Eaton 9395XR Series Installation And Operation Manual
Eaton 9395XR Series Installation And Operation Manual

Eaton 9395XR Series Installation And Operation Manual

Table of Contents

Advertisement

Quick Links

Eaton
®
9395XR UPS
9395XR Series
Installation and Operation Manual

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 9395XR Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Eaton 9395XR Series

  • Page 1 Eaton ® 9395XR UPS 9395XR Series Installation and Operation Manual...
  • Page 3 Please adhere to the warnings and instructions specified in the manual and on the equipment, and keep the manual properly for future reference. Do not try to operate the equipment before reading all the safety information and operation instructions The manual applies to the 9395XR series, including: 9395XR-1500 9395XR-1800...
  • Page 4: All Rights Reserved

    The contents of this manual are the copyright of the publisher and may not be reproduced (even extracts) without the written approval of Eaton Corporation. Every care has been taken to ensure the accuracy of the information contained in this manual, but no liability can be accepted for any errors or omission. The right to make design...
  • Page 5: Table Of Contents

    4.2. Inspecting and Unpacking the UPS Cabinets....................33 4.3. Instruction for Removing the UPM Module Packaging ..................36 4.4. Instruction for Removing the Top Exhaust Accessory Packaging ..............37 4.5. UPS System Installation ..........................38 Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 6 Starting the UPS System in Double Conversion Mode ..............83 6.3.2. Starting the UPS System in Bypass Mode ..................83 6.3.3. Transfer from Double Conversion Mode to Bypass Mode ..............84 Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 7 8.3. UPS System Output ............................99 8.4. Battery Specification ............................100 8.5. UPS Environmental Specifications ........................ 100 Chapter 9 WARRANTY ............................... 102 Chapter 10 INSTALLATION CHECKLIST .......................... 103 Chapter 11 APPENDIX A: USER SETTINGS ........................105 Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 8 Figure 5-7: Industrial Relay Card............................66 Figure 6-1: UPS Controls and Indicators ..........................69 Figure 6-2: UPS Color Touch screen Control Panel (Typical) ....................70 Figure 6-3: Parts of the Touch Screen ..........................72 Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 9 Figure 6-46: Maintenance Bypass Mode ..........................100 Figure 6-47: Maintenance Bypass Mode ..........................101 Figure 6-48: Double Conversion Mode..........................101 Figure 7-1: WEEE Symbol..............................104 Figure 7-2: Recycling Batteries Symbol ..........................104 Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 10 Table 8-6: Information copied from Table B1 of ANSI/ISA-71.04-2013 for G1 equipment ........... 101 Table 8-7: Meet the transportation and storage environment requirements ................ 101 Table 11-1: User Settings ..............................105 Table 11-2: Config Settings ..............................105 Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 11: Chapter 1 Safety Instructions Tions

    Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic. • IMPORTANT: the battery may consist of multiple parallel strings, disconnect all strings before installation. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 12 End forklift slots may be used for minor positioning if the forks are kept in a horizontal position with no upward angling. If these instructions are not followed, damage to the wiring channel and wiring will occur. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 13: Ce Marking

    CAUTION • The 9395XR series models are available as C2 UPS product which can be placed both in a residential and commercial/industrial environment. When included in a residential environment, this product may cause radio interference, in which case the user may be required to take additional measures.
  • Page 14: Conventions Used In This Manual

    This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 15: Table 1-1: Acronyms And Abbreviations

    Energy Saver System VMMS Variable Module Management System Advanced Battery Management IO cabinet Cabinet for wiring UPM cabinet The cabinet used to install UPM Input relay Battery relay Inverter relay Integrated backfeed protection Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 16: Environment

    Scheduling initial startup • User’s and Installation Guide • Regional locations and telephone numbers • A question about any of the information in this manual • A question this manual does not answer Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 17: Chapter 2 Introduction

    AC power to critical load and protects it from power failures. Eaton 9395XR Series UPS has flexible power scalability from 125 kW to 6MW, hot swappable modular and standard design, high flexibility and applicability, market leading efficiency, availability and performance, very suitable to applications of multi tenant data center (MTDC), small-middle-large data center, automation, medical etc.
  • Page 18: Figure 2-1: Eaton 9395Xr 1500Kw Ups

    Figure 2-1: Eaton 9395XR 1500kW UPS Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 19: Figure 2-2: Components Layout (1500Kw)

    Universal Power Podule (UPM) Communication Module (CM) (optional)* Machine Control Unit (MCU) Static Transfer Switch (STS) Baffle Plates *: These accessories are only for the top exhaust system. Figure 2-2: Components Layout (1500kW) Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 20: Figure 2-3: Eaton 9395Xr 1800Kw Ups

    Figure 2-3: Eaton 9395XR 1800kW UPS Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 21: Figure 2-4: Components Layout (1800Kw)

    Eaton 9395XR Series UPS Installation and Operation Manual Figure 2-4: Components Layout (1800kW) Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 22: Figure 2-5: Components Layout (125Kw Upm)

    Positioning Lock Cold start Button Status Indicator* Position Lock Table 6-1 *: For a detailed of the Status Indicator functions, see Figure 2-5: Components Layout (125kW UPM) Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 23: Looking Inside The Ups System

    Installation and Operation Manual 2.1. Looking Inside the UPS System The system level static bypass in the 9395XR series UPS determines the attainable output power of the UPS. The static bypass line consists of static switch and a optional backfeed protection isolation device connected in series.
  • Page 24: Figure 2-6: 9395Xr 1500Kw Ups Wiring Diagram

    Figure 2-6: 9395XR 1500kW UPS Wiring Diagram Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 25: Figure 2-7: 9395Xr 1800Kw Ups Wiring Diagram

    Eaton 9395XR Series UPS Installation and Operation Manual Figure 2-7: 9395XR 1800kW UPS Wiring Diagram Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 26: Ups Operating Modes

    Online” is displayed on the front panel, indicating that the incoming power is within voltage and frequency acceptance windows. Double Conversion Mode Figure 2-8 shows the path of electrical power through the UPS system when the UPS is operating in Double Conversion Mode. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 27: Figure 2-8: Path Of Current Through The Ups In Double Conversion Mode

    UPS supporting power less than N-1 UPM rated power. However, if there is no redundancy between the UPMs due to high load level, the UPS switches automatically to Bypass Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 28: Figure 2-9: Path Of Current Through The Ups In Energy Saver System

    Energy Saver System increases system efficiency up to 99% when supplying 20-100% nominal load, reducing energy losses by up to 80%. Internal relay contacts Figure 2-9: Path of current through the UPS in Energy Saver System Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 29: Stored Energy And Battery Mode

    Unless utility power is restored, the output can be supported for maximum two minutes before the output of the system shuts down. If the bypass source is available, the UPS transfers to bypass instead of shutting down. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 30: Bypass Mode

    The backfeed Copyright © 2024 Eaton Corporation plc. All rights reserved. protection is normally always closed, ready to support the static switch unless the bypass input...
  • Page 31: Ups Features

    2.3. UPS Features The Eaton UPS has many features that provide cost-effective and consistently reliable power protection. The feature descriptions provide a brief overview of the UPS standard features. 2.3.1.
  • Page 32: Module Hot Swap Feature

    2.3.4. Variable Module Management System (VMMS) Eaton Variable Management Module System (VMMS) is a key component of Eaton EAA(Energy Advantage Architecture). Eaton VMMS technology maximizes UPS efficiencies at low load levels while supporting the load with continuous double conversion power but increase the system efficiency by dynamic adjusting the UPM active and idle.
  • Page 33: External Battery Cabinet (Ebc)

    The Eaton Sync Control maintains critical load synchronization of either two separate single Eaton UPS systems or two separate single Eaton UPS systems. Synchronization of the UPS systems facilitates the uninterrupted transfer of customer loads from one load bus to another by means of downstream, dual source, solid state transfer switches.
  • Page 34: Basic System Configurations

    The UPS frames can be connected in parallel to create even larger systems. A maximum of four 9395XR UPS frames can be connected in parallel. Above four UPS in parallel requirement can ask help from Eaton technical solution team to customization design.
  • Page 35: Chapter 3 Ups Installation Plan And Unpacking

    Chapter 10 6. Have authorized service personnel perform preliminary operational checks and startup. NOTE Startup and operational checks must be performed by an authorized Eaton Customer Service Engineer, Chapter 9 or the warranty terms specified in become void. This service is offered as part of the sales contract for the UPS.
  • Page 36: Table 3-1: Dimensions And Weights

    When ignored, either one of these aspects can create an undesirable microclimate at the UPS location. If the environment created by this microclimate exceeds the Eaton UPS operating specification, the UPS reliability, over time, will be reduced. These same environmental extremes will also create reliability concerns for any servers that are exposed to them.
  • Page 37: Figure 3-1: Ups Cabinet Clearances

    1000 mm 1000 mm From Back of Cabinet 800 mm* 0 mm** * Cabling may require more space. The picture takes a 1500kW cabinet as an example Figure 3-1: UPS Cabinet Clearances Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 38: Table 3-3: Air Conditioning Or Ventilation Requirements During Full Load Operation

    The UPS ventilation requirements are shown in the following table: Table 3-3: Air conditioning or Ventilation Requirements During Full Load Operation Rating Heat Rejection (Kcal/hour) Heat Rejection (BTU/h x 1000) 1500kW 48305 191.74 1800kW 58632 232.8 Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 39: Figure 3-2: 1500Kw Ups Dimensions

    Eaton 9395XR Series UPS Installation and Operation Manual TOP VIEW FRONT VIEW RIGHT VIEW BOTTOM VIEW Figure 3-2: 1500kW UPS Dimensions Dimensions are in millimetres Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 40: Figure 3-3: 1500Kw Ups Dimensions With Top Exhaust Accessory

    1600 1100 Figure 3-3: 1500kW UPS Dimensions with Top Exhaust Accessory Dimensions are in millimetres Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 41: Figure 3-4: 1800Kw Ups Dimensions

    .. .. .. .. 、 、 .. .. .. .. .. .. .. � . . � 霓 . . 酒 BO丁TOM Figure 3-4: 1800kW UPS Dimensions Dimensions are in millimetres Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 42: Figure 3-5: 1800Kw Ups Dimensions With Top Exhaust Accessory

    76.2 Ø38 186.2 2402.4 840.3 1100 Ø14 55.2 Figure 3-5: 1800kW UPS Dimensions with Top Exhaust Accessory Dimensions are in millimetres Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 43: Figure 3-6: Upm Dimensions

    Eaton 9395XR Series UPS Installation and Operation Manual Left View Right View Top View Front View Figure 3-6: UPM Dimensions Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 44: Ups System Power Wiring Preparation

    If the neutral wire is disconnected, all phase wires should be disconnected at the same time. 3-wire system: • The input uses three live wires and grounding wires (protective grounding conductors). • Without the N-line, it does not support the load that requires the N-line. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 45: Table 3-4: Maximum Recommended Multi-Core Cable Sizes (Unit:mm 2 )

    12*125kW 2374 2255 2174 2279 2165 2078 3255 4688 2849 2706 2608 2735 2598 2504 3906 15*125kW NOTE Bypass fuse type should be greater than 10 times rated I t 20ms. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 46: Table 3-7: Ups Power Cable Terminations

    Inrush or Starting Current. Bypass and output overcurrent protection and bypass and output disconnect switches are to be provided by the user. For UPS wiring diagrams, see Section Looking inside the UPS system. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 47: Ups System Interface Wiring Preparation

    Alarm relay contacts have a maximum current rating of 5 A and a switched voltage rating of 30 Vac (RMS) and 30 Vdc. • Alarm relay wiring should be a minimum of 0.75 mm². Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 48: Chapter 4 Ups System Installation

    2. Use a forklift or pallet jack to move the packaged cabinet to the installation site, or as close as possible, before unpacking. If possible, move the cabinets using the pallet. Insert the forklift or pallet jack forks between the supports on the bottom of the pallet. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 49 1500kW UPS. NOTE While waiting for installation, protect the unpacked cabinet from moisture, dust, and other harmful contaminants. Failure to store and protect the UPS properly may void your warranty. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 50: Figure 4-1: Straighten The Securing Tabs

    The picture takes a 1500kW cabinet as an example securing tabs Figure 4-1: Straighten the Securing Tabs Figure 4-2: Remove Wooden Box Figure 4-5: Fork into Position Figure 4-3: Remove Cushioning Figure 4-4: Remove the Shipping Bracket Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 51: Instruction For Removing The Upm Module Packaging

    Check whether the UPS is damaged during the process of transportation or not. Should any damage be observed or parts be found missing, do not start the machine. Contact the forwarder and distributor immediately. Figure 4-6: Instruction for Removing the UPM Module Packaging Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 52: Instruction For Removing The Top Exhaust Accessory Packaging

    Should any damage be observed or parts be found missing, do not start the machine. Contact the forwarder and distributor immediately. Figure 4-7: Instruction for Removing the Top Exhaust Accessory Packaging Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 53: Ups System Installation

    These machine is too heavy, make sure the ground is able to withstand. The picture takes a 1500kW cabinet as an example Assemble hang bolts(4pcs) at the top of the cabinet. (4-M10 bolts) ≥45 Figure 4-8: Lifting diagram schematic Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 54: Routing Cables

    7. If installing a parallel system, repeat the above steps to all units in the system. 8. Proceed to Section WARNING Custom should take care to arrange cables to left and right sides of cabinet when doing wiring, avoid blocking the rear vent of UPM. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 55: Ups System Installation

    4. Clean the residual debris in the cabinet and install the front upper covers of the IO cabinet of the primary cabinet and the IO cabinet of secondary cabinet; 5. If installing a parallel system, repeat the above steps to all units in the system. 6. Proceed to Section Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 56: Figure 4-9: Gland Plate And Connector Locations 1500Kw (Top Exhaust)

    BAT- BAT+ Output RECTIFIER Input Bypass Input Ground Signal Entry TOP VIEW FRONT VIEW Figure 4-9: Gland Plate and Connector Locations 1500kW (Top Exhaust) Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 57: Figure 4-10: Gland Plate And Connector Locations 1800Kw (Top Exhaust)

    · DC - > 。 . · 参 0- , 。 。 。 。 。 。 。 @ @ @ @ FRONT 詹 Figure 4-10: Gland Plate and Connector Locations 1800kW (Top Exhaust) Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 58: Battery System Installation

    The default battery settings of the UPS are for 12 Vdc VRLA batteries. If requested to use other battery types, contact your Eaton representative. For the battery specification, see Section Connect the battery cabinet as follows: 1.
  • Page 59: Supported Battery Configuration

    UPS EnergyAware kits to utilize Time of Use and peak shaving BESS application. Eaton UPS can protect the critical load without comprise and also fully mining the value of lithium battery. Regarding to 9395XR UPS BESS feature, please contact with Eaton for more details.
  • Page 60 A full list of supported lithium battery brands can be obtained from Eaton local representatives. 9395XR UPS provides 2 kinds of RS485 port (Modbus protocol) connection methods to connect to the lithium battery cabinet. The UPS side can choose the TB terminal interface (See Cabinet...
  • Page 61: Figure 4-11: Separate Battery Configurations (1500Kw)

    Eaton 9395XR Series UPS Installation and Operation Manual Figure 4-11: Separate Battery Configurations (1500kW) Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 62: Figure 4-12: Separate Battery Configurations (1800Kw)

    Figure 4-12: Separate Battery Configurations (1800kW) Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 63: Installing A Remote Epo Switch

    (1500kW) UPS Section REPO TB REPO Twisted Switch Wires (NO) Figure 4-13: Normally-Open REPO Switch Wiring NOTE The REPO switch must be a latching-type switch not tied to any other circuits. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 64: Figure 4-14: Normally-Closed Repo Switch Wiring

    (1500kW) REPO Twisted UPS Section Switch Wires REPO TB (NC) Figure 4-14: Normally-Closed REPO Switch Wiring NOTE The REPO switch must be a latching-type switch not tied to any other circuits. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 65: Installing Interface Connections

    4.9.2. External Battery Breaker Wiring Interface When using the original battery cabinet from the Eaton, the battery breaker interface wiring is provided with the cabinet. Connecting it requires only routing the wires from the cabinet to the top section of the UPS.
  • Page 66: Relay Output Interface Connections

    Chapter 5 For Mini-slot accessories and communication devices selection see . For installation and setup of a Mini-slot card, please contact your Eaton representative. To install wiring to connections: If not already installed, install the LAN and telephone drops. 2. Open the front door of the UPS.
  • Page 67: Wiring Parallel 9395Xr Ups Systems

    UPS frames can be connected in parallel. The UPS static bypass power rating needs to be identical among all paralleled units. However, paralleled UPS cabinets can be housed with different number of UPM power modules. If more than 4 UPS needed in parallel system, please contact local Eaton representatives for more detail.
  • Page 68 Ensure that each UPS static bypass is fed from a single common source, as is an external bypass switch if installed. If each UPS is fed with a separate rectifier source, please consult Eaton for advice on compatibility. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 69: Figure 4-15: Principle Of Paralleled Ups Systems (1500Kw)

    Eaton 9395XR Series UPS Installation and Operation Manual Figure 4-15: Principle of Paralleled UPS Systems (1500kW) Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 70: Control Signals Overview

    2. 12-pin terminal block for external parallel control signals is accessible on the left side of the communication interface, on the top section of the UPS. 3. The Phoenix Contact Figure 4-16: Simplified CAN and Pull-Chain Wiring for Parallel UPS System Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 71: Figure 4-17: Can And Pull-Chain Wiring For Parallel Ups

    This drawing is for distributed bypass wiring purposes and is not a floor layout plan. UPSs can be placed in any physical order. NOTE External CAN connections between UPSs require 3-core shielded twisted pair wire (22AWG). Figure 4-17: CAN and Pull-Chain Wiring for Parallel UPS Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 72: Installing Eaton Sync Control

    4.10.4. Installing Eaton Sync Control Refer to the operating instructions provided with the Eaton Sync Control. UPS Relay Common – – – Bypass Volts Phase A – Bypass Volts Phase B – Bypass Volts Phase C – Output Volts Phase A –...
  • Page 73: Chapter 5 Communication Interfaces

    9. Customer CAN 10.CAN Terminal 11.RS-232 Port for Service (EPO) 14. External Battery Breaker External Parallel Con- 13. Output Relay 16. Voltage test ports Trip & Auxiliary nector 17. Voltage test ports Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 74: Mini-Slots

    • Gigabit Network Card The Eaton Gigabit Network Card (Network-M2) is Eaton’s latest UPS network management card that delivers IT professionals with new and exciting capabilities and features. With better speed and cybersecurity, the Gigabit Network Card improves business continuity by providing warnings of pending issues to administrators and helping to perform orderly shutdown of servers and storage.
  • Page 75: Figure 5-4: Industrial Gateway Card

    • Industrial Gateway Card The Eaton Industrial Gateway Card (INDGW-M2) combines the features of an SNMP agent, HTTP/ web server and a Modbus card to facilitate remote monitoring of your UPS system through any Building Management System. Enjoy the freedom to customize and schedule actions, like shutdown protocols and load shedding, and receive immediate notifications during power events, without having to be onsite.
  • Page 76: Figure 5-6: Relay Card-Ms

    Amperes through its 5 relay connections. By connecting wires to the corresponding places in its terminal blocks you can choose Normally Open or Normally Closed setup for each output. Figure 5-7: Industrial Relay Card Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 77: Intelligent Power Software

    Protector (IPP) application provides automatic, graceful shutdown of computers and virtual machines or servers powered by an Eaton UPS during a power outage that lasts longer than your available battery runtime. Intelligent Power Protector can be remotely supervised and managed by the Intelligent Power Manager (IPM) application.
  • Page 78: Chapter 6 Ups Operating Instructions

    380, 400, or 415 Vac. Before operating the UPS, confirm the UPS nominal voltage and frequency from display by selecting Settings -> Info. If the UPS need to be operated with another voltage or frequency, contact your closest Eaton office or Eaton authorized partner. •...
  • Page 79: Figure 6-1: Ups Controls And Indicators

    Bypass Mode Yellow Yellow turn off, from shut down mode to bypass mode. Mode Green Green Blue VMMS Mode Green Green Blue flashing Mode Yellow Yellow, Green Green flashing Alarm or Fault Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 80: Control Panel

    When the unit powers up, the screen displays as shown in the figure above. When power is applied to the system, the display advances to the Sign In screen shown Parts of the Touch Screen. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 81: Status Indicators

    There are three attempts to input the password. If an incorrect password is given more than three times, you need to wait for 30 minutes before trying again. To modify the user settings, you need Chapter 11 to enter level 2 password.For the default passwords, Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 82: Figure 6-3: Parts Of The Touch Screen

    Figure 6-3: Parts of the Touch Screen Figure 6-4: Sign In or Password Request Screen The UPS status area automatically displays the Eaton model number, current time and date, active alarms, active notices, and load percent and battery run time for the UPS. If the Environmental Monitoring Probe is installed, the temperature and humidity sensed by the probe will also be displayed.
  • Page 83: Home Screen(Online)

    Settings include date and time for the time stamp, display language, the unit Settings Configuration name, meter subscripts, password, and view the firmware version numbers Used only by service personnel. See Chapter 11 for details. Service Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 84: Figure 6-5: Home Screen

    Screens shown are representative examples of system operation. The screen data will vary based on system activity at the time of observation. Figure 6-6 Touching the LOAD kVA button displays the Output kVA screen shown in Figure 6-6: Output kVA Screen from Home Screen Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 85: Figure 6-7: Average Efficiency Screen From Home Screen

    Touching the AVERAGE EFFICIENCY button displays the system efficiency screen shown in Figure 6-7 Figure 6-7: Average Efficiency Screen from Home Screen Figure 6-8 Touching the CONSUMPTION button displays the screen shown in Figure 6-8: Consumption Screen from Home Screen Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 86: Meters

    Home Screen Home Screen Input Meters Screen Figure 6-10 shows the Input Meters screen. This screen displays the individual phase and total power values of the system. Figure 6-10: Input Meters Screen Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 87: Figure 6-11: Bypass Meters Screen

    Bypass conditions. Figure 6-11: Bypass Meters Screen Output Meters Screen Figure 6-12 The Output Meters Screen shown in displays values pertaining to the system output. Figure 6-12: Output Meters Screen Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 88: Figure 6-13: Input Meters Detail Screen

    Figure 6-14: Online Mode Metering Method Option Screen Figure 6-15 The Select Source screen shown in allows the operator to choose the individual source for system readings. Figure 6-15: Select Source Screen Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 89: Figure 6-16: Battery Meters Screens

    Figure 6-18 Click the "Current" button, show a profile of battery Current over various time periods of 24 hours, 7 days, 30 days, or 1 year. Figure 6-18: Battery Current Screens Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 90: Figure 6-19: Lithium Battery Measurement Screen

    The lithium battery page mainly displays the following parameters: SOC, SOH, cell voltage, cell temperature. When the UPS lithium battery is abnormal, the HMI interface will display relevant alarms. Figure 6-20: Lithium battery interface Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 91: Controls

    UPS is in “online mode” or “bypass mode”. shows the System Status screen. Figure 6-21: System Controls Screen UPS Controls Screen This screen can control the charger, battery test and UPS status. Figure 6-22: UPS Controls Screen Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 92: Figure 6-23: Module Controls Screen

    Figure 6-24: Module Control Detail Screen Select the "Turn On Charger" button, there will be a pop-up screen to confirm the request. Figure 6-25: Turn On Charger confirmscreen Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 93: Figure 6-26: Energy Advantage Architecture (Eaa) Screen

    2.2.1 Figure 6-27: Enable ESS Confirmscreen Select the "Enable VMMS" button, there will be a pop-up screen to confirm the request. For details, see Section 2.3.4 Figure 6-28: Enable VMMS Confirmscreen Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 94: Mimics

    Press the "UPM Mimic " on the main menu to display the mimic screen, which is used to observe the power flow, as shown in the figure below: Figure 6-31: UPS Mimic Screen Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 95: Figure 6-32: Ups Module Map Screen

    UPS and UPM parameters. Figure 6-33: System Overview Screen Figure 6-34 The screen shown allows the operator to visually obtain ESS mode efficiency values. Figure 6-34: ESS Screen Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 96: Logs

    This message is also written to the Active Events log. Some notices and alarms may be accompanied by an audible horn. To silence the horn, press any button once. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 97: Figure 6-36: System Log Screen

    Figure 6-37: Active Event Detail Screen Service Log Screen The "Service Log" screen displays service alarms, service notifications and service status, as shown in the figure below: Figure 6-38: Service Log Screen Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 98: Statistics

    Touching the CLEAN SCREEN button disables the screen for 30 seconds to allow the user to safely clean the screen without affecting operation. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 99: Figure 6-41: User Screen Screen

    Figure 6-42: Configuration Options Screen Service Screen The "Service" screen is only used for Eaton service engineers, as shown in the figure below: EATON 9395XR Figure 6-43: Prompt for level 3 Password Screen...
  • Page 100: System Control Instructions

    If the inverter output of the UPS is not available and the critical load needs to be energized, perform the following procedure: CAUTION In Bypass Mode, the critical load is not protected from commercial power interruptions and abnormalities. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 101: Transfer From Double Conversion Mode To Bypass Mode

    2. Press the Go online button on the System controls screen. The UPS system transfers to double conver sion mode. If enough UPM capacity is not available, the system remains on bypass and an alarm sounds. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 102: Transfer From Double Conversion Mode To Energy Saver System Mode

    DANGER Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is opened. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 103: Energizing The Critical Load

    1. Unfasten the front door latch and swing the door open. 2. Close the UPS input feeder circuit breaker. 3. Close the UPS bypass input feeder circuit breaker. 4. Observe the UPS control panel display becoming active, indicating logic power. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 104: Ups Shutdown

    3. Press the Start charger / Stop charger button. 6.5. UPM Control Instructions 6.5.1. Adding/Reducing/Replacing Modules Online N+X is the most reliable power supply configuration at present. N represents the minimum Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 105 The “permitted maximum power” indicates the three-phase power, so the permitted maximum power of single- phase needs to be divided by three. The 9395XR UPS module is hot swappable, but to perform this process, some definite Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 106 ESC key on the LCD panel the cold start button. 9. UPM installation is complete. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 107: Figure 6-44: Upm Module Location

    2. To replace UPM, please implement removing UPM steps and then do adding UPM steps. WARNING Ensure the lock has to unlock the state, when pull out the UPM. The picture takes a 1500kW cabinet as an example Position Lock Figure 6-44: UPM Module Location Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 108: Starting The Upms

    2. On the System controls screen, press Module controls. Select module screen is displayed. 3. Select the UPM you want to shut down (UPM 1 - UPM X). 4. On the UPM control screen, select Shut down module. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 109: Using The Remote Emergency Power-Off Switch

    NOTE The following instructions are for the Eaton Corporation-supplied EPO switch. If a customersuppliedEPO switch is used, it may not activate in the same manner; refer to the operating instructions provided with the switch.
  • Page 110: Transfer The Ups From Double Conversion Mode To Maintenance Bypass Mode

    UPS is now in the Maintenance Bypass Mode: Maintenance bypass switch (MBS) Maintenance bypass input Static bypass input Bypass switch Output Rectifier input Input switch Output switch Figure 6-46: Maintenance Bypass Mode Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 111: Transfer Ups From Maintenance Bypass To Double Conversion Mode

    The UPS is now in Double Conversion Mode Maintenance bypass switch (MBS) Maintenance bypass input Static bypass input Bypass switch Rectifier input Output Output switch Input switch Figure 6-48: Double Conversion Mode Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 112: Chapter 7 Ups Maintenance

    • When replacing batteries, use the same number of sealed, lead-acid batteries. • Proper disposal of batteries is required. Refer to your local codes for disposal requirements. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 113: Performing Preventive Maintenance

    The UPS preventive maintenance including inspection and annual maintenance is necessary, suggest it’s carried by Eaton professional engineer to ensure the UPS and battery are working in normal status. Majority of the work must be performed by Eaton authorized service personnel. Only the actions described in Section 7.2.1...
  • Page 114: Annual Maintenance

    Follow ALL applicable, local regultions for storage, handling and disposal of batteries and battery materials. Figure 7-2: Recycling Batteries Symbol 7.4. Maintenance Training For more information about training and other services, contact your Eaton representative. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 115: Chapter 8 Technical Data

    Eaton 9395XR Series UPS Installation and Operation Manual Chapter 8 TECHNICAL DATA For complete technical specification, contact your Eaton representative. Due to continuous product improvement programs, specifications are subject to change without notice. 8.1. Standards Table 8-1: Standards Safety IEC 62040-1, IEC 60950-1...
  • Page 116: Ups System Output

    10 ms 1000% load (on Bypass) Note! Bypass fuses may limit the overload capability. Output Current Table 3-6 Load Power Factor, (Rated) Load Power Factor, (Permitted Range) From 0.8 lagging to 0.8 leading Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 117: Battery Specification

    At 1m per ISO 7779 standard Acoustic Noise at 1 m ≦ 85 dB Class: C3 (GB 7260.2 / IEC 62040-2) Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 118: Table 8-6: Information Copied From Table B1 Of Ansi/Isa-71.04-2013 For G1 Equipment

    Storage condition for UPS and spare parts store one year (refer unit SN). Place Indoor Dusty Well Storage Temperature <40°C Storage Humidity < 70% RH Other With original package Please re –evaluate the storage time if can not meet above storage condition. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 119: Chapter 9 Warranty

    If the product fails to meet its published specifications due to a defect in material and workmanship, covered by this warranty, the seller will repair or replace the warranted product. Such repair or replacement will be made by Eaton or by a service provider approved by Eaton.
  • Page 120: Chapter 10 Installation Checklist

     Air conditioning equipment is installed and operating correctly.  The area around the installed UPS system is clean and dust-free. (Eaton recommends that the UPS be installed on a  level floor suitable for computer or electronic equipment.) Adequate workspace exists around the UPS and other cabinets.
  • Page 121: Parallel System Installation Checklist

    Pull chain wiring between the UPSs is properly installed.  Adequate workspace exists around the UPSs, parallel tie cabinet, and other cabinets.  Startup and operational checks are performed by an authorised Eaton Customer Service Engineer, for parallel  systems. Battery wire has correctly polarity and installation.
  • Page 122: Appendix A: User Settings

    Adjust the backlight brightness. Change the level 1 password, or remove the password on Control P/W level 1 level 1. The default value is 1111. Config P/W level 2 Change the level 2 password. Copyright © 2024 Eaton Corporation plc. All rights reserved.
  • Page 124 614-40279-00...

This manual is also suitable for:

9395xr-15009395xr-1800