INSTALLATION
GAS PIPE PRESSURE TESTING
The appliance must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any
pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig. (3.45 kPa). Disconnect piping
from valve at pressures over 1/2 psig.
The manifold pressure Is controlled by a regulator built into the gas control, and should be checked at the pressure test point.
Note: To properly check gas pressure, both inlet and manifold pressures should be checked using the valve pressure
ports on the valve.
1)
Make sure the valve is in the "OFF" position.
2}
Loosen the "IN" and/or "OUT" pressure tap(s), turning counterclockvwse wth a 1/8" wide fiat screwdriver.
3)
Attach manometer to "IN" and/or "OUT" pressure tap(s) using a 5/16" ID hose.
4)
Light the pilot and turn the valve to "ON" position. Read manometer.
5)
The pressure check should be carried out with the unit burning and the setting should be v\^hin the limits specified on the
safety label.
6) . When finished reading manometer, turn off the gas valve, disconnect the hose and tighten the screw (clockwise) with a 1/
8" flat screwdriver. Note: Screw should be snua. but do not over tighten
Vaive Description
1)
Gas cock knob
8) Pilot Outlet
2)
Manual high^ow adjustment
9) Main Gas Outlet
3)
Pilot Adjustment
10) Flange Securing Screw Holes
4)
Thermocouple Connection
11) Alternative TC Connection Point
5)
Main Operator
12) Thermoelectric Unit
6)
Outlet Pressure Tap (Manifold Pressure)
13) Additional Valve Mounting Hole
7)
Inlet Pressure Tap (Supply Pressure)
16
U27-1 Regency ULTIMATE Rear Vent Direct Vent Freestanding Gas Heater