Omron E3X-DRT21-S User Manual page 54

E3x-da-s series, e3x-mda series communication unit for digital type sensor
Hide thumbs Also See for E3X-DRT21-S:
Table of Contents

Advertisement

Section 3
Explicit Message Communications
● Read threshold settings/read threshold settings on differentiation
mode/read threshold settings on difference outputs
These commands read threshold settings of the sensor with the unit No. specified with
the Instance ID. Data is shown in hexadecimal, and the data for each single unit is 16-
bits long. If the data is negative, the 12th bit is 1 (on).
Threshold settings
Bit
Bit
15
14
0 Fixed
Depending on the sensor type, [Read Differentiation Threshold Settings] and [Read
Difference Threshold Settings] might not be able to be performed correctly.
● Read Operating Mode Settings
It reads the operating mode settings of the sensor with the unit No. specified with the
Instance ID.
Bit
00
01 to 15
E3X-DRT21-S
52
User's Manual
Bit
Bit
Bit
Bit
Bit
13
12
11
10
09
0:
+
/
1:
-
Description
Operating mode
No data
Bit
Bit
Bit
Bit
08
07
06
05
Threshold setting (0000Hex to 0FA0Hex)
E3X, E3C: 0: L/ON, 1: D/ON; E2C: 0: NO, 1: NC
Always 0
Bit
Bit
Bit
Bit
Bit
04
03
02
01
00
Data