Section 7: Appendices; Appendix A: System Maintenance And Testing - Viking VFR-500 Installation And Operation Manual

Conventional releasing panel
Hide thumbs Also See for VFR-500:
Table of Contents

Advertisement

Section 7: Appendices

Appendix A: System Maintenance and Testing

Testing the panel or associated devices may result in a discharge of the suppression system. All necessary precautions shall be taken to prevent an
unwanted activation of the suppression system. Read, understand and follow all testing instructions as well as all cautions, warnings and notices
associated with the suppression system and this panel before beginning any testing or servicing.
Acceptance Test
The control panel is required to be installed in accordance with local and state building codes and NFPA 72 (For Canada: ULC Standard
CAN/ULC-S536). At the conclusion of each original installation or modification of this system, the control panel and related system is
required to be inspected and tested in accordance with NFPA 72 (For Canada: ULC Standard CAN/ULC-S536) to verify compliance
with the applicable standards.
Testing shall be conducted by personnel trained in the operation of this panel and the suppression system it is operating. Testing shall
be conducted in in the presence of a representative of the Authority Having Jurisdiction (AHJ) and the building owners representative.
Refer to NFPA 72 (National Fire Alarm Code), Inspection Testing and Maintenance chapter. For Canada refer to ULC Standard CAN/
ULC-S536
Periodic Testing and Service
Periodic testing and maintenance of the control panel, all initiating points, all notification appliances and any other associated equipment
is essential to ensure the system will operate as designed in emergency situations. Service and test the control panel according to the
schedules and procedures outlined in the following documents:
NFPA 72, Inspection, Testing and Maintenance chapter. (For Canada refer to ULC Standard CAN/ULC-S536 )
Service manuals and instructions for any and all peripheral points installed in the system. It is very important that any and all trouble
conditions (or faults) be corrected immediately.
Operational Checks
During interim periods between formal testing and at regular intervals the control system should be subjected to the following
operational performance checks. The Authority Having Jurisdiction (AHJ) should be consulted for requirements on frequency of
system testing.
Check that the green AC power LED is lit.
Check that all amber LED's are off.
Using the system menus, perform a Lamp Test function. Verify that all LED's operate.
Before proceeding: (1) Disable the suppression system to prevent an unwanted discharge of the suppression system. (2) Notify
the fire department and the central alarm receiving station if transmitting alarm status conditions; (3) Notify facility personnel of
the test so that alarm-indicating points are disregarded during the test period; and (4) When necessary, bypass activation of alarm
notification appliances and speakers (if installed) to prevent sounding of evacuation signals.
Activate an input device (i.e., manual station, heat or smoke detector), and check that all notification appliances function.
Notify Fire Department, central alarm receiving station and /or building personnel when finished with testing the system.
The test of ground fault must be measured in below 10k ohms impedance.
Make certain that the panel and all releasing devices are in a non-alarm/unactivated condition.
Restore the suppression system back to service
Replacement and Testing Recommendations
The batteries are to be replaced at least once every four years or more frequently if specified by local AHJ and manufacturer
recommendations. Batteries should be dated at the installation. Minimal replacement battery capacity displays on the control panel
marking label. The batteries are required to be UL Recognized batteries with a date of manufacture permanently marked on the battery.
The battery is to be tested at least annually and if the battery is showing signs of failure, it should be replaced. Immediately replace a
damaged or leaking battery, and always replace batteries in pairs.
Proper Handling / First Aid Procedures
In the event a battery leaks and contact is made with the Sulfuric Acid, immediately wash skin with water for at least 15 minutes.
Water and household baking soda provides a good neutralizing solution for Sulfuric Acid.
If Sulfuric Acid makes contact with eyes, flush with water for 15 minutes and seek immediate medical attention.
Ensure proper handling of the battery to prevent short-circuits.
Take care to avoid accidental shorting of the leads from uninsulated work surfaces, tools, jewelry and coins.
If a battery is shorted, the battery and any connected equipment may be damaged. Additionally, a short may injure personnel
VFR-500 • 5403789 • REV A • 10/23
CAUTION
A-42
.

Advertisement

Table of Contents
loading

Table of Contents