Brine; Water - Daikin RZAG71N V1B Series Installer's Reference Manual

Hide thumbs Also See for RZAG71N V1B Series:
Table of Contents

Advertisement

2
|
General safety precautions

2.1.4 Brine

2.1.5 Water

Installer reference guide
12
If
A siphon tube is present
(i.e., the cylinder is marked with "Liquid
filling siphon attached")
A siphon tube is NOT present
Open refrigerant cylinders slowly.
Charge the refrigerant in liquid form. Adding it in gas form may prevent normal
operation.
CAUTION
When the refrigerant charging procedure is done or when pausing, close the valve of
the refrigerant tank immediately. If the valve is NOT closed immediately, remaining
pressure might charge additional refrigerant. Possible consequence: Incorrect
refrigerant amount.
If applicable. See the installation manual or installer reference guide of your
application for more information.
WARNING
The selection of the brine MUST be in accordance with the applicable legislation.
WARNING
Take sufficient precautions in case of brine leakage. If brine leaks, ventilate the area
immediately and contact your local dealer.
WARNING
The ambient temperature inside the unit can get much higher than that of the room,
e.g. 70°C. In case of a brine leak, hot parts inside the unit can create a hazardous
situation.
WARNING
The use and installation of the application MUST comply with the safety and
environmental precautions specified in the applicable legislation.
If applicable. See the installation manual or installer reference guide of your
application for more information.
NOTICE
Make sure water quality complies with EU directive 2020/2184.
Then
Charge with the cylinder upright.
Charge with the cylinder upside down.
RZAG71~140N
Sky Air Alpha-series
4P695307-1A – 2024.02