Remote Control Function - Omron S8VM Product Manual

Switch mode power supply
Hide thumbs Also See for S8VM:
Table of Contents

Advertisement

Remote Control Function

This function turns outputs ON and OFF using an external signal
while input voltage is applied, using the +RC pin (pin 7 on CN) and
the -RC pin (pin 8 on CN). Connect a switch or transistor to the +RC
and -RC pins to use the remote control function. When not using this
function, the +RC and -RC pins are shorted by using the standard
supplied connector.
S8VM
CN
RC Level for RC
Short or L (0 to 0.8 V) ON
Open or H (2.4 to 12 V) OFF
Maximum input voltage: 12 V max.
Maximum allowable reverse voltage: 1 V max.
Sink Current: 3.5 mA
Note: 1. Use 2-conductor shielded cable or twisted-pair cable as
connection wire.
2. The remote control circuit is isolated from the input and out-
put circuits of the power supply.
3. Remove the standard supplied connector and prepare a
connector separately.
Power Failure Alarm Function
The power failure alarm indicator will light red to indicate an output
voltage error if overload, overvoltage, or overheat protection is acti-
vated, if a drop in the input voltage causes the output voltage to drop,
if the built-in fan motor stops, and during remote control standby. The
alarm is also output externally by a transistor.
Transistor output: 30 VDC max., 50 mA max.
Residual voltage when ON: 2 V max.
Leakage current when OFF: 0.1 mA max.
Alarm detection voltage: Approx. 80% of output voltage setting
During detection, the transistor is OFF (with no continuity across pins
11 and 12 on CN), and the LED (red) lights.
CN
S8VM
Note: 1. This function monitors the voltage at the Power Supply out-
put terminals. To check actual voltage, measure the voltage
on the load side.
2. Outputs are forced OFF if the built-in fan motor stops
(S8VM-15224C only).
3. Remove the standard supplied connector and prepare a
connector separately.
16
Switch Mode Power Supply
RC
SW
TR
RC
Output
Built-in Fan Motor
Rotate
Stop
PF-C
Vce max.: 30 VDC
PF-E
Ic max.: 50 mA
S8VM
Inrush Current, Start Up Time,
Output Hold Time
Input ON
AC input
voltage
Inrush current on input application
AC input
current
Output
voltage
Start up time
Input Current Waveform When
Input Is Turned ON
(The following examples show typical waveforms.)
S8VM-300@@C
100 VAC, Load ratio: 100%
100 ms
AC input
current
(10 A/DIV)
Output
voltage
AC input
voltage
200 VAC, Load ratio: 100%
100 ms
AC input
current
(10 A/DIV)
Output
voltage
AC input
voltage
Input OFF
95%
90%
Hold time

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents