Setting Address; Idc-6 Wiring Configuration - Viking VFR-500 Installation And Operation Manual

Conventional releasing panel
Hide thumbs Also See for VFR-500:
Table of Contents

Advertisement

Setting Address

The IDC-6's address is set by dip switch S1 (as shown below). The address must be set in the range of one to thirty-one (1–31) to
be recognized by the panel. (Refer to the "P-Link Addresses" table shown earlier in this section for DIP switch programming.)
Figure 20. IDC-6 Dip Switch locations
Input Wiring Specification
Maximum short circuit current = 47mA
Maximum wiring resistance = 100 Ohms
Maximum wiring capacitance = 1 mF
Maximum wire length in feet = 10,000 feet
Normal standby current = 2.5 mA
IDC operating voltage range = 15VDC – 28VDC

IDC-6 Wiring Configuration

The IDC-6's may be configured and installed as Class B or Class A. Please refer to the following examples:
Figure 21. Example of IDC-6 Class A Wiring
INPUT 1
+
Input Circuit Class A Notes:
1.
Maximum wiring resistance must not exceed 100 ohms.
2.
The input has ground fault detection with 0 ohm impedance to ground.
VFR-500 • 5403789 • REV A • 10/23
-
+
-
+
A
B
IDC PWR
P LINK
INPUT 2
INPUT 3
-
+
-
+
-
Dip Switch S1
Normally Open Contact
INPUT 5
INPUT 6
INPUT 4
+
-
+
-
+
3-24
-