DynaGen GSC200 Installation And User Manual

Auto start engine & transfer switch controller

Advertisement

Quick Links

GSC200
Auto Start Engine & Transfer Switch
Controller
Installation and User Manual for the GSC200 Controller
Full Version
File: GSC200_R1_1doc
8/12/2008

Advertisement

loading
Need help?

Need help?

Do you have a question about the GSC200 and is the answer not in the manual?

Questions and answers

Summary of Contents for DynaGen GSC200

  • Page 1 GSC200 Auto Start Engine & Transfer Switch Controller Installation and User Manual for the GSC200 Controller Full Version File: GSC200_R1_1doc 8/12/2008...
  • Page 2 LIMITED WARRANTY POLICY: DynaGen Technologies Inc. hereafter known as the Seller warrants articles sold hereunder to be free from defects in material and workmanship. These express warranties are the sole warranties of the Seller and any other warranties, expressed, implied in law, or implied in fact, are hereby specifically excluded.
  • Page 3 0 – 59 seconds (GREEN Engine Run LED will flash during Delay on Start) Crank Tries: 1 to 10 Failure Bypass: 10 – 55 seconds Low Battery Indication: 7 – 35 VDC Operating & Installation Manual for the GSC200 Controller...
  • Page 4 -Minimum Input Voltage: 0.7VAC RMS Generator Output Sensing -60Hz Rejection Filter Included -Loss of Speed Signal Included Failure Inputs: Oil Pressure Coolant Temperature 2 Auxiliary Inputs -Programmable for switch configuration NO or NC Operating & Installation Manual for the GSC200 Controller...
  • Page 5 -Windows based software interface utilizing the parallel port of your PC -Needs no power to program using the PC Interface – uses power from parallel port of PC -Specifications May Change Without Notification Operating & Installation Manual for the GSC200 Controller...
  • Page 6: Controller Overview

    Transfer Switch Controls Utility Sensing GENERAL FAILURE CONDITIONS The following conditions can cause the GSC200 controller to shut down the Engine Generator system unexpectedly. Low Oil Pressure Low Oil Failure is indicated by a steady on Red Low Oil pressure Led...
  • Page 7 Engine Controller. Please note that disabling the transfer switch controls does not disable or turn off the Exerciser Function, it only disables the controller from starting the generator on a loss of utility. UTILITY SENSING Operating & Installation Manual for the GSC200 Controller...
  • Page 9: Led Indications

    Utility sensing is measured from line to neutral and can accept voltages up to 300VAC. Single or three phase sensing is user selectable in the GSC200 Configurator software. LED INDICATIONS Auto Manual Auto LED High Temp Low Oil OverCrank OverSpeed Loss Speed Low Batt Engine Run...
  • Page 10 LCD DISPLAY: The LCD display will show the total time that the generator has ran. This time is displayed when the controller is in Engine run mode and can not be reset. Operating & Installation Manual for the GSC200 Controller...
  • Page 11 PROGRAMMING THE GSC200 All of the features of the GSC200 that are user selectable or adjustable can be selected or adjusted by using the GSC200 Configurator, the exception to this is the Exerciser Function which can only be programmed by the use of the front panel buttons.