Introduction To Cabinet Cable Management; Introduction To Cabinet Grounding Points - 3Com LS8M1P12TEH Installation Manual

S7500 series ethernet switches
Table of Contents

Advertisement

Installation Manual
H3C S7500 Series Ethernet Switches
front side, back side, left side, and right side of the lower part of the cabinet respectively.
Install the protection grounding cables after installing the cabinet doors.
B.5 Introduction to Cabinet Cable Management
This section introduces cable management for N68 cabinets, including introduction to
the cabinet grounding points and internal cable management.
B.5.1 Introduction to Cabinet Grounding Points
I. Grounding points connecting the cabinet and the modules
The grounding points of the internal modules are reserved on both sides of the
back mount angle. Two types of grounding points are available: M4 and M6. They
should be installed alternatively. The spacing between two grounding points of the
same specification is 133.35 mm (5.3 in.), as shown in Figure B-58 (1).
The main grounding point used to connect the module and the cabinet is located at
the back of the upper enclosure frame. The specification is M6, as shown in Figure
B-58 (2).
(1) Grounding points used to connect the internal modules and the cabinet
(2) Main grounding points of the internal modules
Figure B-58 Grounding points of internal modules
Appendix B N68 Cabinet Installation
B-61