Heater Current Monitor; Heater Burnout - Omron E5EK User Manual

Digital controller
Hide thumbs Also See for E5EK:
Table of Contents

Advertisement

Heater current monitor

• Measures the current value of the heater from CT input.
Function
Monitor Range
0.0 to 55.0
• [
Monitor
F Related article
4.5 How to Use the Heater Burnout Alarm (page 4-13)
F Related parameters
See
"Heater burnout" (level 1 mode) "HBA latch" (option mode)
E5EK-AA2 AC100-240
E5EK-AA2 AC/DC24
Model

Heater burnout

• Outputs the heater burnout alarm when the heater current value falls below this
parameter setting.
• When the set value is "0.0", the heater burnout alarm is "OFF". When the set
Function
value is "50.0", the heater burnout alarm is "ON".
Setting Range
0.0 to 50.0
Comment
F Related article
4.5 How to Use the Heater Burnout Alarm (page 4-13)
F Related parameters
See
"Heater current monitor" (level 1 mode) "HBA latch" (option mode)
E5EK-AA2 AC100-240
E5EK-AA2 AC/DC24
Model
Unit
A
] is displayed when 55.0 A is exceeded.
Unit
A
Level 1 Mode
Conditions of Use
The HBA output function must be
assigned.
Conditions of Use
The HBA output function must be
assigned.
Default
0.0
5--17