LEVEL ALARM SCREENS
The next screens are as follows:
Adjust and advance through the alarm settings as described previously. The 'alarm timer'
provides an adjustable time delay for alarm notification after the alarm setpoint has been
reached in order to prevent nuisance alarms.
After the 'alarm timer' has been set, return to Menu 1 and select 'ALT', press 'ENTER' to access
the alternative menu.
From Menu 1 select 'ALT' and press ENTER to select the Lead/Lag order screen.
LEAD/LAG ORDER SCREEN
The example shows the #1 pump as the 'Lead', #2 as the 'Lag', and #3 pump as the second
'Lag'. The starting position of any pump may be changed in this screen by positioning the cursor
with the   buttons and selecting the desired pump sequence. NOTE: If alternation is
enabled, the pump sequence will change based on time or pump cycle. If alternation is selected
to be 'off' then pump sequence will be 'fixed' per the selected 'pump order'.
The help screen can be selected from the Lead/Lag Order screen or it may appear if an
incorrect pump order was entered. This screen explains that pump numbers should be entered
in the order in which they come on. If there are unused pumps, enter them as coming on last.
You must enter each pump once.
Low Level Alarm Set Point
Low Level Alarm Reset Point
High Level Alarm Set Point
High Level Alarm Reset Point
Alarm Timer
'ALTERNATION'
17