LED Annunciator Installation (LED-4410G3)

The panel supports up to ten (10) LED-4410G3 Annunciators.The LED-4410G3 displays alarm, supervisory, and trouble
conditions for up to16 zones per annunciator. They also provide Local Silence and Lamp Test functionality. Blank zone labels
are provided for use with the LED annunciators to label each zone name or identifier. The labels may be printed or written on the
supplied card-stock, and then inserted into the back of the front panel as shown in the right-most figure below.
Figure 26. LED-4410G3 Module Showing Front Panel & Board
Zone labels
e
will display her
The LED-4410G3 is controlled over the 4-wire P-Link connection. The higher current required for the LED outputs can be
provided by the panel, or from an auxiliary power source as shown below. The auxiliary power can be any 24VDC source, and is
fully supervised.
Figure 27. Examples of Wiring LED-4410G3 Module to Control Panel or Auxiliary Power Supply
Example:
Powered by
control panel
LED PWR
P -Link
-
+
-
+
A
P-Link from
control panel
VFR-500 • 5403789 • REV A • 10/23
DWG # FIG 2
Example:
Powered by
aux supply
LED PWR
P -Link
B
-
+
-
+
P-Link from
Power from
control panel
auxiliary
supply
A
B
DWG #608-6
3-28
Labels are inserted here
as needed
DWG #608-5