ROTATE PUMPS SCREEN
This screen is provided to allow the operator to limit the maximum number of pumps to be
alternated. In the example shown the cursor is over the programmable number of pumps
allowed to be in the alternation cycle, i.e. 3 pumps (Triplex).
Use the keys to select a time of day to alternate. Select 'NEXT' and press 'ENTER' to
return to Menu 1.
MAXIMUM PUMPS ALLOWED SCREEN
This screen allows the operator to select the maximum number of pumps that are allowed to run
regardless of level conditions. Select the maximum number of pumps with the buttons.
ALTERNATION SCREEN
NOTE: Three options are available for alternating the pump lead position:
A) 'ALT OFF' no alternation of lead/lag pump.
B) 'WHEN PUMPS STOP' pumps alternate when a pump has completed a pump
cycle.
C) 'DAILY' allows for alternation of the pumps in systems which run continuously.
Selecting 'DAILY' brings up a new selection which is the time of day at which the
pumps will alternate their position in the sequence even if they are operating.
From 'Menu 1' select 'ALARMS' and press 'ENTER' to view the current alarm status.