Specifications - Omron S8VM Product Manual

Switch mode power supply
Hide thumbs Also See for S8VM:
Table of Contents

Advertisement

Specifications

Ratings/Characteristics
Item
Efficiency
5-V models
12-V models
15-V models
24-V models
Input
Voltage (See note 1.)
Frequency (See note 1.)
Current
100-V input
200-V input
Power factor
100-V input
200-V input
Harmonic current emissions
Leakage current
100-V input
200-V input
Inrush current
100-V input
(See note 2.)
200-V input
Output
Voltage adjustment range (See note 3.)
Ripple
Input variation influence
Load variation influence (rated input voltage) 0.8% max. (with rated input, 0 to 100% load)
Temperature variation influence
Start up time (See note 2.)
Hold time (See note 2.)
Additional
Overload protection (See note 2.)
functions
Overvoltage protection (See note 2.)
Undervoltage alarm indication
Undervoltage alarm output
Power failure alarm indication
Power failure alarm output
Series operation
Parallel operation
Remote sensing function
Other
Ambient operating temperature
Storage temperature
Ambient operating humidity
Dielectric strength
Insulation resistance
Vibration resistance
Shock resistance
Output indicator
EMI
Conducted Emission
Radiated Emission
EMS
Approved standards
Weight (See note 7.)
Note: 1. Do not use the Inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal temperature of the Power
Supply may result in ignition or burning.
2. Refer to the Engineering Data (15-W, 30-W, 50-W, 100-W, 150-W Models) section on page 9 to 11 for details.
3. If the V. ADJ adjuster is turned, the voltage will increase by more than +20% of the voltage adjustment range.
When adjusting the output voltage, confirm the actual output voltage from the Power Supply and be sure that the load is not damaged.
4. To reset the protection, turn OFF the input power for three minutes or longer and then turn it back ON.
5. Conducted emissions: The noise value is affected by factors such as the wiring method. The Power Supply conforms to Class B when the aluminum plate is laid under
the Power Supply. For 15-W models, insert a clamp filter (ZCAT2436-1330 by TDK: 50
6. Radiated emissions: The noise value is affected by factors such as the wiring method. The Power Supply conforms to Class B when the aluminum plate is laid under the
Power Supply. For 150-W models, insert a clamp filter (ZCAT2017-0930 by TDK: 35
7. The weight indicated is for bottom mounting, open-frame models.
8. A@: Sinking type (NPN)
P@: Sourcing type (PNP)
Power rating
15 W
75% min.
78% min.
78% min.
80% min.
100 to 240 VAC (85 to 264 VAC)
50/60 Hz (47 to 63 Hz)
0.5 A max.
0.25 A max.
---
---
---
0.4 mA max. (at rated output)
0.75 mA max. (at rated output)
17.5 A max. (for cold start at 25 C)
35 A max. (for cold start at 25 C)
20% to 20% (with V. ADJ) (S8VM-@@@24A@/P@: 10% to 20%)
3.2% (p-p) max. (5 V),
1.5% (p-p) max. (12 V),
1.2% (p-p) max. (15 V),
1.0% (p-p) max. (24 V),
(at rated input/output voltage)
0.4% max. (at 85 to 264 VAC input, 100%)
0.02%/ C max.
1,100 ms max. (at rated input/output voltage) 800 ms max. (at rated input/output voltage)
20 ms typ. (15 ms min.) (at rated input/output voltage)
105% to 160% of rated load current, voltage
drop, intermittent, automatic reset
Yes (See note 4.)
Yes (color: yellow (DC LOW1), red (DC LOW2)) (S8VM-@@@24A@/P@ only)
No
No
No
Yes
No
No
Refer to the derating curve in Engineering Data (15-W, 30-W, 50-W, 100-W, 150-W Models). (with no icing or con-
densation) (See note 2.)
25 to 65 C
30% to 85% (Storage humidity: 25% to 90%)
3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 20 mA)
2.0 kVAC for 1 min. (between all inputs and PE/FG terminals; detection current: 20 mA)
500 VAC for 1 min. (between all outputs and PE/FG terminals; detection current: 100 mA)
500 VAC for 1 min. (between all outputs (except the detection output terminals) and detection output terminals; de-
tection current: 20 mA) (S8VM-@@@24A@/P@ only)
100 M
min. (between all outputs and all inputs, PE/FG terminals) at 500 VDC
10 to 55 Hz, 0.375-mm single amplitude for 2 hours each in X, Y, and Z directions
2
150 m/s
, 3 times each in X, Y, Z directions
Yes (color: green)
Conforms to EN61204-3 EN55011 Class B and based on FCC Class B (See note 5.)
Conforms to EN61204-3 EN55011 Class B (See note 6.)
Conforms to EN61204-3 High severity levels
UL: UL508 (Listing), UL60950-1, UL1604 (Class I/Division 2, Listing)
CSA: cUL: C22.2 No.14, No.213 (Class I/Division 2), cUR: No. 60950-1
EN: EN50178, EN60950-1
SELV (EN60950-1)
According to VDE0160/P100
180 g max.
30 W
50 W
75% min.
80% min.
79% min.
79% min.
79% min.
79% min.
81% min.
80% min.
0.9 A max.
0.8 A max.
0.45 A max.
0.4 A max.
0.98 min.
0.94 min.
Conforms to EN 61000-3-2
3.2% (p-p) max. (5 V),
1.5% (p-p) max. (12 V),
1.2% (p-p) max. (15 V),
0.75% (p-p) max. (24 V),
(at rated input/output voltage)
105% to 160% of rated load current,
voltage drop (12 V, 15 V, and 24 V),
voltage drop, intermittent (5 V), automatic reset
Yes (S8VM-@@@24A@/P@ only)
(Transistor output), 30 VDC max., 50 mA max. (See note 8.)
SEMI-F47 (200 VAC input)
220 g max.
290 g max.
min. [50 to 500 MHz], or the equivalent) in the output wire to reduce noise.
min. [50 to 500 MHz], or the equivalent) in the input wire to reduce noise.
Switch Mode Power Supply
100 W
150 W
81% min.
81% min.
81% min.
81% min.
81% min.
81% min.
82% min.
83% min.
1.4 A max.
2.0 A max.
0.7 A max.
1.0 A max.
Yes
460 g max.
530 g max.