Using Digital Input + Fieldbus - CD Automation REVEX 1PH User Manual

Hide thumbs Also See for REVEX 1PH:
Table of Contents

Advertisement

REVEX
1PH from 60A to 90A

13.5 Using Digital Input + FieldBus

The static unit as an option can be ordered with a FieldBus (Ex: profinet).
This option continuously writes the values on the unit keeping them up to date.
The external contact Sw
to enable the static unit, both contacts must be enabled.
Using the FieldBus it is possible to change the status of the Sw
(See the communication manual of the respective FieldBus), bearing in mind that the Sw
be closed to enable it.
This configuration is useful for having an external contact for a safety or emergency alternative to the FieldBus.
Sw
H
Sw
= Switch hardware
H
NOTE:
The parameters written are:
• command table
• reference
• rescaling
if the FieldBus is active but disconnected these values will be forced to 0.
and the internal software contact Sw
H
Software switch
from communication
External
DI
Contact
DI Con gurated like "Enable" function
are connected in series, therefore if you want
S
contact with bit 2 of the "Command table"
S
Sw
S
Instrument Enable
Sw
= Switch software
S
59
User's manual
contact must also
H

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the REVEX 1PH and is the answer not in the manual?

Questions and answers

This manual is also suitable for:

M-rx1-60-90

Table of Contents