We do assure you that all persons are regarded without discrim- ination and on an equal basis. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for the user's internal purposes. Suggestions and comments for improving this documenta- tion will be gratefully received.
Changing an electronic module during operation ..............18 Wiring ............................19 General wiring guidelines......................19 6.1.1 Mechanical connection of the base modules ................19 Terminal configuration.......................21 Connecting the module ......................25 Technical details ........................26 Order reference ........................28 Product............................28 Accessories..........................28 Operating Manual PSSu E AI SHT1 1001465-EN-07...
Introduction Validity of documentation This documentation is valid for the products PSSu E AI SHT1 and PSSu E AI SHT1-T. It is valid until new documentation is published. This operating manual explains the function and operation, describes the installation and provides guidelines on how to connect the product.
It also highlights areas within the text that are of particular import- ance. INFORMATION This gives advice on applications and provides information on special fea- tures. Operating Manual PSSu E AI SHT1 1001465-EN-07...
– Evaluation via analogue input module with an input resistance = 115 Ohm, (e.g. PSSu E F AI I), order no.: 312 260) For standard and failsafe applications in system environment A and B T-type: PSSu E AI SHT1-T: for increased environmental requirements Operating Manual PSSu E AI SHT1 1001465-EN-07...
– 2D code 2: Labelling strip for the terminal configuration on the base module 3: Name of electronic module 4: Connection level 1 5: Connection level 2 6: Connection level 3 7: Connection level 4 Operating Manual PSSu E AI SHT1 1001465-EN-07...
Page 8
9: Round connection holes (connection levels 1, 2, 3 and 4) for connecting the signal lines 10: Mounting slot for colour marker to label the connection level (connection levels 1, 2, 3 and 4) Operating Manual PSSu E AI SHT1 1001465-EN-07...
Standard applications The module may be used for standard applications. Particular application areas Increased environmental requirements The module PSSu E AI SHT1-T is suitable for use where there are increased environ- mental requirements (see Technical details [ 26]). EMC-compliant installation Intended use includes making the electrical installation EMC-compliant.
Page 10
We recommend that you always use the latest version of the software tool (download from www.pilz.com). Base modules The PSSu E AI SHT1 module may be used in conjunction with the following base modules: PSSu BP 1/8 S PSSu BP 1/8 C...
In safety-related applications, please comply with the mission time T in the safety-related characteristic data. When decommissioning, please comply with local regulations regarding the disposal of electronic devices (e.g. Electrical and Electronic Equipment Act). Operating Manual PSSu E AI SHT1 | 11 1001465-EN-07...
16 26 Module features 4.2.1 Functions The electronic module PSSu E AI SHT1 contains two shunts for scaling an input current I (connection I0). The two current outputs I (connection O0+) and I (connection O1+) are evaluated by analogue current inputs.
Page 13
R = 5 mA Output current I at R = 2.5 mA I O 0 I I 0 O 0 + I O 1 O 1 + O 0 - O 1 - Operating Manual PSSu E AI SHT1 | 13 1001465-EN-07...
Please refer also to the PSSuniversal Installation Manual. 5.1.1 Dimensions Base modules with four connection levels: 12,6 mm 8,1 mm 52,1 mm (0.496") (0.319") (2.051") 12,6 mm 72,6 mm (0.496") (2.858") Operating Manual PSSu E AI SHT1 | 14 1001465-EN-07...
Page 15
Installation Base modules with six connection levels: 12,6 mm 8,1 mm 52,1 mm (0.496") (0.319") (2.051") 12,6 mm 72,6 mm (0.496") (2.858") Operating Manual PSSu E AI SHT1 | 15 1001465-EN-07...
Push the base module back [2] until you hear it lock into position. On the mounting rail, slide the base module to the left until you hear the two lateral mounting hooks on the adjacent module lock into position [3]. Schematic representation: Operating Manual PSSu E AI SHT1 | 16 1001465-EN-07...
The mechanics of the electronic modules are designed for 50 plug in/out cycles. 5.3.1 Inserting an electronic module Procedure: The electronic module must audibly lock into position [1]. Mark the electronic module using the labelling strips [2]. Schematic representation: Operating Manual PSSu E AI SHT1 | 17 1001465-EN-07...
It is possible to change an electronic module during operation. However, changing an elec- tronic module during operation may cause an ST communication error. The configuration data is retained when a module is changed. Operating Manual PSSu E AI SHT1 | 18 1001465-EN-07...
– Insert the stripped cable into the round fixing hole [2], as far as it will go. – Tighten up the screw on the screw terminal. – Check that the cable is firmly seated. Operating Manual PSSu E AI SHT1 | 19 1001465-EN-07...
Page 20
– Inputs/outputs on the counter modules: 1.5 mm (AWG16) – Analogue inputs/outputs: 1.5 mm (AWG16) – Communication cables: 1.5 mm (AWG16) – Test pulse outputs: 1.5 mm (AWG16) – Power supply: 2.5 mm (AWG12) – Functional earth: 2.5 mm (AWG12) Operating Manual PSSu E AI SHT1 | 20 1001465-EN-07...
21: Output O1+ PSSu BP 1/8 C PSSu BP 1/8 C-T 12: Output O0- 22: Output O1- 13-23: Shield connection (13-23 linked within the base module) 14: Input I0 24: 0 V analogue Operating Manual PSSu E AI SHT1 | 21 1001465-EN-07...
Page 22
PSSu BP-C 1/8 C PSSu BP-C 1/8 C-T 12: Output O0- 22: Output O1- 13-23: C-rail supply, shield connection (13-23 linked within the base module) 14: Input I0 24: 0 V analogue Operating Manual PSSu E AI SHT1 | 22 1001465-EN-07...
Page 23
13-23: Shield connection (13-23-16-26 linked within the base module) 14: Input I0 24: 0 V analogue 15: Output O0- 25: Output O1- 16-26: Shield connection (13-23-16-26 linked within the base module) Operating Manual PSSu E AI SHT1 | 23 1001465-EN-07...
Page 24
(13-23-16-26 linked within the base module) 14: Input I0 24: 0 V analogue 15: Output O0- 25: Output O1- 16-26: C-rail supply, shield connection (13-23-16-26 linked within the base module) Operating Manual PSSu E AI SHT1 | 24 1001465-EN-07...
PSSu E F AI I n.c. n.c. PSSu E AI SHT1 PSSu E F AI I PSSu E AI SHT1 NOTICE Input I0 must be protected with a circuit breaker F1, 1 A, characteristic C. Operating Manual PSSu E AI SHT1 | 25 1001465-EN-07...
Output variable error at 25 ℃ Environmental data 312261 314261 Climatic suitability EN 60068-2-1, EN 60068-2-14, EN EN 60068-2-1, EN 60068-2-14, EN 60068-2-2, EN 60068-2-30, EN 60068-2-2, EN 60068-2-30, EN 60068-2-78 60068-2-78 Operating Manual PSSu E AI SHT1 | 26 1001465-EN-07...
Page 27
12,6 mm 12,6 mm Depth 60,2 mm 60,2 mm Weight 30 g 29 g Mechanical coding Type Colour Light grey Light grey Where standards are undated, the 2022-01 latest editions shall apply. Operating Manual PSSu E AI SHT1 | 27 1001465-EN-07...
Base module with C-rail and screw terminals, T-type 314620 PSSu BP-C 1/12 C Base module with C-rail and cage clamp terminals 312621 PSSu BP-C 1/12 C-T Base module with C-rail and cage clamp terminals, T-type 314621 Operating Manual PSSu E AI SHT1 | 28 1001465-EN-07...