Emerson Rosemount 8600 Series Quick Start Manual
Emerson Rosemount 8600 Series Quick Start Manual

Emerson Rosemount 8600 Series Quick Start Manual

Vortex flowmeter
Hide thumbs Also See for Rosemount 8600 Series:

Advertisement

Quick Links

Quick Start Guide
00825-0100-4860, Rev ED
October 2024
Rosemount
8600 Series Vortex
Flowmeter

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Rosemount 8600 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Emerson Rosemount 8600 Series

  • Page 1 Quick Start Guide 00825-0100-4860, Rev ED October 2024 Rosemount 8600 Series Vortex ™ Flowmeter...
  • Page 2: Table Of Contents

    Quick Start Guide October 2024 Contents About this guide........................... 3 Installation............................ 6 Consider housing rotation......................13 Set jumpers..........................14 Connect wiring and power up....................15 Verify configuration........................19 Product certifications........................ 20 www.Emerson.com...
  • Page 3: About This Guide

    There are limits to the security capabilities of the protocol and the devices that use it. Emerson recommends a Defense-in-Depth (DiD) strategy. It is recommended to use physical security controls along with electronic security controls of any networked devices connected to the HART transmitter.
  • Page 4: Return Policy

    Emerson. 1.2  Return policy Emerson procedures must be followed when returning equipment. These procedures ensure legal compliance with government transportation agencies and help provide a safe working environment for Emerson employees. Failure to follow Emerson procedures will result in your equipment being refused delivery.
  • Page 5 October 2024 Quick Start Guide 1.3  Emerson Flow customer service Email: • Worldwide: flow.support@emerson.com • Asia-Pacific: APflow.support@emerson.com www.Emerson.com...
  • Page 6: Installation

    If the vortex flowmeter will be installed in a vertical orientation: • Install upward or downward flow for gas or steam. • Install upward flow for liquids. Figure 2-1: Vertical installation A. Gas flow B. Liquid or gas flow www.Emerson.com...
  • Page 7 The electronics must not exceed 185 °F (85 °C). Figure 2-3 shows combinations of ambient and process temperatures needed to maintain a housing temperature of less than 185 °F (85 °C). www.Emerson.com...
  • Page 8 Insulate pipe and meter body only. Do not insulate support tube bracket or transmitter so heat can be dissipated. 2.1.4  Steam installations Avoid installation shown in Figure 2-4. Such conditions may cause a water-hammer condition at start-up due to trapped condensation. www.Emerson.com...
  • Page 9 Figure 2-5. Figure 2-5: Upstream/Downstream piping A. Pressure transmitter B. Four straight pipe diameters downstream C. Temperature transmitter D. Six straight pipe diameters downstream www.Emerson.com...
  • Page 10 1. The meter body with an adapter installed in the support tube and an interconnecting coaxial cable attached to it. 2. The electronics housing installed on a mounting bracket. Prerequisites 1. Mount the meter body in the process flow line as described in Mount the flowmeter. www.Emerson.com...
  • Page 11 I. ½ in. NPT conduit adapter or cable gland (supplied by customer) J. Electronics housing K. Ground connection L. Housing base screw M. Housing adapter N. Housing adapter screws O. ½ in. NPT conduit adapter or cable gland (supplied by customer) P. Coaxial cable nut www.Emerson.com...
  • Page 12 11. Tighten the conduit adapter or cable gland to the housing adapter.  CAUTION To prevent moisture from entering the coaxial cable connections, install the interconnecting coaxial cable in a single dedicated conduit run or use sealed cable glands at both ends of the cable. www.Emerson.com...
  • Page 13: Consider Housing Rotation

    This will stress the cable and may damage the sensor. 6. Place the electronics housing into the top of the support tube. 7. Use a hex wrench to turn the four housing rotation screws counterclockwise (outward) to engage the support tube. www.Emerson.com...
  • Page 14: Set Jumpers

    Adjust jumpers to desired settings. 4.1  HART jumpers If alarm and security jumpers are not installed, the flowmeter will operate normally with the default alarm condition alarm HIGH and the security OFF. Figure 4-1: HART jumpers and LCD display ALA RM SECURITY www.Emerson.com...
  • Page 15: Connect Wiring And Power Up

    If the conduit originates above the flowmeter, route conduit below the flowmeter to form a drip loop before entry. In some cases, a drain seal may need to be installed. www.Emerson.com...
  • Page 16 Use 24 AWG or larger wire and do not exceed 5,000 feet (1,500 meters). For ambient temperatures above 140 °F (60 °C), use wire rated to 176 °F (80 °C) or higher. www.Emerson.com...
  • Page 17 Straight threads require a minimum of three wraps of tape to obtain a tight seal. 5. If applicable, install wiring with a drip loop. Arrange the drip loop so the bottom is lower than the conduit connections and the flowmeter housing. www.Emerson.com...
  • Page 18 3. Using an M4 hex wrench, loosen the jam screw until it contacts the transmitter cover. 4. Turn the jam screw an additional ½ turn counterclockwise to secure the cover.  CAUTION Application of excessive torque may strip the threads. 5. Verify that the cover cannot be removed. www.Emerson.com...
  • Page 19: Verify Configuration

    In most cases, all of these variables are pre-configured at the factory. Configuration may be required if your flowmeter is not configured or if the configuration variables need revision. Emerson recommends the following variables are reviewed before startup. HART ®...
  • Page 20: Product Certifications

    Quick Start Guide October 2024 7  Product certifications For information about product certifications, refer to Rosemount 8600 Series Vortex Flowmeter Approval Document (00825-VA00-0011). You can find it at Emerson.com/Global or contact an Emerson Flow representative. www.Emerson.com...
  • Page 21 October 2024 Quick Start Guide www.Emerson.com...
  • Page 22 Quick Start Guide October 2024 www.Emerson.com...
  • Page 23 October 2024 Quick Start Guide www.Emerson.com...
  • Page 24 2024 Emerson. All rights reserved. Emerson Terms and Conditions of Sale are available upon request. The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount is a mark of one of the Emerson family of companies. All other marks are the property of their respective owners.

Table of Contents