Notes On Operation; Insulation Testing; Disable/Enable Overvoltage Protection; Inrush Current - WAGO Power Supply Pro 2 Manual

Hide thumbs Also See for Power Supply Pro 2:
Table of Contents

Advertisement

Notes on Operation

Notes on Operation
10

10.1 Insulation Testing

Before the electrical system is put into operation, insulation testing must be performed.
You can find more detailed information in the following standards, for example:
• DIN VDE 0100-600 VDE 0100-600:2017-06 "Low-voltage electrical installations – Part
 6: Verification"
• IEC 60364-6:2016 "Low voltage electrical installations – Part 6: Verification"
To protect the product against damage during this testing, it is necessary to disable the
overvoltage protection. You can find more information in section
Overvoltage Protection

10.2 Disable/Enable Overvoltage Protection

The product is protected against overvoltage (for more information, see section
voltage Protection
The letters shown in parentheses refer to positions in the "View" figure in section
[} 12].
Disable Overvoltage Protection
Remove the screw (i) on the side of the product.
ð The overvoltage protection is disabled.
Enable Overvoltage Protection
Screw in the screw (i) on the side of the product.
ð The overvoltage protection is enabled.

10.3 Inrush Current

High inrush currents can occur if multiple products are supplied through the same circuit
on the input side. In this case, it is advisable to switch the WAGO Power Supply Pro 2 on
with a delay. The corresponding switch-on delay can be parameterized in the
Settings [} 41]
ware.
The maximum number of products that can be operated in parallel on one circuit is given
by the sum of the leakage currents. According to EN 62368-1, this sun must not exceed
the maximum value of 3.5 mA.

10.4 Derating

The maximum load is a function of the surrounding air temperature and the installation al-
titude.
52
Product manual | Version: 1.0.0
Power Supply Pro 2
[} 52].
[} 28]).
dialog in the "System" section of the WAGO Interface Configuration soft-
2787-2147
8 Disable/Enable
8 Over-
8 View
8 Dialog:

Advertisement

Table of Contents
loading

This manual is also suitable for:

2787-2147

Table of Contents