Remote I/O Allocations
CS/CJ-series DeviceNet Unit
Note
Using a Standard Master That Cannot Actively Change the Default Standard I/O
Assembly Data
1,2,3...
Note
A CS/CJ-series DeviceNet Unit can change I/O assembly data, so there is no
need to use this function to change the default standard I/O assembly data.
Even if this function is used to change the data, the CS/CJ-series DeviceNet
Unit settings will be given priority.
For details on making these settings, refer to the CS/CJ-series DeviceNet Unit
Operation Manual (Cat. No. W380).
Set the initial standard I/O assembly data (Default Connection Path) when
using the Network Configurator to set the configuration.
1. Open the Edit Device Parameters Window of the DST1-XD0808SL-1.
From Default Connection Path, select the I/O assembly data for the type of
connection (Poll, BitStrobe, COS, Cyclic) to be used for I/O communica-
tions with the Standard Master. "Null" means that I/O assembly data is not
to be used, i.e., that the data size is 0 bytes.
Check that extended display is set.
2. Download the specified configuration to the DST1-XD0808SL-1.
3. Set the Standard Master so that the connection type (Poll, BitStrobe, COS,
or Cyclic) and I/O data size agree with the settings that were made in step
1 above.
"Null" means that I/O assembly data is not used, i.e., that the data size is 0
bytes. The output connection size for a Bit-Strobe connection is always 0
bytes.
Make selections for the input connection and output
connection to be used.
Section 3-2
51