Summary of Contents for Daikin RZASG71M2V1B

  • Page 1: Installation Manual

    Installation manual Sky Air Advance-series RZASG71M2V1B     RZASG100M7V1B     RZASG125M7V1B     RZASG140M7V1B                            RZASG100M7Y1B     Installation manual RZASG125M7Y1B     English Sky Air Advance-series RZASG140M7Y1B...
  • Page 2 (mm) — ≥100 A, B, C — ≥250 ≥100 ≥100 B, E — ≥100 ≥1000 ≤500 A, B, C, E — ≥250 ≥150 ≥150 ≥1000 ≤500 — ≥500 D, E — ≥500 ≥1000 ≤500 B, D — ≥100 ≥500 B, D, E <H ≤½H ≥250...
  • Page 3 2P472847-4...
  • Page 4 2P472847-4...
  • Page 5 2P472847-2...
  • Page 6 2P472847-2...
  • Page 7: Table Of Contents

    About the refrigerant ........... 11 Daikin website (publicly accessible). 4.4.3 To determine the additional refrigerant amount ..12 ▪ The full set of latest technical data is available on the Daikin 4.4.4 To determine the complete recharge amount ..... 12 extranet (authentication required).
  • Page 8: Preparation

    3 Preparation NOTICE Preparation Fix the outdoor unit to the foundation bolts using nuts with resin washers (a). If the coating on the fastening area is Preparing installation site stripped off, the nuts rust easily. WARNING The appliance shall be stored in a room without continuously operating ignition sources (example: open 4.1.2 To install the outdoor unit...
  • Page 9: To Prevent The Outdoor Unit From Falling Over

    4 Installation 4× Ø6 mm 4× Ø6 mm          2 Remove the burrs, and paint the edges and areas around the edges using repair paint to prevent rusting. 4 Do the following: ▪ Connect the liquid pipe (a) to the liquid stop valve. 4.1.4 To prevent the outdoor unit from falling ▪...
  • Page 10: Checking The Refrigerant Piping

    4 Installation NOTICE NOTICE Do not block the air vents. This could affect air circulation Make sure to use a recommended bubble test solution inside the unit. from your wholesaler. Do not use soap water, which may cause cracking of flare nuts (soap water may contain salt, which absorbs moisture that will freeze when the piping gets cold), and/or lead to corrosion of flared joints (soap water may contain ammonia which causes a corrosive...
  • Page 11: About The Refrigerant

    4 Installation Charging additional refrigerant Before charging additional refrigerant, make sure the outdoor unit's external refrigerant piping is checked (leak test, vacuum drying). INFORMATION Depending on the units and/or the installation conditions, it might be necessary to connect electrical wiring before you can charge refrigerant.
  • Page 12: To Determine The Additional Refrigerant Amount

    4 Installation Examples WARNING The refrigerant inside the unit is mildly flammable, but Layout Additional refrigerant amount (R) normally does not leak. If the refrigerant leaks in the room L2=7 m Case: Twin, standard liquid pipe size (Ø6.4 mm) and comes in contact with fire from a burner, a heater, or a 1 G1 Total Ø9.5 =>...
  • Page 13: To Completely Recharge Refrigerant

    ▪ R32 contains fluorinated greenhouse gases. Its global 4.5.1 About electrical compliance warming potential (GWP) value is 675. Do NOT vent these gases into the atmosphere. RZASG71M2V1B + RZASG100~140M7V1B ▪ When charging refrigerant, always use protective Equipment complying with EN/IEC  61000‑3‑12 (European/ gloves and safety glasses.
  • Page 14: Specifications Of Standard Wiring Components

    4 Installation Item Tightening torque (N•m) Item Tightening torque (N•m) M4 (earth) 1.2~1.4 M5 (earth) 2.4~2.9 M5 (X1M) 2.0~3.0 If limited space is available at the wire terminal, use bended crimp- style ring terminals. 4.5.3 Specifications of standard wiring components Component 125+140 Power supply cable...
  • Page 15: Finishing The Outdoor Unit Installation

    5 Commissioning Connecting to the When cables are routed from the unit, a 4.6.2 To close the outdoor unit frame protection sleeve for the conduits (PG insertions) can be inserted at the knockout hole. When you do not use a wire conduit, protect the wires with vinyl tubes to prevent the edge of the knockout hole from cutting the wires.
  • Page 16: To Perform A Test Run

    5 Commissioning The following field wiring has been carried out according Action Result to this document and the applicable legislation: Go to the home menu. Cool ▪ Between the local supply panel and the outdoor unit Set to ▪ Between the outdoor unit and the indoor unit (master) °C ▪...
  • Page 17: Error Codes When Performing A Test Run

    6 Disposal Action Result Press. The unit returns to normal operation, and the home menu is displayed. Error codes when performing a test run If the installation of the outdoor unit has NOT been done correctly, the following error codes may be displayed on the user interface: Error code Possible cause Nothing displayed...
  • Page 18: Technical Data

    7 Technical data Technical data A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is available on the Daikin extranet (authentication required). Overview: Technical data This chapter contains information about: •...
  • Page 19: Piping Diagram: Outdoor Unit

    7 Technical data Piping diagram: Outdoor unit Heat sink (PCB) Capillary tube Electronic expansion valve 4‑way valve High pressure switch Low pressure switch Compressor accumulator Heat exchanger Compressor Charge port / Service port (with 5/16" flare) Distributor Stop valve Liquid receiver Filter Check valve Flare connection...
  • Page 20 7 Technical data Printed circuit board (noise filter) L*, L*A, L*B, NA, NB, Connector E*, U, V, W, X*A BS1~BS3 (A1P) Push button switch (A1P~A2P) C1~C5 (A1P) (Y1 Capacitor only) DS1 (A1P) Dipswitch Bottom plate heater (option) Fuse HAP (A1P) Light-emitting diode (service monitor is green) K1M, K3M (A1P) (Y1...