Omron E3X-DRT21-S User Manual page 43

E3x-da-s series, e3x-mda series communication unit for digital type sensor
Hide thumbs Also See for E3X-DRT21-S:
Table of Contents

Advertisement

■ Remote I/O Communications 2CH Mode (SW1=ON, SW2=OFF)
Up to 16 sensors can be connected. The IN area occupies 2CH of the master.
mCH
Bit
Description
00
Unit No. 1 ON/OFF output data
01
Unit No. 2 ON/OFF output data
02
Unit No. 3 ON/OFF output data
03
Unit No. 4 ON/OFF output data
04
Unit No. 5 ON/OFF output data
05
Unit No. 6 ON/OFF output data
06
Unit No. 7 ON/OFF output data
07
Unit No. 8 ON/OFF output data
m + 1CH
Bit
Description
00
Number of connected sensors (2
01
Number of connected sensors (2
02
Number of connected sensors (2
03
Number of connected sensors (2
04
Number of connected sensors (2
05
Always 0
06
Always 0
07
Always 0
• Number of connected sensors:
The number of currently registered sensors is shown in a range from 1 to 10 in
hexadecimal (between 1 and 16 in decimal).
• Number of sensors that can be communicated with:
The number of current sensors that can be communicated with is shown in a range from
0 to 10 in hexadecimal (between 0 and 16 in decimal).
When failure occurs, you can confirm how many sensors are communicating normally.
• Sensor communications error:
When the registered number of connected sensors doesn't match the number of sensors
that can be communicated, or when communications with a sensor fail after the
connection with the sensor is established, it is turned ON.
• Communicating with a sensor: When the communication with a sensor is established, it
is turned ON.
DeviceNet Remote I/O Communications
Bit
08
09
10
11
12
13
14
15
Bit
0
)
08
Number of sensors that can be communicated with (2
1
)
09
Number of sensors that can be communicated with (2
2
)
10
Number of sensors that can be communicated with (2
3
)
11
Number of sensors that can be communicated with (2
4
)
12
Number of sensors that can be communicated with (2
13
Communicating with the Mobile Console
14
Sensor communications error
15
Communicating with Sensor
Description
Unit No. 9 ON/OFF output data
Unit No. 10 ON/OFF output data
Unit No. 11 ON/OFF output data
Unit No. 12 ON/OFF output data
Unit No. 13 ON/OFF output data
Unit No. 14 ON/OFF output data
Unit No. 15 ON/OFF output data
Unit No. 16 ON/OFF output data
Description
E3X-DRT21-S
User's Manual
Section 3
0
)
1
)
2
)
3
)
4
)
41

Advertisement

Table of Contents
loading

Table of Contents