9. SETTINGS - ADVANCED LEVEL
Access the settings menu by pressing the
SET
and then press the
key again, short press. Use the   or
code value, 123, and when ready press the
keys to select the desired function. With a short press on the
its value. Use the   or
keys to change the value, and when ready, give a short press on
SET
the
key to memorize the set value and return to the functions menu.
To exit the menu and return to normal operation (temperature display) press the
(long press).
If you have not entered code 123, the adjustment will be locked and when pressing the
  and
keys to change the value of the function, the controller will show the message
on the display.
With the function lock active, when pressing the
change the function value, the controller will display the message
will not be possible to adjust the parameter.

9.1 PARAMETERS TABLE

ADVANCED
FUN
DESCRIPTION
CODE Access code
DF.01 Differential (T1-T2) to start the pump
DF.02 Differential (T1-T2) to turn off the pump
Minimum T2 (pool/reservoir) superheat
DF.03
temperature setpoint allowed to the user
Maximum T2 (pool/reservoir) superheat
DF.04
temperature setpoint allowed to the user
T2 superheat temperature to turn off the
DF.05
pump
T2 superheat temperature hysteresis to
DF.06
restart the pump
DF.07 T1 Antifreeze temperature to start the pump
DF.08 Minimum antifreeze time
T1 superheat temperature to turn off the
DF.09
pump
DF.10 Pump on time in manual mode
Temperature sensor T3 to turn off cooling
DF.11
in Holidays mode
Minimum temperature T1 to start the pump -
DF.12
scan mode
DF.13 Pump on time - scan mode
DF.14 Pump off time - scan mode
Maximum differential (T1-T2) for thermal
DF.15
shock protection
DF.16 Circulation pump type
Differential setpoint (T1-T2) (variable speed
DF.17
pump)
DF.18 Increment rate (variable speed pump)
Minimum pump speed (variable speed
DF.19
pump)
Maximum pump speed (variable speed
DF.20
pump)
Pump start time at maximum speed (variable
DF.21
speed pump)
A1.01 Auxiliary 1 operating mode
A1.02 Auxiliary 1 reference temperature sensor
Minimum temperature setpoint of auxiliary 1
A1.03
allowed to the user
SET
key for 4 seconds. Then CODE will appear
keys to enter the access
SET
key again (short press). Use the   or
SET
key it is possible to edit
  and
on the display and it
CELSIUS (FAHRENHEIT)
MIN.
MAX.
UNIT
DEFAULT
0
9999
-
40.0
°C
1.0
(72.0)
(°F)
40.0
°C
1.0
(72.0)
(°F)
-20.0
°C
DF.04
(-4.0)
(°F)
105.0
°C
DF.03
(221.0)
(°F)
°C
DF.03
DF.04
(°F)
0.1
20.0
°C
(0.2)
(36.0)
(°F)
OFF(-20.0)
10.0
°C
(OFF(-4.0))
(50.0)
(°F)
OFF(0)
600
sec.
0.0
200.0
°C
(32.0)
(392.0)
(°F)
1
720
min.
0.0
105.0
°C
(32.0)
(221.0)
(°F)
0.0
105.0
°C
(32.0)
(221.0)
(°F)
OFF(9)
999
sec.
1
999
min.
OFF(0.0)
200.0
°C
OFF(0.0)
(OFF(32.0))
(392.0)
(°F)
(OFF(32.0))
-
STD
LIN
40.0
°C
1.0
(70.0)
(°F)
20.0
°C
1.0
(36.0)
(°F)
30
DF.20
%
DF.19
100
%
5
300
sec.
OFF
REF
-
S1
S4
-
-20.0
°C
A1.04
(-4.0)
(°F)
ADVANCED
FUN
Maximum temperature setpoint of auxiliary 1
A1.04
allowed to the user
A1.05 Auxiliary 1 temperature setpoint
A1.06 Auxiliary 1 temperature setpoint Economic
SET
key
A1.07 Auxiliary 1 operating hysteresis
A1.08 Auxiliary 1 manual activation time
keys to
Cyclic timer on time / scan time
A1.09
(recirculation)
A1.10 Cyclic timer off time / interval between scans
Maximum time for auxiliary 1 output on
A1.11
without reaching the setpoint (A1AL)
A1.12 Auxiliary 1 output time off by alarm A1AL
0
A1.13 Auxiliary 1 connection type
8.0
(14.4)
A2.01 Auxiliary 2 operating mode
4.0
(7.2)
A2.02 Auxiliary 2 reference temperature sensor
Minimum temperature setpoint of auxiliary 2
-20.0
A2.03
allowed to the user
(-4.0)
Maximum temperature setpoint of auxiliary 2
A2.04
allowed to the user
105.0
(221.0)
A2.05 Auxiliary 2 temperature setpoint
70.0
(158.0)
A2.06 Auxiliary 2 temperature setpoint Economic
2.0
A2.07 Auxiliary 2 operating hysteresis
(3.6)
A2.08 Auxiliary 2 manual activation time
8.0
(46.4)
Cyclic timer on time / scan time
A2.09
60
(recirculation)
70.0
A2.10 Cyclic timer off time / interval between scans
(158.0)
Maximum time for auxiliary 2 output on
360
A2.11
without reaching the setpoint (A2AL)
50.0
A2.12 Auxiliary 2 output time off by alarm A2AL
(122.0)
A2.13 Auxiliary connection type 2
35.0
IN.01 Digital input signal type
(95.0)
20
IN.02 Digital input operating mode
30
T1 sensor indication offset
SE.01
(Offset)
T2 sensor indication offset
SE.02
(Offset)
STD
T3 sensor indication offset
10.0
SE.03
(Offset)
(18.0)
1.0
(1.8)
T4 sensor indication offset
SE.04
(Offset)
30
Controller power-on delay
GE.01
(delay inicial)
100
GE.02 Buzzer mode (buzzer)
GE.03 Preferred indication
10
GE.04 Display brightness intensity
GE.05 Function lock mode
HOT
GE.06 Time for function lock
S3
0.0
(32.0)
CELSIUS (FAHRENHEIT)
DESCRIPTION
MIN.
A1.03
A1.03
A1.03
0.1
(0.2)
OFF(0)
OFF(0)
OFF(0)
OFF(0)
1
OFF(0)
OFF
S1
-20.0
(-4.0)
A2.03
A2.03
A2.03
0.1
(0.2)
OFF(0)
OFF(0)
OFF(0)
OFF(0)
1
OFF(0)
0
OFF(0)
-20.0
(-36.0)
-20.0
(-36.0)
OFF(-20.1)
(OFF(-36.2))
OFF(-20.1)
(OFF(-36.2))
OFF(0)
OFF(0)
HOUR
ECO
OFF(0)
4
MAX.
UNIT
DEFAULT
105.0
°C
105.0
(221.0)
(°F)
(221.0)
°C
45.0
A1.04
(°F)
(113.0)
°C
40.0
A1.04
(°F)
(104.0)
20.0
°C
1.0
(36.0)
(°F)
(1.8)
9999
min.
120
9999
sec.
OFF(0)
9999
min.
OFF(0)
9999
min.
OFF(0)
9999
sec.
30
3
-
OFF(0)
REF
-
HOT
S4
-
S3
0.0
A2.04
(32.0)
105.0
°C
105.0
(221.0)
(°F)
(221.0)
°C
45.0
A2.04
(°F)
(113.0)
°C
40.0
A2.04
(°F)
(104.0)
20.0
°C
1.0
(36.0)
(°F)
(1.8)
9999
min.
120
9999
sec.
OFF(0)
9999
min.
OFF(0)
9999
min.
OFF(0)
9999
sec.
30
3
-
OFF(0)
3
-
0
7
-
0
20.0
°C
0.0
(36.0)
(°F)
20.0
°C
0.0
(36.0)
(°F)
20.0
°C
0.0
(36.0)
(°F)
20.0
°C
OFF(-20.1)
(36.0)
(°F)
(OFF(-36.2))
999
sec.
5
2
-
1
-
T4
T3
-
ON
ECO
6
-
OFF(0)
60
sec.
10