page 37: Keypad Installation

    Goodrive880 Series Single-Drive VFD Hardware Manual Mechanical installation Figure 3-14 Bottom bracket mounting Nine-fold profile cabinet Unit bottom installation tray Two crossbeams must be installed at the cabinet bottom to support the unit. (Recommended material thickness≥2.0mm) Note: If you use another type of cabinet but not nine-fold profile cabinet, the fixing holes for the mounting bracket need to be drilled and assembled on site.
  • Page 38: Fastening Torque

    Goodrive880 Series Single-Drive VFD Hardware Manual Mechanical installation Figure 3-17 Keypad bracket dimensions (unit: mm) 14.6 116.3 5-M4 3.3.6 Fastening torque You need the following tools to install the drive unit: Standard toolbox, including screwdrivers, nut wrenches, socket wrenches. ...
  • Page 39 Goodrive880 Series Single-Drive VFD Hardware Manual Mechanical installation Operation Compliant Completed was pushed into place. Inserted screws into the fixing holes at the unit front top and bottom □ □ to fix the unit to the cabinet. Installed the (+) and (-) bus copper bars.
  • Page 40: Electrical Installation

    Goodrive880 Series Single-Drive VFD Hardware Manual Electrical installation 4 Electrical installation 4.1 Safety notes All safety precautions in this manual must be read and followed. Only trained and  qualified professionals are allowed to carry out the operations mentioned in this chapter.
  • Page 41: Emc Regulations

    Goodrive880 Series Single-Drive VFD Hardware Manual Electrical installation 4.3 EMC regulations General knowledge of electromagnetic compatibility EMC is short for electro magnetic compatibility, which refers to the ability of a device or system to function properly in its electromagnetic environment and not constitute an unbearable electromagnetic disturbance to anything in that environment.
  • Page 42: Power Cable

    Goodrive880 Series Single-Drive VFD Hardware Manual Electrical installation grounding. Different control system needs to use special pole grounding, different devices in the same control system needs to use common pole grounding, and different devices connected by the same power cables needs to use series-wound grounding.
  • Page 43: Wiring Suggestions

    Goodrive880 Series Single-Drive VFD Hardware Manual Electrical installation shielded twisted pair for each signal. Do not use the same ground wire for different analog signals. Communication cables and encoder cables need to be single-shielded twisted-pair cables (as shown in figure b). The shield layer of cable is connected to the system PE by means of a 360-degree connection or twisting into a single bundle, and the exposed shield layer is wrapped with insulating tape to prevent interference introduced by the shield layer in contact with other equipment and structural components.
  • Page 44 Goodrive880 Series Single-Drive VFD Hardware Manual Electrical installation Analog signals and digital signals cannot share a same cable, and their cables must be routed  separately. If a control cable and power cable must cross each other, ensure that the angle between them is 90°.
  • Page 45: Shielded Cable Connection

    Goodrive880 Series Single-Drive VFD Hardware Manual Electrical installation Figure 4-6 Routing multiple types of cable Interference cable Relay cable Not recommended × Sensitive cable Metal isolator Recommended Optimum √ √ 4.3.4 Shielded cable connection The shield layer of signal cable is grounded at both ends, of which the grounding points must be the same.
  • Page 46: Electrical Wiring

    Goodrive880 Series Single-Drive VFD Hardware Manual Electrical installation Figure 4-8 Power cable shield connection Shielded Shielding AC wires busbar layer EMC shield clamp Outer layer of wire PE busbar PE potential 4.4 Electrical wiring 4.4.1 E2–E5 unit wiring Figure 4-9 E2–E5 unit terminals ①...
  • Page 47: E6 Unit Wiring

    Goodrive880 Series Single-Drive VFD Hardware Manual Electrical installation 4.4.2 E6 unit wiring Figure 4-10 E6 main circuit terminals ② ③ ④ ② ③ ④ ① ① Terminal name Description 220V auxiliary power terminal (+), (-) positive or negative busbar DC terminals Voltage: 510–720VDC...
  • Page 48: E7-E8 Unit Wiring

    Goodrive880 Series Single-Drive VFD Hardware Manual Electrical installation 4.4.3 E7–E8 unit wiring Figure 4-11 E7–E8 unit terminals ① ① ③ ② ④ ③ ④ ② Terminal name Description 220V auxiliary power terminal (+), (-) positive or negative busbar DC terminals Voltage: 510–720VDC...
  • Page 49: E9 Unit Wiring

    Goodrive880 Series Single-Drive VFD Hardware Manual Electrical installation 4.4.4 E9 unit wiring Figure 4-12 E9 unit terminals ① ① ③ ② ④ ③ ② ④ Terminal name Description 220V auxiliary power terminal (+), (-) positive or negative busbar DC terminals Voltage: 510–720VDC...
  • Page 50: E11-E12 Unit Wiring

    Goodrive880 Series Single-Drive VFD Hardware Manual Electrical installation 4.4.5 E11–E12 unit wiring Figure 4-13 E11–E12 unit terminals ② ① ③ ④ Terminal name Description 220V auxiliary power terminal (+), (-) positive or negative busbar DC terminals Voltage: 510–720VDC AC input: Voltage: 0–Rated voltage...
  • Page 51: 11A8 Unit Wiring

    Goodrive880 Series Single-Drive VFD Hardware Manual Electrical installation 4.4.6 11A8 unit wiring Figure 4-11 11A8 unit terminals ② ③ ① A1A2 ⑤ Power ④ COM1 COM2 COM3 Terminal name Description 220V auxiliary power terminal (+), (-) positive or negative busbar DC terminals Voltage: 400V 510–720VDC;...
  • Page 52: Electrical Installation Checklist

    Goodrive880 Series Single-Drive VFD Hardware Manual Electrical installation Number of cables per phase*cable Model Connection terminal diameter (mm GD880-11-0149-4 1*70 OT/70-8 GD880-11-0170-4 1*95 OT/95-12 GD880-11-0215-4 1*120 OT/120-12 GD880-11-0260-4 1*150 OT/150-12 GD880-11-0305-4 1*185 OT/185-12 GD880-11-0340-4 1*185 OT/185-12 GD880-11-0380-4 2*120 OT/120-12 GD880-11-0425-4...
  • Page 53: Control Unit

    Goodrive880 Series Single-Drive VFD Hardware Manual Control unit 5 Control unit 5.1 Control unit composition ⑬ ⑫ ⑭ ① ⑮ ② ③ ⑪ ⑯ ④ ⑤ ⑥ ⑦ ⑧ ⑨ ⑩ Table 5-1 Function description Component Function description Applied to 73.5 × 103 × 23.5(mm) function expansion modules and...
  • Page 54: Led Indicator

    Goodrive880 Series Single-Drive VFD Hardware Manual Control unit Component Function description Power interface 24V power input terminal Fiber optic interface Master/slave fiber optic interface Upper computer interface, connecting to a PC for status RJ45 terminal monitoring User terminal Standard input and output terminals for users...
  • Page 55: Control Unit Size

    Goodrive880 Series Single-Drive VFD Hardware Manual Control unit Do not fasten with excessive torque; otherwise, terminals may be damaged.  5.3.1.1 Required tools 1# Phillips screwdriver may be required during installation. 5.3.1.2 Fastening torque Screws are used to install the control unit with fastening torque.
  • Page 56: Control Unit Installation Space

    Goodrive880 Series Single-Drive VFD Hardware Manual Control unit 5.3.3 Control unit installation space To make the control unit installation smooth, the distance between the upper and lower parts of the control unit and the building and its components should be left as shown in the following figure, and the control unit must be installed on a conductive metal plate, the entire conductive bottom of the control unit must properly work with the installation surface.
  • Page 57 Goodrive880 Series Single-Drive VFD Hardware Manual Control unit Figure 5-3 Control unit installation M4 threaded hole Metal conductive plate Three M4×12 combination screws Positioning hole Figure 5-4 Recommended hole position for the main control box installation 10.3 7.25 3-∅4 3-M4...
  • Page 58: Control Unit Interface

    Goodrive880 Series Single-Drive VFD Hardware Manual Control unit 5.4 Control unit interface Figure 5-5 Control unit circuit wiring RJ45 Keypad RO3C RO3B Relay 3 output RO3A RO2C RO2B Relay 2 output RO2A RO1C RO1B Relay 1 output RO1A AO2 J7...
  • Page 59: External Standard Interfaces

    Goodrive880 Series Single-Drive VFD Hardware Manual Control unit 5.4.1 External standard interfaces Terminal symbol Terminal name Description Input power 24E, CM Power supply for the control box Digital input DI1–DI6,DIL Input type: relay contact, NPN or PNP Digital power output...
  • Page 60 Goodrive880 Series Single-Drive VFD Hardware Manual Control unit Terminal Function description Cable specifications symbol When pin 1 and pin 2 are short-circuited, i.e. the PW and internal COM are connected, DI uses the internal power ground. If the external power supply is used, the shorting cap should be removed.
  • Page 61 Goodrive880 Series Single-Drive VFD Hardware Manual Control unit Terminal Function description Cable specifications symbol When 1 and 2 are short-circuited, AI2 current input is used. When 2 and 3 are short-circuited, AI2 voltage input is used. Analog output terminal AO output range: Two-core twisted-pair cable is 0–20mA, Rload≤500Ω...
  • Page 62: Control Unit Function Application

    Goodrive880 Series Single-Drive VFD Hardware Manual Control unit Terminal Function description Cable specifications symbol delivery by default. Cross-sectional area: 0.5–2.5mm² STO2 +24V RJ45 keypad RJ45 Connected to SOP-880-01 keypad Standard shielded network cable RJ45 Ethernet RJ45 Ethernet communication with a PC Standard shielded network cable 5.5 Control unit function application...
  • Page 63: Slot Expansion Application

    Goodrive880 Series Single-Drive VFD Hardware Manual Control unit 5.5.2 SLOT expansion application The ICU can cooperate with different functional modules, which are directly installed on the SLOT card slot of the ICU, as shown in the following figure. Table 5-3 Expansion card installation description...
  • Page 64 Goodrive880 Series Single-Drive VFD Hardware Manual Control unit The ICU has three SLOT card slots. When more modules are needed, install the fiber optic expansion module EC-TX823 and SLOT expansion module I-ESM-30. Each SLOT expansion module can expand three functional modules, as shown in the following figure.
  • Page 65: Accessories

    The 380V 0048–0820 (E5–E12) models are equipped with built-in DC reactors.  The braking units are INVT DBU series standard braking units. For details, see the DBU operation  manual. Image...
  • Page 66: Power Supply

    VFD and motor is 50 m to 100 m, select the reactor according to the following table. If the distance is longer than 100 m, contact INVT's technical support technicians. DC reactors can improve the power factor, avoid damage to bridge rectifiers caused due to large input current of the VFD when large-capacity transformers are connected, and also avoid damage to the rectification circuit caused due to harmonics generated by grid voltage transients or phase-control loads.
  • Page 67: Filters

    Goodrive880 Series Single-Drive VFD Hardware Manual Accessories Table 6-1 Reactor VFD model Input reactor DC reactor Output reactor GD880-11-0013-4-B ACL2-5R5-4 OCL2-5R5-4 GD880-11-0017-4-B ACL2-7R5-4 OCL2-7R5-4 GD880-11-0023-4-B ACL2-011-4 OCL2-011-4 GD880-11-0033-4-B ACL2-015-4 OCL2-015-4 GD880-11-0038-4-B ACL2-018-4 Built-in DC reactor OCL2-018-4 GD880-11-0048-4-B ACL2-022-4 Built-in DC reactor...
  • Page 68: Input Filter

    Noise filters on the output side can decrease the radio noise caused by the cables between VFDs and motors and the leakage current of conducting wires. INVT provides some of the filters for you to choose. Table 6-2 Filter model selection...
  • Page 69: Braking System

    Goodrive880 Series Single-Drive VFD Hardware Manual Accessories Note: The input EMI meets the C2 requirements after an input filter is configured.  The preceding table describes external accessories. You need to specify the ones you choose when  purchasing accessories.
  • Page 70: Braking Resistor Cable Selection

    42*2 210*2 336*2 Note: Select braking resistors according to the resistance and power data provided by INVT.  The braking resistor may increase the braking torque of the VFD. The preceding table describes the  resistance and power for 100% braking torque, 10% braking usage, 50% braking usage, and 80% braking usage.
  • Page 71: Braking Resistor Installation

    Goodrive880 Series Single-Drive VFD Hardware Manual Accessories 6.6.4 Braking resistor installation All resistors must be installed in places with good cooling conditions. The materials near the braking resistor or braking unit must be flame resistant. since  the surface temperature of the resistor is high and air flowing from the resistor is of hundreds of degrees Celsius.
  • Page 72: Maintenance And Inspection

    Goodrive880 Series Single-Drive VFD Hardware Manual Maintenance and inspection 7 Maintenance and inspection 7.1 Periodical inspection 7.1.1 Overview Only trained and qualified professionals are allowed to maintain the equipment. Before operating the interior of the equipment: Disconnect the power from the equipment.
  • Page 73 Goodrive880 Series Single-Drive VFD Hardware Manual Maintenance and inspection Table 7-2 Check items Check scope Check item Method Expected result Check the temperature, and Visual inspection, The requirements humidity, and whether there is and use stated in this vibration, dust, gas, oil spray, and instruments for manual are met.
  • Page 74: Replacement Of Wearing Parts

    Visual inspection duct occurs. Check whether there are foreign objects attached. For more details about maintenance, contact the local INVT office, or visit our website www.invt.com, and choose Support > Services. 7.2 Replacement of wearing parts 7.2.1 Capacitor 7.2.1.1 Capacitor reforming If the drive unit has been left unused for a long time, you need to follow the instructions to reform the DC bus capacitor before using it.
  • Page 75: Electrolytic Capacitor Replacement

    30℃ and a load rate of less than 70%, it must be replaced. The actual service life is related to the load rate and the ambient temperature. For details about the replacement, contact the local INVT office. 7.2.3 Cooling fan The service life of the cooling fan of the drive unit is more than 45000 hours (5 years).
  • Page 76 Goodrive880 Series Single-Drive VFD Hardware Manual Maintenance and inspection The procedure is as follows (The number of fans varies with different models): Figure 7-2 Replacing the fan for E2–E9 Fan air direction Step 1 Disconnect the DC power supply of the drive system and check to ensure there is no voltage in the equipment.
  • Page 77: Control Unit

    Goodrive880 Series Single-Drive VFD Hardware Manual Maintenance and inspection Figure 7-4 Replacing the fan for 11A8 Front cover Fan box Fan air direction Step 1 Stop the unit, disconnect the AC power supply, and wait for a time no shorter than the waiting time designated on the unit.
  • Page 78 Goodrive880 Series Single-Drive VFD Hardware Manual Maintenance and inspection Step 2 Insert and push the micro SD card into the card holder of the new module in the direction shown in the figure. Step 3 Ensure that the micro SD storage card is pushed into place. Otherwise, abnormalities may occur due to poor contact.
  • Page 79 Goodrive880 Series Single-Drive VFD Hardware Manual Maintenance and inspection Step 3 Close the cover and rotate it clockwise by 45° to tighten it. CLOSE Step 4 Dispose of waste batteries in accordance with local disposal rules or applicable laws. Replace the SOP battery.
  • Page 80 Goodrive880 Series Single-Drive VFD Hardware Manual Maintenance and inspection Step 3 Close the cover and rotate it clockwise by 30° to tighten it. CLOSE Step 4 Dispose of waste batteries in accordance with local disposal rules or applicable laws. 202403 (V1.0)
  • Page 81: Appendix A Technical Data

    Goodrive880 Series Single-Drive VFD Hardware Manual Technical data Appendix A Technical data A.1 Capacity Choose a inverter model based on the rated current and power of the motor. To endure the rated power of the motor, the rated output current of the inverter must be larger or equal to the rated current of the motor.
  • Page 82: Ce Marking

    Goodrive880 Series Single-Drive VFD Hardware Manual Technical data A.3.1 CE marking The CE marking on the product nameplate indicates that the inverter is CE-compliant, meeting the regulations of the European low-voltage directive (2014/35/EU) and EMC directive (2014/30/EU). A.3.2 EMC compliance declaration...
  • Page 83: Appendix B Dimension Drawings

    Goodrive880 Series Single-Drive VFD Cabinet Hardware Manual Dimension drawings Appendix B Dimension drawings B.1 Single-drive unit Figure B-1 Dimensions of frame E3–E6 Installation Hole Outline dimensions (mm) Fixing dimensions (mm) Frame diameter screw (mm) 243.5 Ø6 303.5 Ø6 Ø6 Ø6...
  • Page 84 Goodrive880 Series Single-Drive VFD Cabinet Hardware Manual Dimension drawings Figure B-3 Dimensions of frame E8 Outline dimensions Installation Hole diameter Frame (mm) dimensions (mm) Fixing screw (mm) Ø10 Figure B-4 Installation dimensions of frame E9 Outline dimensions Installation Hole diameter...
  • Page 85 Goodrive880 Series Single-Drive VFD Cabinet Hardware Manual Dimension drawings Figure B-5 Installation dimensions of frame E11–E12(without an output reactor) Outline dimensions Installation dimension Hole diameter (mm) (mm) Frame Fixing screw (mm) 1288 1150 Ø13 1398 1280 Ø13 Figure B-6 Installation dimensions of frame E11–E12(with an output reactor) Ø...
  • Page 86 Goodrive880 Series Single-Drive VFD Cabinet Hardware Manual Dimension drawings Figure B-7 Installation dimensions of frame 11A8 120.5 120.5 4-OB10X14 COM1 COM2 COM3 127.5 127.5 164.5 202403 (V1.0)
  • Page 87: Single-Drive Cabinet

    Goodrive880 Series Single-Drive VFD Cabinet Hardware Manual Dimension drawings B.2 Single-drive cabinet Figure B-8 Outline dimensions of 16S4 cabinet Installation Outline dimensions (mm) dimension (mm) VFD model 16S4 2300 2000 202403 (V1.0)
  • Page 88 Goodrive880 Series Single-Drive VFD Cabinet Hardware Manual Dimension drawings Figure B-9 Outline dimensions of 16S5 cabinet Installation Outline dimensions (mm) dimension (mm) VFD model 16S5 1400 2300 2000 1200 202403 (V1.0)
  • Page 89 Goodrive880 Series Single-Drive VFD Cabinet Hardware Manual Dimension drawings Figure B-10 Outline dimensions of 16S8–16S10 cabinet Installation Outline dimensions (mm) VFD model dimension (mm) 16S6–16S7 2140 2000 16S8–16S10 2140 2000 202403 (V1.0)
  • Page 90: Appendix C Example Electrical Diagram

    Goodrive880 Series Single-Drive VFD Cabinet Hardware Manual Example electrical diagram Appendix C Example electrical diagram GD880 single-drive basic electrical drawing 设 计 审 核 标准化 封面 设计日期 批 准 图纸名称 图 号 功 能 位 置 Cover Designed Designed Date Checked Std.Checked...
  • Page 91 Goodrive880 Series Single-Drive VFD Cabinet Hardware Manual Example electrical diagram Variable Circuit AC main Input Output AC fuse Input filter frequency breaker contactor reactor reactor unit Optional Optional Optional Optional Optional -QF1 -RU1 -KM1 Power supply incoming AC400V -DBU1 2.3 2.3...
  • Page 92 Goodrive880 Series Single-Drive VFD Cabinet Hardware Manual Example electrical diagram Inverter Inverter running fault indicator indicator 2.7 N 2.7 L +24E COM1 RJ45 Power supply Ethernet STO1 +24V STO2 card +24V RJ45 Keypad interface RX TX 设 计 审 核...
  • Page 93: Appendix D Ordering Information

    Goodrive880 Series Single-Drive VFD Cabinet Hardware Manual Ordering information Appendix D Ordering information Product model Structure Ordering code Remarks GD880-11-0013-4-B GD880-11-0013-4-B Drive unit GD880-11-0017-4-B GD880-11-0017-4-B Drive unit GD880-11-0023-4-B GD880-11-0023-4-B Drive unit GD880-11-0033-4-B GD880-11-0033-4-B Drive unit GD880-11-0038-4-B GD880-11-0038-4-B Drive unit GD880-11-0048-4-B...
  • Page 94 Goodrive880 Series Single-Drive VFD Cabinet Hardware Manual Ordering information Product model Structure Ordering code Remarks GD880-ICU-11 Control unit Applicable to HFBR-3M Fiber optic GD880-ICU-11-Z frame E2–E12 and SOP-880-01 Keypad and mounting bracket 11A8 L=2M (CHV-SE) Network cable GD880-ICU-13 Control unit...
  • Page 95 Website: www.invt.com 6 6 0 0 1 - 0 1 3 0 7...

This manual is also suitable for:

Gd880-11-0013-4-bGd880-11-0017-4-bGd880-11-0023-4-bGd880-11-0033-4-bGd880-11-0038-4-bGd880-11-0048-4-b ... Show all

Table of Contents