E T C I n s t a l l a t i o n G u i d e
It is recommended that stations and sensors be placed with in 50 feet (15m) of the UASRR
controller for optimal performance.
Typical Radio Range
Material
Line of sight
Line of sight
Plasterboard
Brick
Concrete
FerroConcrete
Ceiling
N o t e :
Signal Loss
Material
Wood/Plaster/Glass
Brick/MDF
Metal
Installation
The UASRR is mounted directly to an electrical wiring compartment at the lighting load or
before the load in the circuit.
N o t e :
W A R N I N G :
W A R N I N G :
Step 1:
Step 2:
Step 3:
Unison Aero Slimline Dual Relay Controller Page 2 of 4
Range - typical
100 feet (30m) corridors
330 feet (100m) open halls
100 feet (30m) through 5 walls
65 feet (20m) through 3 walls
65 feet (20m) through 3 walls
33 feet (10m)
1 ceiling
When you install the UASRR in a fixture with multiple ballasts, a
reduced range can be expected.
Attenuation
0-10%
5-35%
90-100%
If the circuit will have an additional hard wired switch, wire the
UASRR in series before the switch.
Risk of electric shock! The UASRR utilizes high voltage and
should only be installed by a qualified installer or electrician.
Follow all local codes for installation. Before terminating the AC
power wiring verify the main breaker is in the off position and
follow the proper lockout/tag out procedures per NFPA
Standard 70E.
For indoor use only! Must install in an electrical junction box or
wire way.
Locate the circuit breaker panel and turn off the power to the circuit.
Remove covers and other hardware from the fixture or wiring compartment,
gaining access to the high voltage wiring.
The UASRR mounts in the ballast wiring compartment of most fixtures using
two screws (not included).
Unison Aero Power Series
Electronic Theatre Controls, Inc.
Need help?
Do you have a question about the Unison Aero Slimline Dual Relay Controller and is the answer not in the manual?
Questions and answers