Summary of Contents for Eaton Power Xpert 9395XC-1000/1000
Page 1
® ® E E a a t t o o n n 9 9 3 3 9 9 5 5 X X C C U U P P S S 825kW/825kVA, 900kW/900kVA, 1100kW/1100kVA, 1125kW/ 1125kVA, 1200kW/1200kVA, 1350kW/1350kVA or 1500kW/ 1500kVA Installation and Operation Manual p/n: 164001079 Revision 19...
Page 2
Eaton reserves the right to change specifications without prior notice. Eaton and Power Xpert are registered trademarks and PredictPulse is a trademark of Eaton or its subsidiaries and affiliates. CA Technologies is a registered trademark of CA, Inc. IBM and AS/400 are registered trademarks of International Business Machines Corporation.
Page 3
Dear Customer, On behalf of everyone at Eaton, we thank you for partnering with us, and trusting us to maintain your business continuity and preventing downtime at your facility. Our suite of backup power, power distribution and power management products are designed to protect you from a host of threats including power outages, surges, lighting strikes, and enable you to monitor and control your power infrastructure.
Page 4
2 2 . . 2 2 L L i i c c e e n n s s e e G G r r a a n n t t . Eaton grants to Licensee a limited, revocable, non-exclusive, non-assignable...
Page 5
5 5 . . 1 1 U U p p d d a a t t e e P P o o l l i i c c y y .
Page 6
Third Party Licensors contained in the Firmware. 5 5 . . 1 1 1 1 I I n n d d e e m m n n i i t t y y . Licensee shall defend, indemnify and hold Eaton and its officers, directors, employees, and agents harmless from and against all losses, damages, liabilities, claims, actions, and associated costs and expenses (including reasonable attorneys’...
Page 7
5 5 . . 1 1 2 2 O O p p e e n n S S o o u u r r c c e e S S o o f f t t w w a a r r e e .
Page 8
4 4 U U P P S S S S y y s s t t e e m m I I n n s s t t a a l l l l a a t t i i o o n n ....................................................5 5 3 3 4.1 Preliminary Installation Information....................... 53 4.2 Unloading the UPS Cabinet from the Pallet..................... 53 4.3 Installing and Connecting the UPS Sections ....................59 viii Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 9
7.1 UPS Controls ............................114 7.1.1 Control Panel ........................... 115 7.2 Touchscreen Control Panel ........................115 7.3 Using the Touchscreen Control Panel......................115 7.3.1 Touch Screen Controls........................117 7.3.2 Using the Navigation Menu Buttons...................... 119 Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 10
1 1 0 0 P P r r o o d d u u c c t t S S p p e e c c i i f f i i c c a a t t i i o o n n s s ................................................... . 1 1 5 5 2 2 10.1 Model Numbers ........................... 152 10.2 Specifications............................152 10.2.1 UPS Input............................152 10.2.2 UPS Output ........................... 153 Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 11
Table of Contents 10.2.3 UPS Environmental ......................... 153 Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 15
External Power Cable Terminations ....................39 Table 9. Supplied External Power Wiring Terminal and Cabinet to Cabinet Hardware Kit........... 39 Table 10. Recommended Installation Parts and Tools (Not Supplied by Eaton) ............40 Table 11. 480V Power Cable Conduit Recommendations ..................41 Table 12.
Page 16
(PM) rated for a maximum of 1500 kVA. The Eaton 9395XC online power protection system is used to prevent loss of valuable electronic information, minimize equipment downtime, and minimize the adverse effect on production equipment due to unexpected power problems.
Page 17
F F i i g g u u r r e e 1 1 . . E E a a t t o o n n 9 9 3 3 9 9 5 5 X X C C U U P P S S ( ( L L D D ) ) I/O SECTION ISBM/PM SECTION Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 18
F F i i g g u u r r e e 2 2 . . E E a a t t o o n n 9 9 3 3 9 9 5 5 X X C C U U P P S S ( ( H H D D ) ) I/O SECTION ISBM/PM SECTION Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 19
F F i i g g u u r r e e 3 3 . . E E a a t t o o n n 9 9 3 3 9 9 5 5 X X C C 1 1 1 1 2 2 5 5 k k W W U U P P S S ( ( L L D D ) ) I/O SECTION ISBM/PM SECTION Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 20
Some system configurations may limit the number of inputs available. The UPS uses these inputs to monitor the building alarms in addition to the UPS status. See Chapter 8 Communication for additional information. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 21
1 1 . . 2 2 . . 1 1 I I n n t t e e g g r r a a t t e e d d B B a a t t t t e e r r y y C C a a b b i i n n e e t t s s Battery backup protection can be provided by equipping the UPS system with Eaton 9395XC battery cabinets containing sealed lead-acid, maintenance-free batteries.
Page 22
U U s s i i n n g g T T h h i i s s M M a a n n u u a a l l This manual describes how to install and operate the Eaton 9395XC UPS. Read and understand the procedures described in this manual to ensure trouble-free installation and operation.
Phillips and Pozidriv are registered trademarks of Phillips Screw Company. ECopyright 2008–2010 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be ECopyright 2008–2010 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be ECopyright 2008–2010 Eaton Corporation, Raleigh, NC, USA.
Page 24
1 1 . . 9 9 W W a a r r r r a a n n t t y y To view the UPS warranty please click on the link or copy the address to download from the Eaton website: UPS Product Warranty UPS Product Warranty https://www.eaton.com/content/dam/eaton/products/backup-power-ups-surge-it-power-distribution/...
Page 25
Do not check UPS operation by any action that includes removal of the earth (ground) connection with loads attached. • Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
The operating environment should be maintained within the parameters stated in this manual. • Keep surroundings uncluttered, clean, and free from excess moisture. • Observe all DANGER, CAUTION, and WARNING notices affixed to the inside and outside of the equipment. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 27
End forklift slots may be used for minor positioning if the forks are kept in a horizontal position with no upward angling. If these instructions are not followed, damage to the wiring channel and wiring will occur. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 28
Failure To Follow These Instructions May Tout manquement à ces instructions peut Result In Serious Injury Or Death. entraîner des blessures graves voire la mort. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 29
Instable Lorsqu’il Est Tiré De Plus De La Moitié. ISO-W026 Failure To Follow These Instructions May Tout manquement à ces instructions peut Result In Serious Injury Or Death. entraîner des blessures graves voire la mort. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 30
Energized Even When AC Power Is l’alimentation en C.A. Disconnected. Tout manquement à ces instructions peut Failure To Follow These Instructions entraîner des blessures graves voire la mort. May Result In Serious Injury Or Death. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Removed. Test Before Touching. avant de toucher. Le Failure To Follow These non-respect de ces instructions Instructions Will Result In peut entraîner de graves Serious Injury Or Death. blessures ou la mort. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Service Engineer, or the warranty terms specified on 1.9 Warranty become void. This service is offered as part of the sales contract for the UPS. Contact an Eaton service representative in advance (usually a two-week notice is required) to reserve a preferred startup date.
Page 33
3 3 . . 2 2 . . 3 3 I I n n s s t t a a l l l l a a t t i i o o n n C C o o n n s s i i d d e e r r a a t t i i o o n n s s The UPS system installation must meet the following guidelines: • The system must be installed on a level floor suitable for computer or electronic equipment. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 34
F F r r o o m m L L e e f f t t S S i i d d e e o o f f C C a a b b i i n n e e t t The basic environmental requirements for operation of the UPS are: Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 35
Maximum Relative Humidity: 95%, non-condensing N N O O T T E E If Eaton battery cabinets are located in the same room as the UPS, the battery cabinet environmental requirements supercede the UPS requirements. Operating temperatures above the recommended range will result in decreased battery life and performance, and will reduce or void the battery warranty.
Page 36
F F i i g g u u r r e e 1 1 5 5 . . U U P P S S C C a a b b i i n n e e t t D D i i m m e e n n s s i i o o n n s s – – H H D D ( ( F F r r o o n n t t V V i i e e w w ) ) 2004.1 [78.9] 2700.1 [106.3] Dimensions are in millimeters [inches] Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 37
F F i i g g u u r r e e 1 1 6 6 . . U U P P S S C C a a b b i i n n e e t t D D i i m m e e n n s s i i o o n n s s – – L L D D ( ( F F r r o o n n t t V V i i e e w w ) ) 2004.8 [78.9] 2930.1 [115.4] Dimensions are in millimeters [inches] Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 38
F F i i g g u u r r e e 1 1 7 7 . . U U P P S S C C a a b b i i n n e e t t D D i i m m e e n n s s i i o o n n s s – – 1 1 1 1 2 2 5 5 k k W W ( ( F F r r o o n n t t V V i i e e w w ) ) 2004.8 [78.9] 2376.1 [93.5] Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 39
F F i i g g u u r r e e 1 1 8 8 . . C C a a b b i i n n e e t t D D i i m m e e n n s s i i o o n n s s ( ( R R i i g g h h t t S S i i d d e e V V i i e e w w ) ) 45.5 805.8 [1.8] [31.7] 851.3 [33.5] Dimensions are in millimeters [inches] Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 40
F F i i g g u u r r e e 1 1 9 9 . . I I S S B B M M / / P P M M S S e e c c t t i i o o n n D D i i m m e e n n s s i i o o n n s s – – ( ( F F r r o o n n t t V V i i e e w w ) ) 2004.8 [78.9] 1927.5 [75.9] Dimensions are in millimeters [inches] Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 41
F F i i g g u u r r e e 2 2 0 0 . . I I S S B B M M / / P P M M S S e e c c t t i i o o n n 1 1 1 1 2 2 5 5 k k W W D D i i m m e e n n s s i i o o n n s s – – ( ( F F r r o o n n t t V V i i e e w w ) ) 160.5 [63.2] ISBM/PM FRONT VIEW (1125kW) Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 42
F F i i g g u u r r e e 2 2 2 2 . . U U P P S S B B o o t t t t o o m m V V i i e e w w CONDUIT LANDING FOR AC INPUT AND OUTPUT AND DC INPUT I/O SECTION ISBM/PM SECTION Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 43
F F i i g g u u r r e e 2 2 3 3 . . I I / / O O S S e e c c t t i i o o n n D D i i m m e e n n s s i i o o n n s s – – H H D D ( ( F F r r o o n n t t V V i i e e w w ) ) 2004.8 [78.9] 139.5 Dress [30.1] [5.5] Skirt (Optional) I/O SECTION FRONT Dimensions are in millimeters [inches] Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 44
F F i i g g u u r r e e 2 2 4 4 . . I I / / O O S S e e c c t t i i o o n n D D i i m m e e n n s s i i o o n n s s – – ( ( T T o o p p V V i i e e w w ) ) [1.2] 47.5 47.5 [36.6] [27.5] [1.9] [1.9] [28.5] [28.5] Front Front I/O SECTION TOP (LD) I/O SECTION TOP (HD) Dimensions are in millimeters [inches] Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 49
(from a Wye source) for proper equipment operation. • The Eaton 9395XC 480V unit is designed for operation on a grounded-wye source of supply. There is no additional connection point for a neutral conductor. The output of this UPS will not directly support phase to neutral loads.
Page 50
UPSs or each UPS in distributed bypass and parallel systems must use a separate battery system for each UPS. The Eaton 9395XC UPS provides backfeed detection and protection through a +48V DC Shunt Trip Interface of the bypass input breaker. An optional I/O Cabinet is also available with an integrated backfeed contactor.
Page 51
B B a a t t t t e e r r y y C C o o n n d d u u c c t t o o r r S S i i z z i i...
Page 52
4-Stud Mounting 40 (29.5) Phase C 4-Stud Mounting 40 (29.5) Bypass Input to ISBM Phase A 2-Stud Mounting 22 (16.3) Phase B 2-Stud Mounting 22 (16.3) Phase C 2-Stud Mounting 22 (16.3) Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 53
Table 9 for supplied external wiring terminal hardware, and Table 10 recommended installation parts and tools not supplied by Eaton Corporation. Figure 45 through Figure 47 show the location of the power cable terminals inside the UPS.
Page 54
Bolt, Hex–Head, (cabinet M6 x 20 mm 180190078-045 connecting - side) M6 Serr Flg Hex, Clr ZN 180200005-002 Washer, Flat M6 HD 180500036-060 180190118-028 Hex Bolt, Locking (joining M5 x 12 mm strap) Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 55
Conduit is sized to accommodate one ground conductor sized in accordance with NEC Table 250.122. Conduit sizes listed are for copper wiring only. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 56
AC Input to UPS Rectifier (A, B, C, Ground) AC Output 480 Vac (A, B, C, Ground) Eaton 9395XC-1125/1125 AC Bypass (A, B, C, Ground) DC (Common Battery Battery) (Positive, Negative, Ground) Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 57
AC Input to UPS Rectifier (A, B, C, Ground) AC Output 480 Vac (A, B, C, Ground) Eaton 9395XC-1400/1400 AC Bypass (A, B, C, Ground) DC (Common Battery Battery) (Positive, Negative, Ground) Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 58
Wiring Requirements. External overcurrent protection and disconnect are not provided by this product, but are required by codes. If an output lockable disconnect is required, it is to be supplied by the customer. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 59
Includes < 4% low line input voltage – Includes 4% battery charging capacity – Includes 5 mins overload at 110% • Alternatively: Full capabilities at max 88% load **- Indicates without reduction in performance. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 60
Bypass and output overcurrent protection and bypass and output disconnect switches are to be provided by the customer. Module Output Breakers (MOBs) are to be provided by the customer. Table 14 lists the recommended rating for bypass, output, and MOB circuit breakers with breaker ratings. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 61
3 3 . . 2 2 . . 5 5 U U P P S S S S y y s s t t e e m m I I n n t t e e r r f f a a c c e e W W i i r r i i n n g g P P r r e e p p a a r r a a t t i i o o n n Control wiring for features and options should be connected at the customer interface terminal blocks located inside the UPS. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 62
The REPO switch wiring must be in accordance with NEC Article 725 Class 2 requirements. • The maximum distance between the REPO and the UPS cannot exceed 150 meters (500 feet). Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 63
The output of this UPS will not directly support phase to neutral loads. • The tie cabinet must contain Module Output Breakers (MOBs) with dual auxiliary contacts for control of the system. • Use the applicable wiring for the designated interface terminals: Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 64
Si ces instructions ne sont pas suivies, des dommages au câblage et à son canal surviendront. Carefully inspect the outer packaging for evidence of damage during transit. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 65
UPS Installation Plan and Unpacking Do not install a damaged cabinet. Report any damage to the carrier and contact an Eaton service representative immediately. ATTENTION! Ne pas installer une armoire endommagée. Signaler les dommages au transporteur et communiquer avec un représentant du service Eaton immédiatement.
Page 66
F F i i g g u u r r e e 3 3 0 0 . . U U P P S S C C a a b b i i n n e e t t a a s s S S h h i i p p p p e e d d o o n n P P a a l l l l e e t t ( ( I I S S B B M M / / P P M M S S e e c c t t i i o o n n ) ) Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 67
F F i i g g u u r r e e 3 3 1 1 . . U U P P S S C C a a b b i i n n e e t t a a s s S S h h i i p p p p e e d d o o n n P P a a l l l l e e t t ( ( I I / / O O S S e e c c t t i i o o n n ) ) Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Les sections de l’onduleur sont lourdes (voir le Table 2). Suivre attentivement les instructions de déchargement et de déballage pour éviter de renverser les armoires, ce qui pourrait causer de graves blessures. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 69
For the following steps, verify that the forklift or pallet jack is rated to handle the weight of the cabinet (see Table 2 for cabinet weight). If installed, remove the optional dress skirts at the bottom of the I/O and ISBM/PM cabinets (see Figure 32 Figure 34). Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 70
F F i i g g u u r r e e 3 3 2 2 . . R R e e m m o o v v i i n n g g t t h h e e I I S S B B M M / / P P M M S S e e c c t t i i o o n n L L e e f f t t S S i i d d e e S S h h i i p p p p i i n n g g B B r r a a c c k k e e t t Front Door Dress Skirt (Three sides, Optional) Shipping Bracket Pallet Bolts Shipping Bracket Left Side Shipping Bolts Bracket NOTE: 1125kW UPS cabinets - similar attachements Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 71
Pull the pallet from under the cabinet. Discard or recycle the pallet and shipping brackets in a responsible manner. Carefully lower the cabinet until the cabinet base contacts the floor. Repeat Steps 2 through 6 for the I/O cabinet (see Figure 34 Figure 35 Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 72
F F i i g g u u r r e e 3 3 4 4 . . R R e e m m o o v v i i n n g g t t h h e e I I / / O O S S e e c c t t i i o o n n L L e e f f t t S S i i d d e e S S h h i i p p p p i i n n g g B B r r a a c c k k e e t t Front Panel Shipping Bracket Bolts Dress Skirt (Optional) Shipping Bracket Bolts Pallet Left Side Shipping Bracket Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
F F i i g g u u r r e e 3 3 5 5 . . R R e e m m o o v v i i n n g g t t h h e e I I / / O O S S e e c c t t i i o o n n R R i i g g h h t t S S i i d d e e S S h h i i p p p p i i n n g g B B r r a a c c k k e e t t Front Panel Dress Skirt Shipping Bracket (Optional) Bolts Pallet Shipping Bracket Right Side Shipping Bolts Bracket Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 74
Use care during installation to protect components mounted on the right side of the I/O section and the inter- cabinet wiring harnesses attached to the left side ISBM/PM section from damage. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 75
Lors de l’installation, prendre soin de protéger les composantes du côté droit de la section d'entrée/sortie (I/O) et les faisceaux de câbles reliant les armoires du côté gauche du module de contournement de système intégré (ISBM). Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 76
Remove the retaining screw located inside the door at the bottom hinge pivot point, then lift the door off. • Retain the hardware for later use. Remove the deadfront panels from the I/O and ISBM/PM sections (see Figure 37). Proceed to paragraph 4.3.2 Electrically Connecting the UPS Sections Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 77
ISBM section. The shipping brackets can be removed and discarded after releasing the power wiring. Disconnect the power wiring harnesses from the ISBM shipping brackets (see Figure 39). Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 78
C cable lug connections to the I/O AC Input terminals. Follow the callout details in Figure 39 to connect the correct cable lug to the proper terminals. See paragraph 3.2.4 UPS System Power Wiring Preparation wiring and termination requirements. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 79
PM section left side and the front of the cabinet bases are flush with each other. Make sure to align the connecting bolt holes in the I/O base and the joining strap on the upper ISBM section (see Figure 40 Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 80
Connect the front of the sections using three M6 bolts with nuts and washers. Align the holes on the joining strap between the I/O and ISBM/PM sections. Secure the bracket with five M5 bolts from the hardware kit (see Figure 41). Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 81
Connect the ground cable from the ISBM/PM to the I/O section ground points using the supplied hardware (see Figure 42 Table 9). Route the cable through the ground access hole in the I/O section (see Figure 39). Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 82
43). Do not remove the debris shields until installation is complete. However, remove the shields before operating the UPS. Once the debris shields are removed, do not place objects on the ventilation grills. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 83
F F i i g g u u r r e e 4 4 3 3 . . I I S S B B M M a a n n d d I I S S B B M M / / P P M M S S e e c c t t i i o o n n D D e e b b r r i i s s S S h h i i e e l l d d s s Debris Shields Front I/O SECTION ISBM/PM SECTION Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
(E1, E2, E3) in the I/O section (see Figure 46 Figure 47. See paragraph 3.2.4 UPS System Power Wiring Preparation System Power Wiring Preparation for wiring and termination requirements. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Power Terminal Detail BB) Bypass Input: E6, E7, E8 UPS Output: E9, E10, E11 DC Input from (See gure UPS Battery Input (+), E4 Power Terminal Detail AA) Battery Output (-) E5 I/O FRONT Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 86
4 4 . . 6 6 . . 2 2 B B a a t t t t e e r r y y P P o o w w e e r r W W i i r r i i n n g g When sizing the battery system, do not exceed the internal battery charger capabilities. See Chapter 10 Product Specifications for maximum battery charger currents. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 87
Ne pas installer une armoire endommagée. Signaler les dommages au transporteur et communiquer avec un représentant du service Eaton immédiatement. To install wiring to connections: N N O O T T E E B B a a t t t t e e r r y y C C a a b b l l e e R R o o u u t t i i n n g g R R e e q q u u i i r r e e m m e e n n t t s s u u s s i i n n g g C C o o n n d d u u i i t t : •...
Page 88
4.6.1 External Power Wiring Installation Step 2 and secure with the retained hardware. Reinstall the panels removed in paragraph 4.6.1 External Power Wiring Installation, Step 1 and secure with the retained hardware. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 89
4.7.2 TB1 Battery Interface Connections; if wiring the Minislot connections only, proceed to paragraph 4.7.3 Minislot Connections; otherwise, proceed to Step 10. 10. Reinstall the ISBM deadfront panel and secure with the retained hardware. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 90
Minislot-Slot Communication Bays (See Figure “Terminal Blocks TB1, TB2, and TB3 (See Figure “Minislot-Slot Communication Bays” Connector Assignments” for terminal assignments.) for detail.) Minislot Panel K5 Backfeed Contactor (LD option) ISBM/PM Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 91
F F i i g g u u r r e e 4 4 9 9 . . M M i i n n i i s s l l o o t t W W i i r r e e E E n n t t r r y y Wire Entry (ref) Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 92
Output: 3-Phase UPS Output Voltage to Sync Box for Sync Control. Out VOLT ØC BYP VOLT RTRN ØA BYP VOLT RTRN ØB Input: 3-Phase Synchronization Source sent from Sync Box for Sync Control. BYP VOLT RTRN ØC Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 93
NOTE Alarm relay normally-open and normally-closed return terminals are separated on the terminal board but are electrically in common. NOTE Do not directly connect relay contacts to the mains related circuits. Reinforced insulation to the mains is required. NOTE Alarm relay wiring should be a minimum of 22 AWG Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 94
(see Figure To locate the appropriate terminals and review the wiring and termination requirements, see paragraph 3.2.4 UPS System Power Wiring Preparation, Table 17, and Figure 48 through Figure Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 95
When installing internal wiring to Minislot terminals, route the wiring through the internal opening in the Minislot communication bay and the interface entry conduit landing plates. For installation and setup of an Minislot card, contact an Eaton service representative (see 1.8 Getting Help).
Page 96
4.7 Installing Interface Connections. N N O O T T E E When installing the REPO switch, you must install conduit between the device and the UPS cabinet for wiring the switch. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 97
N N O O T T E E This procedure is intended to be used for the installation of the Eaton-supplied REPO switch. If installing another manufacturer's switch, use this procedure only as a guide.
Page 98
15. Close the door and secure the latch. Figure 56 shows the wiring connections if the normally-closed REPO contacts are used and Figure 57 shows alternative methods of connecting a REPO switch if using another manufacturer's switch. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 99
REPO switch must be a latching-type switch not tied to any other circuits. NOTE REPO normally-open and normally-closed return terminals are separated on the terminal board but are electrically in common. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 100
1.9 Warranty become void. This service is offered as part of the sales contract for the UPS. Contact an Eaton service representative in advance (usually a two-week notice is required) to reserve a preferred startup date. 4 4 . . 1 1 1 1 C C o o m m p p l l e e t t i i n n g g t t h h e e I I n n s s t t a a l l l l a a t t i i o o n n C C h h e e c c k k l l i i s s t t The final step in installing the UPS system is completing the following Installation Checklist.
Page 101
Accessories are mounted in installed locations and wiring is terminated inside the UPS cabinet. (OPTIONAL) o The debris shield covering the UPS cabinet ventilation grill is removed. o Startup and operational checks are performed by an authorized Eaton Customer Service Engineer. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 102
UPS System Installation N N o o t t e e s s _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 103
Use only 75°C copper wire. The procedures in this section describe the installation of Distributed Bypass Control wiring for: • Controller Area Network (CAN) • Pull Chain wiring with Module Output Breakers (MOBs). Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Output: General purpose normally-open (NO) ALM RLY NO relay contact. Output: ALM RTN is shared for (NC) and ALM RTN (NO) relay contacts. Output: General purpose normally-closed ALM RLY NC (NC) relay contact. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 105
Input: 1G Ethernet Port for PredictPulse. PORT 3 To install distributed bypass control wiring: Verify the UPS system is turned off and all power sources are removed. See Chapter 7 UPS Operating Instructions for shutdown instructions. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 106
F F r r o o m m U U P P S S 1 1 T T o o U U P P S S 2 2 CN13 (GND-ISO) CN13 (GND-ISO) CN13 (CANBL) CN13 (CANBL) CN13 (CANBH) CN13 (CANBH) Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 107
Always confirm contact operation prior to wiring. Route and install distributed bypass system pull-chain wiring between the UPS cabinets and customer- supplied tie cabinet MOBs. See Table Table 23 Figure 60 for wiring information. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 108
Input: Programmable UPS alarm, 30AWG] activated by a remote dry contact ZCN5 closure. Default function set for on [Recommended Wire: Twisted Pair BLD ALRM 5 maintenance bypass. Wires #18AWG (per Building Alarm)] Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 109
MOB 2 AUX 1 NC UPS 2 J89 – PULL CHAIN/REM EPO MOB 2 AUX 2 COM Pull Chain Common UPS 2 J89 – PULL CHAIN MOB 2 AUX 2 NO Pull Chain Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 111
Wire the connectors to the wires and connect to the applicable terminals (see Table Reinstall all panels previously removed and secure with the retained hardware. Close the UPS front doors and secure the latches. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
U U P P S S S S y y s s t t e e m m O O v v e e r r v v i i e e w w The Eaton Power Xpert 9395XC UPS is a continuous-duty, solid-state, transformerless (at 480 Vac), three- phase, true online system that provides conditioned and uninterruptible AC power to the UPS system's output and critical load.
Page 113
The inverter produces a three-phase AC output to a customer's load without the use of a transformer. The inverter derives regulated DC from the rectifier and uses Power Semiconductor or SiC MosFET devices and pulse-width modulation (PWM) to produce a regulated and filtered AC output. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 114
ESS mode is a normal operating mode, and not an alarm condition. While the UPS is in this mode, the Online light on the front display will illuminate. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 115
Les charges critiques ne sont pas protégées des fluctuations de tension ou de fréquence ni des pannes de courant lorsque l’onduleur est en mode Contournement. The Eaton 9395XC UPS provides backfeed detection and protection through a Shunt Trip mechanism of the bypass input breaker. An optional Bypass Contactor is available in the I/O Cabinet.
Page 116
Bypass Input Switch Rectifier Input Output f i t r e i r e t Battery Converter Main Power Flow Breakers Contactors Trickle Current Closed Battery Breaker Energized Open De-Energized Battery Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 117
Feed, Common Battery, Dual-Feed Configuration Figure 66 Eaton 9395XC (1125 kW) Three UPM, Common Rectifier Feed, Common Battery, Dual- Feed Configuration, Continuous Static Switch Figure 67 Eaton 9395XC Simplified Dual-Feed UPS with Maintenance Bypass Panel Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 118
NOTE AC input to rectifier is not used in single feed configuration. Dashed lines indicate optional features/components NOTE Backfeed protection is not provided as a part of UPS. Customer supplied bypass input breaker with 48-60 VDC shunt trip is required. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 119
E4, E5 Battery Breaker BATTERY SYSTEM (Not supplied with the UPS) Service Connector NOTE Callout letters , and map the applicable Input/Output Ratings and External Wiring Requirements Table in Chapter 3. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 120
(BIB) is installed in the maintenance bypass and a single-feed UPS is being installed, a single feed to the maintenance bypass is acceptable for supplying both the UPS and the bypass. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 121
If the utility AC power is interrupted or is out of specification, the UPSs automatically switch to Battery mode to support the critical load without interruption. When utility power returns, the UPSs return to Normal mode. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 122
If a module is taken offline, the other modules remain online to support the load. If more modules than can support the load must be taken offline, the load must be transferred to maintenance bypass or shut down. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 123
(Online and On Battery), and create an entry into the alarm event history. As the battery discharges, the boost converter and inverter constantly make minute adjustments maintaining a steady output. The UPSs remain in Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 124
Depending on the total load and the duration of the battery discharge, battery and rectifier input current limit alarms may be seen for a short time due to the current required to recharge the batteries. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 126
– AC Input to Bypass – DC Input from Battery – UPS AC Output to Tie Cabinet – Output to Critical Load – Overcurrent Protection supplied by customer AC Output to Critical Load Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 127
– AC Input to Bypass – DC Input from Battery – UPS AC Output to Tie Cabinet – Output to Critical Load – Overcurrent Protection supplied by customer AC Output to Critical Load Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 128
– AC Input to Bypass – DC Input from Battery – UPS AC Output to Tie Cabinet – Output to Critical Load – Overcurrent Protection supplied by customer AC Output to Critical Load Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 129
F F i i g g u u r r e e 7 7 4 4 . . U U P P S S C C o o n n t t r r o o l l s s Control Panel Touchscreen Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 130
When power is supplied to the UPS, the control panel touchscreen boots and the Eaton logo appears. If the user is not logged in a Tap to Unlock screen appears (see Figure 76 Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 131
USER + CONTROL + CONFIGURATION + SERVICE The number in an unlocked padlock icon shows the current accessed security level . Click on the icon to change the security level or sign out (see Figure 78). Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 132
7 7 . . 3 3 . . 1 1 T T o o u u c c h h S S c c r r e e e e n n C C o o n n t t r r o o l l s s The touch screen control panel provides an operator interface with the UPS system. Figure 80 identifies the display areas discussed in the following sections. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 133
The Timeline header bar also provides clear alarms/logs, sort, filter and search functions (see .7.3.3 Timeline Screen). Security Level Overview Header Bar (Typical) Padlock Current Screen Selected Timeline Header Bar Clear Alarms/ Sort Filter Logs/Status Search Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 134
Allows selection of operating mode, normal, bypass, charger on/off and power module on/off. The EAA controls screen can be used to enable and disable installed Energy Advantage Controls Architecture options. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 135
Yellow lines indicates an out-of-tolerance condition. N N O O T T E E Screens shown are representative examples of system operation. The screen data will vary based on system activity at the time of observation. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 136
F F i i g g u u r r e e 8 8 3 3 . . T T i i m m e e l l i i n n e e S S c c r r e e e e n n — — A A c c t t i i v v e e E E v v e e n n t t s s Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 137
F F i i g g u u r r e e 8 8 4 4 . . T T i i m m e e l l i i n n e e S S c c r r e e e e n n — — N N o o E E v v e e n n t t s s Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 138
F F i i g g u u r r e e 8 8 6 6 . . T T i i m m e e l l i i n n e e — — E E v v e e n n t t S S o o r r t t Tap the Clear icon to clear alarms, logs or status items from the Timeline list. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 139
D D a a t t e e & & T T i i m m e e : Date & Time when alarm was logged into system • E E v v e e n n t t : Describe Event title in short detail. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 140
Input, Bypass, Output and Battery status. Details for each meter screen can be selected by touching the item in the header bar or column name on the Summary Screen. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 141
F F i i g g u u r r e e 9 9 2 2 . . I I n n p p u u t t M M e e t t e e r r s s S S c c r r e e e e n n The Bypass Meters Screen shown in Figure 93 displays values pertaining to the Bypass conditions. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 142
F F i i g g u u r r e e 9 9 4 4 . . O O u u t t p p u u t t M M e e t t e e r r s s S S c c r r e e e e n n Selecting Battery on the Meters screen Figure 95 shows the Battery Meters screen. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 143
(see Table 26). When the correct security code is entered, the Controls screen appears. The Controls screen shows system status and includes four sub screens: • System • This UPS Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 144
F F i i g g u u r r e e 9 9 9 9 . . S S y y s s t t e e m m C C o o n n t t r r o o l l S S c c r r e e e e n n — — O O n n l l i i n n e e Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 145
The E E S S S S C C o o n n t t r r o o l l s s shows the ESS (Energy Saver System) status and contains two sections to control the ESS: • ESS Commands — Enable/Disable ESS • ESS Action Buttons — Enable High Alert and Configure ESS (link to ESS in Settings) Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 146
Advanced settings are available to configure system parameters and will require password login to higher security levels (see Table 26). Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 147
Battery Health, Discharge, Run Battery Tests and View Previous Results Reminders Service, Warranty Reminders Display Adjust Backlight Brightness, Adjust Idle Timeout, Test Lamp Levels and Passcodes Enable Locks, Change Passcodes for all levels Legal EULA, Terms and Conditions, Licenses Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 148
Do not close battery breaker until pre-charge is complete (i.e. Bypass Mode or Online Mode has been achieved). N N O O T T E E If "Batteries Disconnected" and/or "Battery Breaker Open" alarms are present, close the battery breaker. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 149
à l’étape suivante. N’utiliser cette fonction que pour mettre la charge critique hors tension. N N O O T T E E The following instructions are for the Eaton-supplied REPO switch. If a customer- supplied REPO switch is used, it may not activate in the same manner; refer to the operating instructions provided with the switch.
Page 150
Close all Module Output Breakers (MOBs). Close all UPS input feeder circuit breakers. Close all UPS Bypass input feeder circuit breakers. Observe the UPS control panel displays becoming active, indicating logic power. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 151
7 7 . . 5 5 . . 3 3 S S i i n n g g l l e e U U P P S S S S h h u u t t d d o o w w n n u u s s i i n n g g L L o o a a d d O O f f f f N N O O T T E E To shut down a single UPS, MOBs with dual auxiliary contacts must be installed and connected. To shut down a single UPS: Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 152
The UPS will start, sync to the other UPSs online, and go online. 10. Verify the following messages display sequentially on the UPS status line: DC STARTING, BYPASS ONLINE The rectifier and inverter turn on. The inverter continues to ramp to full voltage. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 153
Press the C C o o n n t t r r o o l l button on the menu bar. The Controls screen is displayed (see Figure 99). Select T T h h i i s s U U P P S S from the Control screen (see Figure 106). Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 154
On the C C o o n n t t r r o o l l s s screen, select LOAD OFF. The Load Off screen is displayed, providing a choice to proceed or abort the shutdown. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 155
N N O O T T E E The following instructions are for the Eaton-supplied REPO switch. If a customer- supplied REPO switch is used, it may not activate in the same manner; refer to the operating instructions provided with the switch.
Page 156
F F i i g g u u r r e e 1 1 0 0 7 7 . . R R E E P P O O O O p p e e r r a a t t i i o o n n Activated Deactivated Pu sh but to n lo cked in to p lace Un lo ck pushbutt o n to rele ase Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 157
C C h h a a p p t t e e r r 8 8 C C o o m m m m u u n n i i c c a a t t i i o o n n This chapter describes the communication features of the Eaton 9395XC UPS system and provides information about connecting hardware.
Page 158
Real-time alarm events for all subscribed devices via the PredictPulse mobile app (Apple and Android). You can track all alarms by device. As critical alarms occur, Eaton will acknowledge them so you know when Eaton has diagnosed the alarm (and pending notification of resolution).
Page 159
, which allows graceful shutdown of operating systems. Eaton’s Intelligent Power Software gives you all the tools you need to monitor and manage power devices on your network, even in a virtualized environment. This innovative software solution combines the most critical applications in ensuring system uptime and data integrity: not only power monitoring and management, but also graceful shutdown during an extended power outage.
Page 160
If contact ratings are required that can be operated above the rated voltage and current available with the UPS general purpose relay contacts, an IRC-MS card should be used and separation of Class 1 and Class 2 wiring is observed. Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 161
T T H H E E B B A A T T T T E E R R Y Y S S T T R R I I N N G G Y Y O O U U R R S S E E L L F F . . V V O O L L T T A A G G E E S S A A R R E E A A L L W W A A Y Y S S P P R R E E S S E E N N T T I I N N T T H H E E B B A A T T T T E E R R Y Y S S T T R R I I N N G G . If you suspect that a battery string needs service, contact an Eaton service representative.
Ensure the UPS is in Normal mode (Normal status indicator is illuminated). If an alarm lamp is illuminated or the Normal status indicator is not illuminated, contact an Eaton service representative. 9 9 . . 2 2 . . 2 2 M M O O N N T T H H L L Y Y M M a a i i n n t t e e n n a a n n c c e e...
Page 163
F F i i g g u u r r e e 1 1 0 0 9 9 . . I I S S B B M M / / P P M M S S e e c c t t i i o o n n A A i i r r F F i i l l t t e e r r L L o o c c a a t t i i o o n n s s ISBM Air Filter PM Air Filters Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 164
F F i i g g u u r r e e 1 1 1 1 0 0 . . I I S S B B M M / / P P M M S S e e c c t t i i o o n n A A i i r r F F i i l l t t e e r r R R e e p p l l a a c c e e m m e e n n t t Front Door Deadfront Front Panel Filter (Typical) Screws (6) Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 165
9 9 . . 2 2 . . 4 4 A A N N N N U U A A L L M M a a i i n n t t e e n n a a n n c c e e Annual preventive maintenance should be performed only by authorized service personnel familiar with maintenance and servicing of the UPS system. Contact an Eaton service representative for more information about service offerings.
Page 166
Phillips and Pozidriv are registered trademarks of Phillips Screw Company. Copyright 2008–2010 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be Ne pas éliminer les déchets d’équipements électriques et électroniques (DEEE) aux ordures. Pour connaître la reproduced in any way without the express written approval of Eaton Corporation.
Page 167
110% OL at 480V fixed DC Steady State up to overload timer. No overload below 480V. 100% load at 420V fixed DC Steady State. Operates to System Current of 4000A UPS shall transfer to Bypass mode if available or shutdown after the overload timer expires Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Page 168
E E l l e e c c t t r r o o s s t t a a t t i i c c D D i i s s c c h h a a r r g g e e ( ( E E S S D D ) ) IEC61000-4-2 Level 3 - 4kV contact/ 8kV air discharge. I I m m m m u u n n i i t t y y Eaton 9395XC UPS Installation and Operation Manual 164001079—Rev 19...
Need help?