Setting List - Omron E5EK User Manual

Digital controller
Hide thumbs Also See for E5EK:
Table of Contents

Advertisement

APPENDIX

SETTING LIST

Mode
Parameter Name
Security
Protect
Protect
[A/M] key protect
Manual
Manual MV
Set point
Level 0
Level 0
Run/Stop
AT Execute/Cancel
Set point 0
Set point 1
Set point 2
Set point 3
Alarm value 1
Alarm value 2
Alarm value 3
Proportional band
Integral time
Derivative time
Level 1
Level 1
Cooling coefficient
Dead band
Position-proportional
dead band
Manual reset value
Hysteresis (heat)
Hysteresis (cool)
Control period (heat)
Control period (cool)
Heater burnout
Remote/Local
SP mode
SP ramp time unit
SP ramp set value
LBA detection time
MV at stop
MV at PV error
MV upper limit
Level 2
MV lower limit
MV change rate limit
Input digital filter
Open/close hysteresis
Alarm 1 hysteresis
Alarm 2 hysteresis
Alarm 3 hysteresis
Input shift upper limit
Input shift lower limit
*1 During heat and cooling control, the lower limit becomes -105.0%.
During position-proportional control the setting becomes HOLD, OPEN or CLOS.
*2 During heat and cooling control, the setting range becomes 0.0 to 105.0%.
*3 During heat and cooling control, the setting range becomes -105.0 to 0.0%.
A--8
Setting Range
0 to 6
ON/OFF
-5.0 to 105.0
Set point lower limit to Set point upper limit
Run/Stop
OFF/AT-1/AT-2
Set point lower limit to Set point upper limit
Set point lower limit to Set point upper limit
Set point lower limit to Set point upper limit
Set point lower limit to Set point upper limit
-1999 to 9999
-1999 to 9999
-1999 to 9999
0.1 to 999.9
0 to 3999
0 to 3999
0.01 to 99.99
-19.99 to 99.99
0.1 to 10.0
0.0 to 100.0
0.01 to 99.99
0.01 to 99.99
1 to 99
1 to 99
0.0 to 50.0
RMT/LCL
RSP/LSP
M(Minutes) / H(Hours)
0 to 9999
0 to 9999
-5.0 to 105.0
-5.0 to 105.0
MV lower limit + 0.1 to 105.0
-5.0 to MV upper limit -0.1
0.0 to 100.0
0 to 9999
0.1 to 20.0
0.01 to 99.99
0.01 to 99.99
0.01 to 99.99
-199.9 to 999.9
-199.9 to 999.9
Unit
Default
None
1
None
OFF
%
0.0
*1
EU
0
None
RUN
None
OFF
During running
EU
0
Multi-SP
EU
0
Multi-SP
EU
0
Multi-SP
EU
0
Multi-SP
EU
0
EU
0
EU
0
%FS
10.0
sec
233
sec
40
At heating and
None
1.00
cooling control
At heating and
%FS
0.00
cooling control
At position-propor-
%
2.0
tional control
%
50.0
%FS
0.10
At heating and
%FS
0.10
cooling control
sec
20
At heating and
sec
20
cooling control
Heater burnout
A
0.0
detection
Communications
None
LCL
unit setting
None
LSP
None
M
EU
0
*1
Sec
0
*1
%
0.0
*2
%
0.0
*3
%
105.0
%
-5.0
%/sec
0.0
sec
0
%
0.8
%FS
0.02
%FS
0.02
%FS
0.02
0.0
Temperature input
°C/°F
0.0
Temperature input
°C/°F
Remarks
Setting