Return to Service During Utility
Outage
Proceed as follows to return generator to service:
NOTE: Start with step 1 if inspection and/or maintenance
tasks were performed. Start at step 5 if unit was only shut
down to conserve fuel or to reduce run hours.
1. Install negative battery cable (black) onto negative
battery (-) terminal.
2. Pull up rubber flap covering fuse holder and install
7.5 amp fuse.
3. Install T1 fuse in transfer switch.
4. Remove the DO NOT OPERATE tag or placard
from both the control panel and transfer switch.
5. Press AUTO on control panel. A green LED illumi-
nates to verify system is in AUTO mode. Allow gen-
erator to start and run for a few minutes.
6. Set generator MLCB (generator disconnect) to ON
(CLOSED).
7. Set utility MLCB to ON (CLOSED).
8. Close viewing window.
Spark-Ignited Stationary Generators Owner's Manual