Notes on Operation
9 Notes on Operation
9.1 Parallel Connection
In parallel operation, set the output voltage of the products that will be connected in paral-
lel to precisely the same value, if possible. The resistance of the conductors between the
product and the load must be nearly identical. Only connect products of the same type in
parallel.
Use external rail-mount terminal blocks when connecting in parallel. A parallel connection
directly on the connectors on the secondary side of the product is not allowed.
To decouple the outputs in parallel mode, a suitable redundancy module or diodes in the
positive path are recommended. These diodes must be designed for the product's maxi-
mum output current.