2 phase unit to drive 3 phase load from 100a to 700a

Advertisement

REVO I
2PH from 100A to 700A
Parameter Name
Pb Power
Set the gain for the main loop. A larger
value yields a larger adjustment for a
given deviation
Ti Power
Set how aggressively the integral part
of the control algorithm acts. A larger
settings yields a larger adjustment for
a given deviation over a given time
HB Sense
Set the threshold of resistance that
activates the Heater Break alarm. This
setting is in percentage of the nominal
load resistance
HB Delay
Set a delay between when the
resistance drops below the value set
for a heater break sensitivity and when
the heater break alarm is indicated.
This set increments of 50mSec
Parameter Name
Log Period
Set how often data is logged
Description
Description
50
Default
Range
10%
0 to 255
50
0 to 255
100%
0 to 100.0
0 to 255
50
(0 to 12,75
(2,5 sec)
sec)
Default
Range
5 sec
0 to 255
User's manual
Modbus
Par.
Unit
Address
Type
Read
%
26
Write
Read
27
Write
Read
%
29
Write
Read
28
Write
Modbus
Par.
Unit
Address
Type
Read
sec
70
Write