Input Ranges; Alarm Types - Omron E5CWL Connections

Hide thumbs Also See for E5CWL:
Table of Contents

Advertisement

Input Ranges

Models with Thermocouple Inputs
Model
(temperature input)
TC input
Default setting: 0
Applicable standards (K, J, T, R, S): JIS C1602-1995 and IEC 60584-1
Models with Resistance Thermometer Inputs
Model
(temperature input)
Pt input
Default setting: 8
Applicable standards (Pt100): JIS C1604-1997 and IEC 60751

Alarm Types

Select alarm types out of the 11 alarm types listed in the following
table.
Setting
Alarm type
0
No alarm
Deviation upper/
1
lower limit
Deviation upper
2
limit
Deviation lower
3
limit
Deviation upper/
4
lower range
5
Deviation upper/
(See
lower limit standby
note.)
sequence ON
6
Deviation upper
(See
limit standby
note.)
sequence ON
7
Deviation lower
(See
limit standby
note.)
sequence ON
Absolute value
8
upper limit
Absolute value
9
lower limit
10
Absolute value
(See
upper limit standby
note.)
sequence ON
11
Absolute value
(See
lower limit standby
note.)
sequence ON
12
Do not set.
Arrow.com.
Arrow.com.
Arrow.com.
Downloaded from
Downloaded from
Downloaded from
Range
Set value
Input type
C
200 to 1,300
0
K
20.0 to 500.0
1
100 to 850
2
J
20.0 to 400.0
3
200 to 400
4
T
199.9 to 400.0
5
6
R
0 to 1,700
7
S
0 to 1,700
Range
Set value
Input type
C
8
-200 to 850
Pt100
9
-199.9 to 500.0
Positive alarm
Negative alarm
value (X)
value (X)
Output OFF
X
X
ON
Always ON
OFF
SP
X
X
ON
ON
OFF
OFF
SP
SP
X
X
ON
ON
OFF
OFF
SP
SP
X
X
ON
Always OFF
OFF
SP
X
X
ON
Always OFF
OFF
SP
X
X
ON
ON
OFF
OFF
SP
SP
X
X
ON
ON
OFF
OFF
SP
SP
X
X
ON
ON
OFF
OFF
0
X
X
ON
ON
OFF
OFF
0
X
X
ON
ON
OFF
OFF
0
X
X
ON
ON
OFF
OFF
0
F
300 to 2,300
0.0 to 900.0
100 to 1500
0.0 to 750.0
300 to 700
199.9 to 700.0
0 to 3,000
0 to 3,000
F
-300 to 1500
-199.9 to 900.0
Note: Alarms with a Standby Sequence
The alarm is blocked until the first safe-state is reached.
Unwanted alarm during start-up are prevented.
Example: Deviation Lower Limit Standby Sequence ON
Alarm with standby sequence
Alarm without standby sequence
The standby sequence is cleared when the alarm OFF condition has
been met.
The standby sequence is started again when any of the following
conditions is met.
 Operation is started (power is turned ON or operation is switched
from stop to run).
 The alarm value is changed.
 The temperature input offset is changed.
 The set point is changed.
0
0
0
0
E5CSL/E5CWL/E5EWL
Alarm value
Process value
Standby sequence cleared
Alarm hysteresis
(always 0.2 °C/°F)
Time
3