Charging Batteries - Omron S8TS Product Manual

Switch mode power supply
Hide thumbs Also See for S8TS:
Table of Contents

Advertisement

Operating and Storage Environments
Do not use or store the Power Supply in the following locations.
Doing so may result in failure, malfunction, or deterioration of perfor-
mance characteristics.
• Do not use in locations subject to direct sunlight.
• Do not use in locations where the ambient temperature exceeds
the range of the derating curve.
• Do not use in locations where the humidity is outside the range
25% to 85%, or locations subject to condensation due to sudden
temperature changes.
• Do not store in locations where the ambient temperature is outside
the range –25 to 65°C or where the humidity is outside the range
25% to 95%.
• Do not use in locations where liquids, foreign matter, corrosive
gases, or flammable gases may enter the interior of products.

Charging Batteries

If a battery is connected as the load, provide an overcurrent control
circuit and an overvoltage protective circuit.
Output Voltage Adjuster (V.ADJ)
Do not exert excessive force on the output voltage adjuster (V.ADJ).
Doing so may break the adjuster.
Setting the adjuster to a setting less than 10% may cause the under-
voltage detection function to operate.
Bus Line Connectors
Do not apply sudden shocks (e.g., by dropping) to the Bus Line Con-
nectors. Doing so may result in damage.
DIN Track Mounting
To mount the Block on a DIN track, hook portion (A) of the Block onto
the track and press the Block in direction (B).
To dismount the Block, pull down portion (C) with a flat-blade screw-
driver and pull out the Block.
C
No Output Voltage
If there is no output voltage, it is possible that overcurrent protection
or overvoltage protection is operating. It is also possible that the latch
protection circuit is operating due to the application of a large surge,
such as lightning surge. Confirm the 2 points below. If there is still no
output voltage, consult your OMRON representative.
• Checking for Overcurrent Protection:
Separate the load line and confirm that it is not in an overcurrent
state (including short-circuits).
• Checking for Overvoltage Protection or Latch Protection:
Turn the input power supply OFF, and then turn it ON again after 1
minute or more has elapsed.
Switch Mode Power Supply
A
B
30 mm min.
Track stopper
S8TS