Operating Guide | iC7-Automation Functional Safety
Event List
4.10.4
Table 38: Group 0x54FE
Number
Name
4628
STO activated.
Table 39: Group 0x61FF
Number
Name
4608
Internal failure
4609
IO failure detected
4611
SS1
4612
SS1
4613
Warning detected
4614
Startup acknowledgment
needed
4615
Configuration mismatch
54
| Danfoss A/S © 2024.08
Functional Safety for Frequency Converters, Upgradable (+BEF2)
Cause
Safe Torque Off has been activated.
Cause
An internal failure was detected in the
safety system.
An IO failure was detected in the safety
system. See event details for more infor-
mation.
Safe Stop 1, instance 1 has been activated.
Safe Stop 1, instance 2 has been activated.
Detected a non-critical failure. The opera-
tion can continue.
Startup acknowledgment is needed.
The detected safety system differs from
the commissioned system.
Solution
If STO is activated unintentionally, check
the following:
• input cabling
• external activation
• external test pulse timing
• relevant safety parameters
Solution
Restart the system.
If the problem persists, contact Danfoss
customer support.
Check the safety IO circuit connections. If
an external test pulse is used, ensure that
the timing is within specification.
See
3.1.6 STO
Properties.
If SS1 is activated unintentionally, check
the following:
• input cabling
• external activation
• external test pulse timing
• relevant safety parameters
If SS1 is activated unintentionally, check
the following:
• input cabling
• external activation
• external test pulse timing
• relevant safety parameters
Check event logs and messages in the
user interface for additional information.
Depending on the configuration, the ac-
knowledgment can be given via:
• Safe input
• MyDrive® Insight
• Fieldbus interface
• Control panel
If an advanced safety unit is replaced,
recommission the system.
AQ319741840653en-000401 / 136R0268