Setting Parameters in the Initial Setting Level
Parameter Settings Related to Protective Functions
Alarm Level
Alarms for which Alarm
Output Contacts Can Be
Assigned
Note
Setting Procedure
Parameter
Alarm Output Open in Alarm
External Input Range Alarm
External Duty Input Alarm Operation
Load Current Upper Limit
Number of Alarms for Heater Burnout
Detection [P09] (See note 1.)
Heater Burnout Alarm Operation
[P14] (See note 1.)
The G3PW Power Controller has two alarm contact outputs: Alarm output 1
(ALARM1) and alarm output 2 (ALARM2).
For the following alarms, the contacts to which to output an alarm when an
error occurs can be selected with a parameter setting in the initial setting
level.
Alarm level
No alarm
Alarm level 1
Alarm level 2
Note Errors will not be detected if no alarm output is assigned.
• Heater burnout alarm (E40)
• External input range alarm (external variable resistor disconnection
detection) (E50)
• External duty input alarm (external variable resistor disconnection detec-
tion) (E51)
• Total run time exceeded alarm (E60)
(1) If multiple errors occur, the most recent error will be displayed on the 7-
segment display. (For details on error numbers, refer to 7-2 Error Dis-
plays.)
(2) Errors other than the above are set to alarm level 1 and cannot be
changed.
Output mode
Proportional to
Proportional to
phase angle
square voltage
(same as G3PX)
[P12]
[P17]
[P18]
Function OFF
[P10]
[P10] = 0.0#
Parameter
setting
level
0
No error is detected.
1
The alarm is output to alarm output 1.
The output to the load is stopped when a fatal
error is detected, and the error is displayed on
the 7-segment display.
2
The alarm is output to alarm output 2.
The error is displayed on the 7-segment display
and operation continues.
Proportional
Constant-
to voltage
current control
Operation for
Operation for
NO contacts
or
NC contacts
[P12] = 1#
[P12] = 0
When the external main setting variable resistor is disconnected
or when outside the range of 4 to 20 mA or 1 to 5 V.
No alarm
Alarm level 1
Alarm level 2
[P17] = 0
[P17] = 1
When the external duty variable resistor is disconnected or when
outside the range of 4 to 20 mA or 1 to 5 V.
No alarm
Alarm level 1
Alarm level 2
[P18] = 0
[P18] = 1
or
Current limit
specification
[P10] = 0.1 to 66.0
Number of errors to detect before detecting a heater burnout
(1 = Power supply half cycle)
[P09] = 0 to 999 (150 errors)
No alarm
Alarm level 1
or
or
[P14] = 0#
[P14] = 1
Note 1: Constant-current Models only.
Note 2: The alarm status is not determined for 1 s after startup.
Section 4-6
Operation
Optimum cycle
ON/OFF control
control
(See note 2.)
[P17] = 2
[P18] = 2
Function
Function OFF
Current limit
or
OFF
setting
[P10] = *
[P10] = 0.0#
Alarm level 2
[P14] = 2
#: Default
*: Setting disabled
[P10] = 0.1
to 66.0
45