Inrush Current; Leakage Current - Omron S8TS Product Manual

Switch mode power supply
Hide thumbs Also See for S8TS:
Table of Contents

Advertisement

Series Operation
24/12-V models
5-V models
L
N
L
N
S8T
-BUS02
Load
Load
Adjusting Output Voltage for Parallel
Operation
The Blocks are factory-set to the rated output voltage. When adjust-
ing voltages, set the same values for Blocks with V.ADJ before linking
them together. Adjust the set values within the limits given in the fol-
lowing table.
Model number
S8TS-06024@
0.24 V max.
S8TS-03012@
0.12 V max.
Do not adjust voltages after Blocks are linked together. The output
voltage may become unstable.
± Output
24/12-V models 5-V models
L
N
L
N
S8T
-BUS02
Load
Load
Load
Load
Difference between output
voltages

Inrush Current

The inrush current per Basic Block is 25 A max. at 100 VAC and 50 A
max. at 200 VAC. When N Blocks are linked together, the inrush cur-
rent will be equal to N times that for 1 Basic Block. Be sure to use a
fuse with the appropriate fusing characteristics or a breaker with the
appropriate tripping characteristics.

Leakage Current

The leakage current per Basic Block is 0.35 mA at 100 VAC and
0.7 mA at 240 VAC. When N Blocks are linked together, the leakage
current will be equal to N times that for 1 Basic Block.
Mounting
Mounting Direction
Standard mounting
Face-up mounting
Other mounting methods
Use standard mounting only. Using any other mounting method will
prevent proper hear dissipation and may result in deterioration or
damage of internal elements.
Standard mounting
Switch Mode Power Supply
Yes
No
No
Face-up mounting
S8TS
L-31