NDB Technologies CTT Series User Manual page 30

Current transformer tester

Advertisement

However, if the CT under test is in the "Buried in Delta" configuration, do not
short. Refer to section 9.2.
3
4. In order to reduce nearby induction effects, the bushing on which is connected
the H2 clamp, must be shorted to ground.
5. At this step, either refer to section 8.1 for manual mode operation, or section
8.2 for automatic mode operation.
C T T
S e r i e s
Opposite windings are
shorted to ground
4
-
U s e r
M a n u a l
2
1
30