13.5 Using Digital Input + FieldBus
The static unit as an option can be ordered with a FieldBus (Ex: profinet).
This option continuously writes the values on the unit keeping them up to date.
The external contact Sw
to enable the static unit, both contacts must be enabled.
Using the FieldBus it is possible to change the status of the Sw
(See the communication manual of the respective FieldBus), bearing in mind that the Sw
be closed to enable it.
This configuration is useful for having an external contact for a safety or emergency alternative to the FieldBus.
Sw
H
Sw
= Switch hardware
H
NOTE:
The parameters written are:
• command table
• reference
• rescaling
if the FieldBus is active but disconnected these values will be forced to 0.
and the internal software contact Sw
H
Software switch
from communication
External
DI
Contact
DI Con gurated like "Enable" function
are connected in series, therefore if you want
S
contact with bit 2 of the "Command table"
S
Sw
S
Instrument Enable
Sw
= Switch software
S
59
User's manual
contact must also
H