Please adhere to the warnings and instructions specified in the manual and on the equipment, and keep the manual properly for future reference. Do not try to operate the equipment before reading all the safety information and operation instructions The manual applies to the 9395XR series, including: 9395XR-1500 9395XR-1800...
The contents of this manual are the copyright of the publisher and may not be reproduced (even extracts) without the written approval of Eaton Corporation. Every care has been taken to ensure the accuracy of the information contained in this manual, but no liability can be accepted for any errors or omission. The right to make design...
CAUTION • The 9395XR series models are available as C2 UPS product which can be placed both in a residential and commercial/industrial environment. When included in a residential environment, this product may cause radio interference, in which case the user may be required to take additional measures.
AC power to critical load and protects it from power failures. Eaton 9395XR Series UPS has flexible power scalability from 125 kW to 6MW, hot swappable modular and standard design, high flexibility and applicability, market leading efficiency, availability and performance, very suitable to applications of multi tenant data center (MTDC), small-middle-large data center, automation, medical etc.
Installation and Operation Manual 2.1. Looking Inside the UPS System The system level static bypass in the 9395XR series UPS determines the attainable output power of the UPS. The static bypass line consists of static switch and a optional backfeed protection isolation device connected in series.
2.3. UPS Features The Eaton UPS has many features that provide cost-effective and consistently reliable power protection. The feature descriptions provide a brief overview of the UPS standard features. 2.3.1.
2.3.4. Variable Module Management System (VMMS) Eaton Variable Management Module System (VMMS) is a key component of Eaton EAA(Energy Advantage Architecture). Eaton VMMS technology maximizes UPS efficiencies at low load levels while supporting the load with continuous double conversion power but increase the system efficiency by dynamic adjusting the UPM active and idle.
The Eaton Sync Control maintains critical load synchronization of either two separate single Eaton UPS systems or two separate single Eaton UPS systems. Synchronization of the UPS systems facilitates the uninterrupted transfer of customer loads from one load bus to another by means of downstream, dual source, solid state transfer switches.
The UPS frames can be connected in parallel to create even larger systems. A maximum of four 9395XR UPS frames can be connected in parallel. Above four UPS in parallel requirement can ask help from Eaton technical solution team to customization design.
Chapter 10 6. Have authorized service personnel perform preliminary operational checks and startup. NOTE Startup and operational checks must be performed by an authorized Eaton Customer Service Engineer, Chapter 9 or the warranty terms specified in become void. This service is offered as part of the sales contract for the UPS.
When ignored, either one of these aspects can create an undesirable microclimate at the UPS location. If the environment created by this microclimate exceeds the Eaton UPS operating specification, the UPS reliability, over time, will be reduced. These same environmental extremes will also create reliability concerns for any servers that are exposed to them.
The default battery settings of the UPS are for 12 Vdc VRLA batteries. If requested to use other battery types, contact your Eaton representative. For the battery specification, see Section Connect the battery cabinet as follows: 1.
UPS EnergyAware kits to utilize Time of Use and peak shaving BESS application. Eaton UPS can protect the critical load without comprise and also fully mining the value of lithium battery. Regarding to 9395XR UPS BESS feature, please contact with Eaton for more details.
Page 60
A full list of supported lithium battery brands can be obtained from Eaton local representatives. 9395XR UPS provides 2 kinds of RS485 port (Modbus protocol) connection methods to connect to the lithium battery cabinet. The UPS side can choose the TB terminal interface (See Cabinet...
4.9.2. External Battery Breaker Wiring Interface When using the original battery cabinet from the Eaton, the battery breaker interface wiring is provided with the cabinet. Connecting it requires only routing the wires from the cabinet to the top section of the UPS.
Chapter 5 For Mini-slot accessories and communication devices selection see . For installation and setup of a Mini-slot card, please contact your Eaton representative. To install wiring to connections: If not already installed, install the LAN and telephone drops. 2. Open the front door of the UPS.
UPS frames can be connected in parallel. The UPS static bypass power rating needs to be identical among all paralleled units. However, paralleled UPS cabinets can be housed with different number of UPM power modules. If more than 4 UPS needed in parallel system, please contact local Eaton representatives for more detail.
4.10.4. Installing Eaton Sync Control Refer to the operating instructions provided with the Eaton Sync Control. UPS Relay Common – – – Bypass Volts Phase A – Bypass Volts Phase B – Bypass Volts Phase C – Output Volts Phase A –...
• Gigabit Network Card The Eaton Gigabit Network Card (Network-M2) is Eaton’s latest UPS network management card that delivers IT professionals with new and exciting capabilities and features. With better speed and cybersecurity, the Gigabit Network Card improves business continuity by providing warnings of pending issues to administrators and helping to perform orderly shutdown of servers and storage.
• Industrial Gateway Card The Eaton Industrial Gateway Card (INDGW-M2) combines the features of an SNMP agent, HTTP/ web server and a Modbus card to facilitate remote monitoring of your UPS system through any Building Management System. Enjoy the freedom to customize and schedule actions, like shutdown protocols and load shedding, and receive immediate notifications during power events, without having to be onsite.
Protector (IPP) application provides automatic, graceful shutdown of computers and virtual machines or servers powered by an Eaton UPS during a power outage that lasts longer than your available battery runtime. Intelligent Power Protector can be remotely supervised and managed by the Intelligent Power Manager (IPM) application.
380, 400, or 415 Vac. Before operating the UPS, confirm the UPS nominal voltage and frequency from display by selecting Settings -> Info. If the UPS need to be operated with another voltage or frequency, contact your closest Eaton office or Eaton authorized partner. •...
Figure 6-3: Parts of the Touch Screen Figure 6-4: Sign In or Password Request Screen The UPS status area automatically displays the Eaton model number, current time and date, active alarms, active notices, and load percent and battery run time for the UPS. If the Environmental Monitoring Probe is installed, the temperature and humidity sensed by the probe will also be displayed.
Figure 6-42: Configuration Options Screen Service Screen The "Service" screen is only used for Eaton service engineers, as shown in the figure below: EATON 9395XR Figure 6-43: Prompt for level 3 Password Screen...
NOTE The following instructions are for the Eaton Corporation-supplied EPO switch. If a customersuppliedEPO switch is used, it may not activate in the same manner; refer to the operating instructions provided with the switch.
The UPS preventive maintenance including inspection and annual maintenance is necessary, suggest it’s carried by Eaton professional engineer to ensure the UPS and battery are working in normal status. Majority of the work must be performed by Eaton authorized service personnel. Only the actions described in Section 7.2.1...
Eaton 9395XR Series UPS Installation and Operation Manual Chapter 8 TECHNICAL DATA For complete technical specification, contact your Eaton representative. Due to continuous product improvement programs, specifications are subject to change without notice. 8.1. Standards Table 8-1: Standards Safety IEC 62040-1, IEC 60950-1...
If the product fails to meet its published specifications due to a defect in material and workmanship, covered by this warranty, the seller will repair or replace the warranted product. Such repair or replacement will be made by Eaton or by a service provider approved by Eaton.
Air conditioning equipment is installed and operating correctly. The area around the installed UPS system is clean and dust-free. (Eaton recommends that the UPS be installed on a level floor suitable for computer or electronic equipment.) Adequate workspace exists around the UPS and other cabinets.
Pull chain wiring between the UPSs is properly installed. Adequate workspace exists around the UPSs, parallel tie cabinet, and other cabinets. Startup and operational checks are performed by an authorised Eaton Customer Service Engineer, for parallel systems. Battery wire has correctly polarity and installation.