Section 5: Programming Options

The control panel can be configured using the on-board keypad or PC based programming tool. The panel stores the
site specific configuration data in non-volatile memory.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for Control Units and
Accessories for Fire Alarm Systems, UL 864 and ULC S527, certain programming features or options must be limited to specific values or not used at all as
indicated below.
Topic
Feature or Option
Misc
Idle LCD Message
Misc
Display Events
Misc
Waterflow Delay
Misc
AC Report Delay
Misc
Door Holder Low AC
Dropout Delay
Misc
Strobes Active When
Silenced
Misc
Disable 24 hours PZT
Resound
Misc
Display AM/PM
Misc
Synchronize to
Network Time
Misc
SNTP Server
Misc
Time Zone
Misc
DST Enabled
Misc
DST Start
Misc
DST End
Zone
Zone Style
Zone
Silenceable
Zone
Silence Inhibit
Zone
Auto Silence
Zone
Auto Unsilence
VFR-500 • 5403789 • REV A • 10/23
Permitted
Possible Settings
in UL
(Y/N)
Y
Yes/No
Y
Initial Event
Newest Event
Y
0-255 Sec
Y
0 Minutes, .5 - 30 hours
Y
No delay, 15 Sec, 1 minute,
5 minute
Y
Yes/No
Y
Yes/No
Y
Yes/No
Y
Yes/No
Y
North-America.Pool.NTP.org
Y
24 Time Zone Selections
Y
Yes/No
Y
Month/Day
Y
Month/Day
Y
Alarm
Supervisory
Waterflow
Trouble
Releasing
Releasing Confirmation
Unused
System Alarm
System Supervisory
Y
Yes/No
Y
0-60 minutes
Y
3-360 minutes
Y
0-60 minutes
5-35
Setting(s)
Permitted
in UL864 / S527
All Settings Allowed
Initial Event
Auto display first event
0-90 sec
1-3 Hours
All Settings Allowed
All Settings Allowed
No
All Settings Allowed
No = 24hour clock
All Settings Allowed
All Settings Allowed
All Settings Allowed
All Settings Allowed
All Settings Allowed
All Settings Allowed
All Settings Allowed
All Settings Allowed
All Settings Allowed
3-60 UL864
Shall be set in accordance
S527 (see comment)
with section 3.2.4.6 of the
National Building Code of
Canada
All Settings Allowed
Comment