Note: You can store only two codes: multi-step speed reference 0 (A020) and 2nd multi-step speed
4

Forced Operator Function

This function forcibly switches to operation via the Digital Operator by turning on/off the multi-
function terminal if the frequency reference/RUN command sources are not set to the Digital
Operator.
Data
Symbol
31
Related parameters
Related codes
•If you switch on/off this function during operation, the RUN command is reset to stop the Inverter.
Before resuming operation, stop the RUN command from each command source to avoid possible
danger and then input it again.

Forced Terminal Block Function

This function forcibly switches to operation via the terminal block by turning on/off the multi-function
terminal if the frequency reference/RUN command sources are not set to the terminal block.
Data
51
Related parameters
Required settings
•When the input of this signal is reset, A001 and A002 return to the command status prior to the
input.
•If you switch on/off this function during operation, the RUN command is reset to stop the Inverter.
Before resuming operation, stop the RUN command from each command source to avoid possible
danger and then input it again.
4-54
reference 0 (A220). Even with C101 set to 01, you cannot store the multi-step speeds 1 to 7
adjusted with the UP/DWN function. To store them, press the Enter key as well.
RUN commands
(FW, RV)
UP
DWN
Output
frequency
Function name
OPE
Forced operator
Symbol
Function name
F-TM
Forced terminal block
Acceleration/Deceleration does
not function if the UP and DWN
terminals turn on simultaneously.
Status
Prioritizes the command from the Digital Operator (A020,
ON
A220 set values) over the A001 and A002 settings.
OFF
Operates according to the A001 and A002 settings.
C001 to C005
A001, A002
Status
ON
Forcibly sets A001 = 01 and A002 = 01.
OFF
Operates according to the A001 and A002 settings.
C001 to C005
A001, A002
Description
Description