Technical data
Version
Type
Sensors
Function check
Acoustic alert
Environment and permeability check
Alarm conditions for CO detector
OPERATING INSTRUCTIONS
Multisensor Plus
Techem Smart System remote inspec-
table alarm Type C, in accordance with
DIN 14676-1
Ì Smoke detection:
Photo-optical scattered light method
Ì Heat detection:
Thermistor (Class A1)
Ì CO-detection:
Carbon monoxid sensor (Type B)
Ì Temperature and relative
humidity measurement:
Temperature/humidity sensor
Ì Automatic, remotely retrievable via radio interface (not perceptible)
Ì Manual, via user button operation
Ì In case of fire/carbon monoxide alarm: at least 85 dB(A)
Ì In case of manual test: approximately 75 dB(A)
Ì In case of fault indication: approximately 75 dB(A)
Ì Regular and automatic checks
Ì Covers
Ì Obstacles within 50 cm of the device
For CO exposure:
Ì 50 ppm: between 60–90 minutes
Ì 100 ppm: between 10–40 minutes
Ì 300 ppm or more: within 3 minutes
Multisensor Plus Kitchen
Techem Smart System remote inspec-
table alarm Type C
Ì Heat detection:
Thermistor (Class A1)
Ì CO-detection:
Carbon monoxid sensor (Type B)
Ì Temperature and relative
humidity measurement:
Temperature/humidity sensorr
-