GSC300 Auto Start Engine Controller Revision 2.9 Installation and User Manual for the GSC300 Auto Start Engine Controller File: MAN-0039 R2.9, GSC300 User Manual.doc May 2011...
(RMA) number issued by DynaGen. Limited Warranty For warranty information refer to the standard terms and conditions of sale at http://www.dynagen.ca. Dynagen GSC300 Webpage For up-to-date manuals and other information please see the GSC300 section of the DynaGen www.dynagen.ca/products/GSC300.htm or www.dynagen.ca/support website at:...
Page 3
3 of 29 GSC300 Specifications Operating Voltage 7 to 30VDC continuous Zero volts operation for 100mS (assumes supply was 12VDC before initiating starting) Operating -40 ºC to +85 ºC (LCD Display operates from to -16 ºC to 70 ºC) Temperature Physical Dimensions 4.5"(H) x 5.5"(W) x 1.25"(D)
Page 4
4 of 29 -All outputs switched to +battery (sourcing) Outputs -Fuel, Crank, and Timer Outputs: (12V/40A or 24V/20A) each, using standard 40A automotive relays -Annunciation Outputs: 300mA individually, 350mA combined Connections -Removable terminal block for annunciation outputs and low power connections -0.25"...
6 of 29 1. GSC300 Product Number Identification The GSC300 series catalog order number provides information pertaining to a specific model. The Product Number Identification Table (see Table 1) provides details on the breakdown of the model number. Table 1 – Identification Table...
7 of 29 2. Wiring Installation Guidelines Danger: Never work on the engine while its power is on. This controller does not generate a warning signal prior to automatic engine start. Warning signs should be placed on engine equipment indicating this important safety measure.
Consult factory for further details. 6. Engine Sensor type MUST be selected and programmed properly to GSC300 (switch or sender type). Failure to do so may result in the controller not shutting down on true engine failure (Low oil pressure or high engine temperature).
SYSTEM OPERATION Figure 1 The GSC300 controller is designed to operate in either 12 or 24VDC system voltages. When operating in 12VDC systems the Fuel, Crank and Preheat/ETS relays need to be the 12VDC relay type. When operating in 24VDC systems these relays need to be the 24VDC relay type.
The magnetic pickup only works for frequencies up to 3000Hz (this is max of 100 teeth at 60Hz) General The GSC300 does not have loss of speed detection. If there is no speed signal during cranking/run but the genset starts up and runs the starter will remain engaged for the remainder of the crank cycle.
Low Oil Pressure sensor input. This sensor can be the resistive type (Sender) or can be the switch type. The proper type of sensor must be selected during GSC300 controller programming. The sender or switch must be connected to ground for proper operation.
Page 12
Figure 2 – GSC300 System Wiring Diagram...
13 of 29 2.6 Back Panel Layout PRE-HEAT PRE-HEAT NO AUX SWITCH INPUT RELAY TEMP. SWITCH INPUT SPEED SIGNAL PRE-HEAT COM INPUTS OIL SWITCH INPUT REMOTE START INPUT BATTERY GROUND GENERAL FAIL OUTPUT BATTERY GROUND NOT IN AUTO OUTPUT CRANK ENGINE RUN OUTPUT RELAY STARTER OUTPUT...
(AUTO or OFF). OFF mode can be entered by pressing the OFF button on the front panel. When the GSC300 is in the OFF mode the “Not In Auto” LED will be lit on the front panel (NOT IN AUTO below).
Page 15
15 of 29 LOW OIL INPUT: The Low Oil Input can be wired to a resistive sender or from a NO or NC type switch. NO / NC refers to the state of the contacts during normal engine operation (engine oil pressure ok).
Page 16
16 of 29 HOUR METER: The controller displays a log of total accumulated generator running hours. Generator Run times will be displayed on the controllers display screen. The display represents both hours and minutes in the form 123456:7. The last digit on the hour meter will represent the time in 1/10 of an hour.
18 of 29 3.3 LED Indications The GSC300 does not have a LED lamp test feature. Table 4 – Front Panel LED Indications LED Appearance Condition/Failure Unit is in OFF state, and automatic Not in Auto LED is ON. starting is disabled “OFF”, no +12/24VDC to main power...
19 of 29 4. Programming the GSC300 Settings 4.1 Using the Front Panel Interface The following table shows the LED’s that correspond to the various settings of the various parameters. To enter the controller into Program Mode, you need to move the small switch at the bottom edge of the controller to the Program position (the Program position is to the left).
Page 20
To scroll through the parameters simply press the Auto button on the front panel of the GSC300. To scroll through the range of values for that parameter simply press the Manual Start button. To program the value into the controller’s memory, press the OFF button. In this manner the settings of the controller can be adjusted by simply using the three buttons on the front panel of the controller.
GSC300 Configurator software. A sample interface screen is illustrated on the following page. General Programming Notes 1. The GSC300 must be unpowered when programming. Ensure it is not connected to battery or other power source. Parallel Port Programming Note 1.
23 of 29 5. Troubleshooting Guidelines TROUBLE POSSIBLE CAUSE SUGGESTED ACTION Unit does not operate when Power leads to unit are reversed Confirm correct wiring for ground and +bat, powered to test mode and re-attempt testing. Bad ground connection from engine to Run wire directly from battery - to the controller unit.
6.1 Controller Memory Clear Time The GSC300 needs 10 seconds for its memory to clear. When the power to the controller is turned off and then back on again without waiting 10 seconds to clear the memory, a loss of speed will may be indicated by the GSC300 (if controller is in AUTO mode and start signal is activated) because the controller remains in run mode and senses that the generator has stopped.
The GSC300 crank output can be attached to the pull coil and the GSC300 fuel output can be attached to the hold coil. When the engine is started the fuel and crank output will come on activating both coils but after cranking is successful the crank output will turn off de-energizing the pull coil.
Page 26
26 of 29 Figure 8 – GCP300 Drawing Figure 9 – GCP300 User Terminal Block Label...