Danfoss iC7 Series Operating Manual page 55

Automation functional safety
Hide thumbs Also See for iC7 Series:

Advertisement

Operating Guide | iC7-Automation Functional Safety
Table 39: Group 0x61FF
(continued)
Number
Name
4616
No valid safety parameters
available
4617
PsAlarmFdestAddMis-
match
4226
PsAlarmWdTimeout
4633
Software update on safety
module
4634
Factory reset
4635
Safety configuration
changed
4636
IO failure acknowledgment
needed
4637
STO acknowledgment
needed
4650
Parameter dependency
checks failed
4651
Parameter range check
Danfoss A/S © 2024.08
Functional Safety for Frequency Converters, Upgradable (+BEF2)
Cause
The safety parameters are invalid or not
present in the device.
Mismatch of safety destination address.
Timeout in communication to safe
module. F_WD_Time or F_WD_Time_2
elapsed.
Advanced safety unit is in a software up-
date state.
Factory reset action triggered by the user.
Safety parametrization action triggered by
user.
Due to the configuration, IO acknowledge
is needed.
Due to the configuration, STO acknowl-
edge is needed.
Check of the safety parameters failed.
The value of a parameter is out of the al-
lowed range. The variable ID is provided
as detail.
Solution
Check the safety configuration in My-
Drive® Insight. Make sure that all configu-
ration steps are successfully verified and
validated.
Recommissioning of the safe module is re-
quired.
Make sure that the addresses on the PLC
and the drive match.
Increase the F_WD_Time or
F_WD_Time_2.
The device stays in a safe state until the
software update is successfully finished.
After the factory reset has been per-
formed, the safety configuration needs to
be recreated.
The safety configuration has been
changed. Ensure that the configuration is
correct before continuing.
Major safety configuration changes may
require a system restart.
If enabled, the safety function may require
an acknowledgment to continue opera-
tion after a signal failure has been cleared.
If enabled, the safety function may re-
quire an acknowledgment to continue
operation after a STO condition has been
cleared.
Ensure that the safety configuration is
valid. The possible errors may be related
to:
• input signal mapping
• output signal mapping
• timing parameters
Make sure that the value of the given vari-
able is set in the allowed range.
AQ319741840653en-000401 / 136R0268 |
55