Setting the Motor Capacity Selection (H003) and Motor Pole Number Selection
(H004)
Parameter
Register
No.
No.
H003
1165h
3
H004
1166h
Key sequence
(In approx. 1 s)
3-6
Name
Description
Sets the capacity of the
Motor capacity
motor connected to the
selection
Inverter.
Motor pole
Sets the pole number of the
number
motor connected to the
selection
Inverter.
Display example
b---
h---
h003
0.20
0.40
0.40
h003
Setting range
200-V class
0.2/0.4/0.75/
1.5/2.2/3.7/
5.5/7.5
400-V class
0.4/0.75/1.5/
2.2/3.7/5.5/7.5
2/4/6/8
Description
Press the Mode key twice to display the mode selection.
Use the Increment or Decrement key to display "H---".
Press the Mode key. "H003" is displayed.
Press the Mode key. The set value in "H003" is displayed.
Use the Increment or Decrement key to set the rated motor capacity.
Press the Enter key. The set value is entered.
The parameter number is displayed again.
Change
Unit of
Default
during
setting
setting
RUN
Varies with
kW
the
No
capacity.
Pole
4
No