Dst1-Md16Sl-1; Safety Input Specifications; Test Output Specifications; Safety Output Specifications For Semiconductor Outputs - Omron DEVICENET SAFETY - 03-2008 Operation Manual

Safety i/o terminals
Table of Contents

Advertisement

DST1-MD16SL-1

5-2

DST1-MD16SL-1

5-2-1

Safety Input Specifications

5-2-2

Test Output Specifications

5-2-3

Safety Output Specifications for Semiconductor Outputs

IMPORTANT In case that a safety output is configured as Safety pulsed test, while this out-
The following table gives the safety input specifications for the DST1-
MD16SL-1.
Item
Input type
ON voltage
OFF voltage
OFF current
Input current
The following table gives the test output specifications for the DST1-MD16SL-
1.
Item
Output type
Rated output current
Residual voltage
Leakage current
The following table gives the safety output specifications for the Semiconduc-
tor outputs on the DST1-MD16SL-1.
Item
Output type
Rated output current
Residual voltage
Leakage current
put is in an ON state, the signal sequence shown below is output continuously
to enable diagnosis. Confirm the response times of the devices connected to
the safety outputs so that the devices do not malfunction due to the OFF
pulse.
ON
OFF
Sinking input (PNP)
11 VDC min. between each input terminal
and G0
5 VDC max. between each input terminal and
G0
1 mA max.
6 mA
Sourcing output (PNP)
0.7 A
1.2 V max. between each output terminal and
V0
0.1 mA max.
Sourcing output (PNP)
0. 5 A
1.2 V max. between each output terminal and
V1
0.1 mA max.
580 µs
typical
Section 5-2
Specifications
Specifications
Specifications
648 ms
typical
63