11.1.3 Determining Max Voltage
If maximal voltage to use isn't known, it is recommended to use the manual mode
to perform a quick saturation test.
Start with the maximal voltage of 2000V.
Perform the saturation test slowly and stop just before full saturation.
The instantaneous voltage will be indicated in the top right corner. In the
example below, the maximal voltage is 320.14V.
If a complete test sequence was required in automatic mode, a max voltage of
320.14V + 10% = ~350V would be appropriate.